The information contained in this operation and maintenance manual is subject
to change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including
but not limited to implied warranties of merchantability and fitness for a particular
application. AERCO International is not liable for errors appearing in this manual.
Nor for incidental or consequential damages occurring in connection with the
furnishing, performance, or use of this material.
Printed in U.S.A. REVISED 12/10
CONTENTS
Para.
Subject
Page
1.1
Warnings & Cautions
1-1
1.2
Emergency Shutdown
1-2
Para.
Subject
Page
1.3
Prolonged Shutdown
1-2
Para.
Subject
Page
2.1
Receiving the Unit
2-1
2.2
Unpacking
2-1
2.3
Installation
2-2
2.4
Gas Supply Piping
2-4
2.5
Electrical Supply
2-5
Para.
Subject
Page
2.6
Field Control W iring
2-6
2.7
Flue Gas Vent Installation
2-9
2.8
Combustion Air
2-9
Para.
Subject
Page
3.1
Introduction
3-1
3.2
Control Panel Description
3-1
3.3
Control Panel Menus
3-3
3.4
Operating Menu
3-4
3.5
Setup Menu
3-4
Para.
Subject
Page
3.6
Configuration Menu
3-6
3.7
Tuning Menu
3-7
3.8
Start Sequence
3-7
3.9
Start/Stop Levels
3-9
Para.
Subject
Page
4-1
Initial Startup Requirements
4-1
4-2
Tools and Instrumentation for
Combustion Calibration
4-1
4-3
Combustion Calibration
4-2
Para.
Subject
Page
4-4
Propane Combustion Calibration
4-5
4.5
Unit Reassembly
4-5
4.6
Temperature Control Calibration
4-6
4.7
Over-Temperature Limit Switch
Adjustments
4-7
GF-111 THE AERCO KC1000 GAS FIRED DOMESTIC WATER HEATER
Operating & Maintenance Instructions
FOREWARD A
Section 1 – SAFETY PRECAUTIONS 1-1
Section 2 – INSTALLATION PROCEDURES 2-1
Section 3 – CONTROL PANEL OPERATING PROCEDURES 3-1
Section 4 – INITIAL START-UP 4-1
i
CONTENTS
Para.
Subject
Page
5.1
Testing of Safety Devices
5-1
5.2
Low Gas Pressure Fault Test
5-1
5.3
High Gas Pressure Test
5-1
5.4
Low Water Level Fault Test
5-2
5.5
Water Temperature Fault Test
5-2
5.6
Interlock Tests
5-3
5.7
Flame Fault Test
5-3
5.8
Air Flow Fault Test
5-4
Para.
Subject
Page
5.9
SSOV Proof of Closure Switch
5-4
Purge
5.11
Ignition Switch Open During
5-5
5.12
Safety Pressure Relief Valve
Test
5-6
Para.
Subject
Page
6.1
Maintenance Schedule
6-1
6.2
Spark Ignitor
6-1
6.3
Flame Detector
6-2
6.4
Combustion Calibration
6-2
6.5
Safety Device Testing
6-2
6.6
BTU Transmitter Pump
Lubrication
6-2
Para.
Subject
Page
6.7
BTU Transmitter Assembly
6-3
6.8
Manifold and Exhaust Tubes
6-5
6.9
Heat Exchanger Inspection
6-8
6.10
Condensate Drain Assembly
6-9
Para.
Subject
Page
7.1
Introduction
7-1
Para.
Subject
Page
App
Subject
Page
A
Water Heater Menu Item
Descriptions
A-1
B
Startup, Status and Fault
Messages
B-1
C
Temperature Sensor Resistance
Chart
C-1
D
Water Heater Default Settings
D-1
App
Subject
Page
E
Dimensional and Parts Drawings
E-1
F
Piping Drawings
F-1
G
Wiring Schematics
G-1
H
KC1000 Control Panel Views
H-1
Section 5 – SAFETY DEVICE TESTING PROCEDURES 5-1
5.10 Purge Switch Open During
Ignition
5-5
Section 6 – MAINTENANCE 6-1
Section 7 – TROUBLESHOOTING 7-1
APPENDICES
WARRANTIES W-1
ii
FOREWORD
Foreword
The AERCO KC Water Heating System is a true industry advance that meets the needs of
today's energy and environmental concerns. Designed for use in any potable water heating
system, it provides constant temperature water, regardless of flow rate. It’s small space
requirements and venting capabilities allow maximum installation flexibility. The KC Heater’s
load tracking controls modulate over a 20:1 turndown ratio for natural gas units and a 14:1
turndown ratio for propane units to match fluctuating system loads and yield high thermal
efficiencies.
With it’s compact design and direct or chimney venting, the KC Water Heating System is
adaptable to any installation. Efficiency, reliability and longevity make the KC Water Heating
System a true step forward in Water Heating System design.
After prolonged shutdown, it is recommended that the startup procedures in Section 4 and test
procedures in Section 5 of this manual be performed to verify system operating parameters. If
there is an emergency, turn off the electrical power supply to the KC Heater or close the
manual gas valve located before the unit. The installer is to identify the emergency shut-off
device. FOR SERVICE OR PARTS, contact your local sales representative or AERCO
INTERNATIONAL.
Installers and operating personnel MUST, at all
times, observe all safety regulations. The
following warnings and cautions are general and
must be given the same attention as specific
precautions included in these instructions. In
addition to all the requirements included in this
AERCO Instruction Manual, the installation of
units MUST conform with local building codes,
or, in the absence of local codes, ANSI Z223.1
(National Fuel Gas Code Publication No. NFPA-
54) for gas-fired heaters and ANSI/NFPASB for
LP gas-fired heaters. Where applicable, the
equipment shall be installed in accordance with
the current Installation Code for Gas Burning
Appliances and Equipment, CGA B149, and
applicable Provincial regulations for the class;
which should be carefully followed in all cases.
Authorities having jurisdiction should be
consulted before installations are made.
See pages 1-2 and 1-3 for important
information regarding installation of units
within the Commonwealth of Massachusetts.
IMPORTANT
This Instruction Manual is an integral part of
the product and must be maintained in
legible condition. It must be given to the user
by the installer and kept in a safe place for
future reference.
IMPORTANT
Read the following restrictions prior to
installing the water heater:
1. The heater can only be used for
applications where the chlorine
concentrations Do Not Exceed 4 mg/L
which is the Environmental Protection
Agency limit for chlorine
concentrations in drinking water.
2. Do Not use this heater for a pool
heating application.
3. If this heater was ordered with the
optional copper-lined, carbon steel
shell, items 1 and 2 Do Not Apply.
(Contact your local AERCO
representative to verify heater shell
material.
WARNINGS!
MUST BE OBSERVED TO PREVENT
SERIOUS INJURY.
WARNING!
BEFORE ATTEMPTING TO PERFORM ANY MAINTENANCE ON THE
UNIT, SHUT OFF ALL GAS AND
ELECTRICAL INPUTS TO THE UNIT.
WARNING
DO NOT USE MATCHES, CANDLES,
FLAMES, OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS
LEAKS.
WARNING!
THE EXHAUST VENT PIPE OF THE
UNIT OPERATES UNDER A POSITIVE PRESSURE AND THEREFORE MUST BE COMPLETELY
SEALED TO PREVENT LEAKAGE
OF COMBUSTION PRODUCTS INTO
LIVING SPACES.
WARNING!
FLUIDS UNDER PRESSURE MAY
CAUSE INJURY TO PERSONNEL
OR DAMAGE TO EQUIPMENT
WHEN RELEASED. BE SURE TO
SHUT OFF ALL INCOMING AND
OUTGOING WATER SHUTOFF
VALVES. CAREFULLY DECREASE
ALL TRAPPED PRESSURES TO
ZERO BEFORE PERFORMING
MAINTENANCE.
WARNING!
ELECTRICAL VOLTAGES OF 120
VAC ARE USED IN THIS EQUIPMENT. THEREFORE THE COVER
ON THE UNIT’S POWER BOX
(LOCATED ON THE FRONT RIGHT
SIDE OF THE UNIT UNDER THE
HOOD AND SHEET METAL SIDE
PANEL) MUST BE INSTALLED AT
ALL TIMES, EXCEPT DURING
MAINTENANCE AND SERVICING.
1-1
SAFETY PRECAUTIONS
MANUAL GAS SHUTOFF VALVE
VALVE OPEN
VALVE CLOSED
CAUTIONS!
Must be observed to prevent equipment
damage or loss of operating effectiveness.
CAUTION!
Many soaps used for gas pipe leak testing
must
are corrosive to metals. The piping
rinsed thoroughly with clean water after leak
checks have been completed.
be
CAUTION!
DO NOT use this heater if any part has been
under water. Call a qualified service
technician to inspect and replace any part
that has been under water.
1.2 EMERGENCY SHUTDOWN
If overheating occurs or the gas supply fails to
shut off, close the manual gas shutoff valve
(Figure 1-1) located external to the unit.
IMPORTANT
The Installer must identify and indicate the
location of the emergency shutdown manual
gas valve to operating personnel.
1.3 PROLONGED SHUTDOWN
After prolonged shutdown, it is recommended
that the startup procedures in Chapter 4 and the
safety device test procedures in Chapter 5 of
this manual be performed, to verify all systemoperating parameters. If there is an emergency,
turn off the electrical power supply to the
AERCO heater and close the manual gas valve
located upstream the unit. The installer must
identify the emergency shut-off device.
Water heater Installations within the Commonwealth of Massachusetts must conform to the
• Heater must be installed by a plumber or a gas fitter who is licensed within the Commonwealth of
• Prior to unit operation, the complete gas train and all connections must be leak tested using a
• The vent termination must be located a minimum of 4 feet above grade level.
• If side-wall venting is used, the installation must conform to the following requirements extracted
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or
structure used in whole or in part for residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
Figure 1-1
Manual Gas Shutoff Valve
IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS
following requirements:
Massachusetts.
non-corrosive soap.
from 248 CMR 5.08 (2):
1-2
SAFETY PRECAUTIONS
INSTALLATION OF CARBON MONOXIDE DETECTORS
1.
horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas
equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the
dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be
the responsibility of the property owner to secure the services of qualified licensed professionals for the
installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be
installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to comply with the above requirements;
provided, however, that during said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
. At the time of installation of the side wall
APPROVED CARBON MONOXIDE DETECTORS.
2.
accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS
certified.
3.
SIGNAGE
building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal
for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no
less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4.
INSPECTION
equipment shall not approve the installation unless, upon inspection, the inspector observes carbon
monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
(b)
EXEMPTIONS
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most
current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or
structure separate from the dwelling, building or structure used in whole or in part for residential
purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED.
(c)
the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting
system design or venting system components with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system
components; and
2. A complete parts list for the venting system design or venting system.
. A metal or plastic identification plate shall be permanently mounted to the exterior of the
. The state or local gas inspector of the side wall horizontally vented gas fueled
: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
Each carbon monoxide detector as required in
When
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
(d)
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does
not provide the parts for venting the flue gases, but identifies "special venting systems", the following
requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or
equipment installation instructions; and
1-3
SAFETY PRECAUTIONS
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for
that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design
instructions shall remain with the appliance or equipment at the completion of the installation.
______________________________________
[End of Extracted Information From 248 CMR 5.08 (2)]
1-4
`SECTION 2 - INSTALLATION
2.1 RECEIVING THE UNIT
Each KC1000 Heater is shipped as a single
crated unit. The shipping weight is approximately
1500 lb. and must be moved with the proper rigging equipment for safety and to avoid damage.
The unit should be completely inspected at the
time of receipt from the carrier before the bill of
lading is signed. Each unit has Tip-N-Tell
indicator on the outside of the crate. This
indicates if the unit has been turned on its side.
If the Tip-N-Tell indicator is tripped, do not sign
for the shipment. Note the information on the
carrier’s paperwork and request a freight claim
and inspection by a claims adjuster before
proceeding. Any other visual damage to the
packaging materials should also be made clear
to the delivering carrier.
2.2 UNPACKING
Carefully unpack the unit. Take care not to
damage the unit jacket when cutting away
packaging materials. A close inspection of the
unit should be made to determine if there has
been any damage incurred during shipment that
was not indicated by the Tip-N-Tell indicator.
The freight carrier should be notified immediately
INSTALLATION
if any damage is detected. The following
accessories come standard with each unit and
are packed separately within the unit’s packing
container
• Spare Spark Ignitor
• Spare Flame Detector
• Manual 1-1/4" Gas Shutoff Valve
• Drain Valve Assembly
• ASME Pressure/Temperature
Relief Valve
• Ignitor Removal Tool (One per Site)
• Regulator Adjustment Tool (One per
Site
• 2 Lifting Lugs
• Stainless Steel Condensate Cup
• Flue Clamps (2 Pieces)
• Shell Cap
• Wing Nut for Shell Cap
Optional accessories are also separately packed
within the unit’s packing container. Standard and
optional accessories shipped with the unit should
be identified and put in a safe place until they are
installed for use.
Figure 2.1 Heater Clearance
2-1
INSTALLATION
2.3 INSTALLATION
The unit must be installed with the prescribed
clearances for service as shown in Fig 2.1 These
are the
by AERCO. Local building codes may require
more clearance and take precedence.
KEEP UNIT AREA CLEAR AND FREE
FROM COMBUSTIBLE MATERIALS AND
FLAMMABLE VAPORS AND LIQUIDS.
MASSACHUSSETTS INSTALLATIONS
For water heater installations within the
Commonwealth of Massachusetts, the heater
must be installed by a plumber or a gas fitter
who is licensed within the Commonwealth. In
addition, the installation must comply with all
requirements specified in Section 1 (Safety
Precautions), pages 1-2 and 1-3.
2.3.1 SETTING THE UNIT
Locate the lifting lugs, shipped with the unit, and
attach them to the 5/8” x 11 studs at the top of
the unit. Remove the unit from the wooden skid
and place in position using a block and tackle or
hoist attached to the lifting lugs. (see Fig. 2.2).
USE THE LIFTING LUGS TO MOVE THE
UNIT.
The KC-1000 is U/L approved for installation on
combustible flooring. A 4” to 6" high housekeeping concrete pad is recommended and
allows for sufficient drainage of the condensate.
The unit must be secured using only the holes
provided in the frame base. Do not use piping to
secure the unit in place. See drawing AP-A-576
in Appendix E for the base frame dimensions.
In multiple unit installations, it is important to plan
the position of each unit. Sufficient space for
piping connections and maintenance requirements must be given. All piping must include
ample provision for expansion.
minimum clearance dimensions required
WARNING !
Figure 2.2
Lifting Lug Location
2.3.2 WATER INLET AND OUTLET
PIPING
The locations of the 2" NPT cold water inlet and
hot water outlet piping connections are shown in
Figure 2.3. Flow rates through the unit are
limited to 30 gpm continuous and 40 gpm
intermittent.
The heater is shipped with a 2” NPT x 12” long
stainless steel flex connector. It is important that
this flex connector be installed at the hot water
outlet as mentioned in the installation diagrams
to ensure compliance with the AERCO warranty.
If it is desired to install the flex connector
elbowed towards the rear or top of the unit, two
additional parts (not supplied with heater) are
required. These parts are a 2”NPT x 6” long 304
or 316 stainless nipple and a 2” NPT 304 or 316
stainless elbow. Both of these parts must be
capable of withstanding up to 155 psig @ 210°F.
These parts may be added between the heater
outlet connection and the flex connector.
However, if this heater was ordered with the
optional copper-lined carbon steel shell (contact
your local AERCO Representative to verify), it is
not shipped with, and does not require a flex
connector.
2-2
INSTALLATION
Shut-off valves and union conections must be
installed in the inlet and outlet lines for maintenance. The use of dielectric unions is recommended. Install the piping and accessories as
per the following drawings, located in Appendix F
of this manual.
• SD-A-424 for single units
• SD-A-425 for multiple units
• SD-A-432 for single units with a stratified
tank
•SD-A-434 for multiple units with a stratified
storage tank
NOTE:
All piping must be arranged so that it does
not interfere with removal of any cover,
inhibit service or maintenance, or prevent
access between the unit and walls, or
another unit.
Figure 2.3
Inlet and Outlet Location
2.3.3 TEST HOSE BIB
A Test Hose Bib connection, upstream of the
shut off valve on the hot water outlet, is required
for startup and testing. It should be a minimum
of 3/4". It cannot be omitted (See Fig. 2.4a)
Figure 2.4a
Hose Bib Location
2.3.4 PRESSURE/TEMPERATURE
RELIEF AND DRAIN
VALVE
INSTALLATION
An ASME rated Pressure/Temperature Relief
Valve is supplied with each unit. The valve
setpoint is 150 psig/210
as shown in Fig. 2.4b. A suitable pipe compound
should be used on the threaded connections.
Any excess should be wiped off to avoid getting
any into the valve body. The relief valve should
be piped to within 12 inches of the floor to
prevent injury in the event of a discharge. The
relief piping must be full size, 1-1/2”, without
reduction. No valves, restrictions, or other
blockages are allowed in the discharge line. In
multiple unit installations the discharge lines
be manifolded together. Each must be
not
must
individually run to a suitable discharge location.
A 1” drain valve assembly is furnished with each
unit. The assembly should be installed as shown
in Figure 2.4b. The drain should be hard piped to
a suitable drain.
°
F. Install the relief valve
2.3.5 SYSTEM RECIRCULATION
The system recirculating line ties into the unit at
the recirculating tee fitting provided in the drain
valve assembly (see Fig. 2.4b). Shut off valves
and union connections are recommended for
maintenance. Recirculation flow rates must be
kept to 8 gpm or less. In a multiple unit
installation, each unit must be tied into the
system recirculation system.
2-3
INSTALLATION
TEMPERATURE SENSOR
EXHAUST
MANIFOLD
CONDENSATE
DRAIN
BURNER
HOSE CLAMP
1-3/4" O.D. x 8-1 /2 “ LG.
SILICONE HOSE
5/8" O.D. TUBE CONN.
CONDENSATE CUP
PLACED ON FLOOR
Figure 2.4b
Pressure/Temperature Relief and Drain
Valve Installation Location
2.3.6 CONDENSATE PIPING
The KC Heater is designed to condense.
Therefore, the installation site must include
suitable provisions for condensate drainage or
collection. A stainless steel condensate cup is
separately packed within unit’s shipping
container. To install the condensate cup,
proceed as follows:
1. Remove the left side panel and only the left
half of the rear cover to provide access to the
exhaust manifold and burner (Figure 2.5).
2. Insert the 1-3/4 inch manifold drain hose into
the condensate cup. Allow the cup to rest on
the floor directly beneath the manifold drain
hole (Figure 2.5).
3. Attach a length of 3/4 inch I.D.polypropylene
tubing to the condensate cup drain tube and
route it to a floor drain. . If a floor drain is not
available, a condensate pump can be used to
remove the condensate to drain. The
condensate drain line must be removable for
routine maintenance. Therefore, DO NOT
hard-pipe.
4. Replace the rear cover and side panel on the
unit.
Figure 2.5
Condensate Drain Assembly Location
2.4 GAS SUPPLY PIPING
AERCO Gas Fired Equipment Gas Components
and Supply Design Guide (GF-1030) should be
consulted before any gas piping is designed or
started.
WARNING !
DO NOT USE MATCHES, CANDLES,
FLAMES OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS LEAKS
.
CAUTION !
Many soaps used for gas pipe leak testing
are corrosive to metals. The piping must be
rinsed thoroughly with clean water after
leak checks have been completed
.
NOTE:
All gas piping must be arranged so that it
does not interfere with removal of any
cover, inhibit service or maintenance, or
prevent access between the unit and walls,
or another unit
The location of the 1-1/4" inlet gas connection
on the right side of the unit is shown in Figure
2.6.
.
2-4
INSTALLATION
W.C. for FM gas train and 8.9” W.C. for IRI
gas trains at 1,000,000 BTU/H for natural
gas and propane units.
The maximum static inlet pressure to the unit
must be no more than 14” W.C.. Minimum gas
pressure is 8.5” W.C. for FM gas trains and 8.9”
W.C. IRI gas trains when the unit is firing at
maximum input. Gas pressure should not
exceed 10.5” W.C. at any time when the unit is
firing. Proper sizing of the gas supply regulator in
delivering the correct gas flow and outlet
pressure is mandatory. The gas supply pressure
regulator must maintain the gas pressure at a
minimum of 8.5” W.C. (FM) or 8.9” W.C. (IRI)
when the unit is at maximum BTU input
(1,000,000 BTU/HR). The supply gas regulator
Figure 2.6
Gas Supply Regulator and Manual Shut -
Off Valve Location
All pipe should be de-burred and internally
cleared of any scale or iron chips prior to
installation. No flexible connectors or nonapproved gas fittings should be installed. Piping
should be supported from floor or walls only and
must not be secured to the unit.
A suitable piping compound approved for use
with gas should be used sparingly. Any excess
must be wiped off to prevent clogging of
components.
To avoid damage to the unit when pressure
testing gas piping, isolate the unit from the gas
supply piping. At no time should there be more
than 1 psig maximum to the unit. Bubble test all
external piping thoroughly for leaks using a soap
and water solution or suitable equivalent. The
gas piping must meet all applicable codes.
2.4.1 GAS SUPPLY PRESSURE
REGULATOR
A mandatory external, in line, supply gas
regulator (supplied by others) should be
positioned as shown in Figure 2.6. Union
connections should be placed in the proper
locations to allow maintenance of the regulator if
required.
NOTE:
An individual gas pressure regulator must
be installed upstream of each unit. The
regulator must regulate gas pressure to 8.5”
must be able to supply sufficient capacity
volume, (1000 cfh), to the unit and should have
no more than 1" droop from minimum to full fire.
The supply gas regulator must also be rated to
handle the maximum incoming gas pressure.
When the gas supply pressure will not exceed
14” W.C. a non-lock up, or flow through style
regulator, may be used. When supply gas
pressure will exceed 14” W.C., a lock up style
regulator must be used. The gas supply
regulator must be propery vented to outdoors.
Consult the local gas utility for exact
requirements concerning venting of supply gas
regulators.
CAUTION!
A lockup style regulator must be used when
gas supply pressure exceeds 14” W.C.
2.4.2 MANUAL GAS SHUTOFF VALVE
A 1-1/4” manual gas shutoff valve is furnished
with each unit and should be positioned as
shown in Figure 2.6. The valve must be installed
upstream of the gas supply regulator in a readily
accessible location.
2.4.3 IRI GAS TRAIN KIT
The IRI gas train is an optional gas train required
in some areas by code or for insurance purposes. The IRI gas train comes pre-assembled
and wired from the factory. See Appendix E,
Drawing SD-A-606.
The IRI gas train may be ordered pre-assembled
or as separate components. If either IRI gas
train option is ordered, a complete instructional
package, detailing field installation will be
included. To obtain a copy of an IRI instructional
package prior to the equipment shipping contact
your local representative or AERCO.
2-5
INSTALLATION
POWER BOX
BLOWER
SSOV
ACTUATOR
FRAME
USE COPPER CONDUCTORS ONLY FOR FIELD WIRING
60 HZ
DISCONNECT POWER BEFORE SERVICING
DANGER: HIGH VOLTAGE
20 AMP
120 VAC,
NEUTRAL
GROUND
LINE
POWER BOX
AERCO INTERNATIONAL INC.
INPUT POWER
2.5 ELECTRICAL SUPPLY
The AERCO Gas Fired Equipment Electrical
Power Wiring Guide, (GF-1060), must be
consulted in addition to the following material
before wiring to the unit is started. AC power
connection to the unit are made at the Power
Box.This box is located on the front right side of
the unit as shown in Figure 2.7.
A means for disconnecting AC power from the
unit (such as a service switch) must be installed
near the unit for normal operation and
maintenance. All electrical connections should
be made in accordance with the National
Electrical Code and/or with any applicable local
codes.
The electrical wiring diagram is shown in Figure
2.8. Conduit should be run from the knockouts in
the side of the box in such a manner that it does
not interfere with the removal of any sheet metal
covers. A flexible electrical connection may be
utilized to allow the covers to be easily removed.
Figure 2.7
AC Power Box Location
NOTE:
All electrical conduit and hardware should
be installed so that it does not interfere with
the removal of any cover, inhibit service or
maintenance, or prevent access between
the unit and walls or another unit.
2.5.1 ELECTRICAL REQUIREMENTS
Electrical requirements for each unit are 120
VAC, 1 Phase, 60 Hz, 20 Amps from a dedicated
electrical circuit. No other devices should be on
the same electrical circuit as a KC1000 unit.
Figure 2.8
AC Power Wiring Diagram
2.6 FIELD CONTROL WIRING
Each unit is fully wired from the factory with an
internal operating control system. No field control
wiring is required for normal operation. However,
the KC1000 control system does allow for some
control and monitoring features. W iring for these
features can be accomplished in the I/O Box
behind the left side panel (Figures 2.9 and 2.10).
The I/O Box is common to both KC1000 water
heaters and boilers. While some of the inputs
and outputs are common to both water heaters
and boilers, some are not applicable to both.
These are noted in the following paragraphs.
CAUTION!
DO NOT make any connections to the I/O
Box terminals labeled “NOT USED”.
Attempting to do so may cause equipment
damage.
2-6
GAS SHUT-OFF
VALVE
I/O BOX
BLOWER
Figure 2.9
Input/Output (I/O) Box Location
2.6.1 OUTDOOR AIR SENSOR IN
Not applicable to Water Heaters.
2.6.2 AUX SENSOR IN
The AUX SENSOR IN terminals can be used to
add an additional temperature sensor for
monitoring purposes. This input is always
enabled and is a view only input that can be
seen in the operating menu. The sensor must be
wired to the AUX SENSOR IN and SENSOR
COMMON and must be similar to AERCO
BALCO wire sensor P/N 12449. A resistance
chart for this sensor can be found in Appendix C.
2.6.3 ANALOG IN
The ANALOG IN + and – terminals are used
when an external signal is used to change the
setpoint of the water heater when operating in
the Remote Setpoint Mode.
Either a 4 to 20 mA / 1 to 5 VDC or a 0 to 20 mA/
0 to 5 VDC signal may be used to vary the
setpoint or valve position. The factory default
setting is for 4 to 20 mA / 1 to 5 VDC, however
this may be changed to 0 to 20 mA / 0 to 5 VDC
using the Configuration Menu described in
Section 3. If voltage rather than current is
selected as the drive signal, a DIP switch must
be set on the CPU Board located inside the
Control Box. Contact the AERCO factory for
information on setting DIP switches.
All supplied signals must be floating
(ungrounded) signals. Connections between the
source and the Heater’s I/O Box must be made
using twisted shielded pair wire of 18 –22
INSTALLATION
AWG,,such as Belden 9841(see Fig. 2.10).
Polarity must be maintained and the shield must
be connected only at the source end. It must be
left floating (not connected) at the Heater’s I/O
Box.
Whether using voltage or current for the drive
signal, they are linearly mapped to a 40°F to
240°F setpoint or a 0% to 100% valve position.
No scaling for these signals is provided
2.6.4 B.M.S. (PWM) IN
Not applicable to Water Heaters.
2.6.5 SHIELD
The SHIELD terminals are used to terminate any
shields used on sensor wires connected to the
unit. Shields must only be connected to these
terminals.
2.6.6 mA OUT
These terminals provide a 4 to 20 mA output that
can be used to monitor setpoint ( to 220°F),
outlet temperature ( to 245°F), or valve position
(0% to 100%). This function is enabled in the
Configuration Menu (Section 3, Table 3.4).
2.6.7 0 – 10V OUT
These terminals provide a 0 to 10 volt output to
control the rotational speed of the blower. This
function is enabled in the Configuration Menu
(Chapter 3, Table 3-4).
2.6.8 RS-485 COMM
These terminals are used for RS-485 MODBUS
serial communication between the unit and an
external “Master”, such as an Energy Management System.
2.6.9 EXHAUST SWITCH IN
These terminals permit an external exhaust
switch to be connected to the exhaust manifold
of the boiler. The exhaust sensor should be a
normally open type switch (such as AERCO P/N
123463) that closes (trips) at 500°F.
2.6.10 INTERLOCKS
The unit offers two interlock circuits for
interfacing with Energy Management Systems
and auxiliary equipment such as pumps or
louvers or other accessories. These interlocks
are called the Remote Interlock and Delayed
Interlock (Fig. 2.10). The wiring terminals for
these interlocks are located inside the I/O Box
on the left side of the unit. The I/O Box cover
contains a wiring diagram which shows the
terminal strip locations for these interlocks
labeled REMOTE INTL’K IN and DELAYED
2-7
INSTALLATION
mA OUT
RS-485
COMM.
+
-
+
-
ANALOG IN
SENSOR COMMON
OUTDOOR SENSOR IN
REMOTE INTL'K IN
B.M.S. (PWM) IN
SHIELD
+
-
+
-
AUX SENSOR IN
NOT USED
EXHAUST SWITCH IN
DELAYED INTL'K IN
FAULT RELAY
120 VAC, 5A, RES
AUX RELAY
120 VAC, 5A, RES
G
RELAY CONTACTS:
120 VAC, 30 VDC
5 AMPS RESISTIVE
DANGER
120 VAC USED
IN THIS BOX
NOT USED
NOT USED
NC
COM
NO
NC
COM
NO
NOT USED
INTL’K IN. Both interlocks, described below, are
factory wired in the closed position.
NOTE:
Both the Delayed Interlock and Remote
Interlock must be in the closed position to
allow the unit to fire.
2.6.10.1 REMOTE INTERLOCK IN
The remote interlock circuit (REMOTE INTL’K
IN) is provided to remotely start (enable) and
stop (disable) the unit if desired. The circuit is
24 VAC and comes factory pre-wired closed
(jumped).
2.6.10.2 DELAYED INTERLOCK
The delayed interlock circuit (DELAYED INTL’K
IN) is typically used in conjunction with the
auxiliary relay described in paragraph 2.6.11.
This interlock circuit is located in the purge
section of the start string. It can be connected to
the proving device (end switch, flow switch etc.)
of an auxiliary piece of equipment started by the
unit’s auxiliary relay. The delayed interlock must
be closed for the heater to fire. If the delayed
interlock is connected to a proving device that
requires time to close (make), a time delay (Aux
Start On Dly) that holds the start sequence of the
unit long enough for a proving switch to make
(close) can be programmed. Should the proving
switch not prove within the programmed time
frame, the unit will shut down. The Aux Start On
Dly can be programmed from 0 to 120 seconds.
This option is locate in the Configuration Menu
(Section 3).
2.6.11 FAULT RELAY
The fault relay is a single pole double throw
(SPDT) relay having a normally open and
normally closed set of relay contacts that are
rated for 5 amps at 120 VAC and 5 amps at 30
VDC. The relay energizes when any fault
condition occurs and remains energized until the
fault is cleared and the CLEAR button is
depressed. The fault relay connections are
shown in Figure 2.10.
2.6.12 AUXILIARY RELAY CONTACTS
Each unit is equipped with a single pole double
throw (SPDT) relay that is energized when there
is a demand for heat and de-energized after the
demand for heat is satisfied. The relay is
provided for the control of auxiliary equipment,
such as pumps and louvers, or can be used as a
unit status indictor (firing or not firing). Its
contacts are rated for 120 VAC @ 5 amps.
Refer to Figure 2.10 to locate the AUX RELAY
terminals for wiring connections.
2-8
Figure 2.10 I/O Box Wiring
INSTALLATION
2.7 FLUE GAS VENT INSTALLATION
AERCO Gas Fired Venting and Combustion Air
Guide, GF-1050, must be consulted before any
flue or combustion air venting is designed or
installed. Suitable, U/L approved, positive
pressure, watertight vent materials MUST be
used for safety and UL certification. Because
the unit is capable of discharging low
temperature exhaust gases, the flue must be
pitched back towards the unit a minimum of 1/4"
per foot to avoid any condensate pooling and to
allow for proper drainage.
While there is a positive flue pressure during
operation, the combined pressure drop of vent
and combustion air systems must not exceed
140 equivalent feet of 0.81” W.C. Fittings as
well as pipe lengths must be calculated as part
of the equivalent length. For a natural draft
installation the draft must not exceed - 0.25”
W.C. These factors must be planned into the
vent installation. If the maximum allowable
equivalent lengths of piping are exceeded, the
unit will not operate properly or reliably.
2.8 COMBUSTION AIR
The AERCO Gas-Fired Heater Venting and
Combustion Air Guide, GF-1050 MUST be
consulted before any flue or inlet air venting is
designed or installed. Air supply is a direct
requirement of ANSI 223.1, NFPA-54, and local
codes. These codes should be consulted before
a permanent design is determined.
The combustion air must be free of chlorine,
halogenated hydrocarbons or other chemicals
that can become hazardous when used in gasfired equipment. Common sources of these
compounds are swimming pools, degreasing
compounds, plastic processing, and refrigerants.
Whenever the environment contains these types
of chemicals, combustion air MUST be supplied
from a clean area outdoors for the protection
and longevity of the equipment and warranty
validation.
The more common methods of combustion air
supply are outlined below. For combustion air
supply from ducting, consult AERCO GF-1050,
Gas Fired Venting and Combustion Air Guide.
2.8.1 COMBUSTION AIR FROM OUTSIDE
THE BUILDING
Air supplied from outside the building must be
provided through two permanent openings. For
each unit these two openings must have a free
area of not less than one square inch for each
4000 BTUs input of the equipment or 250 square
inches of free area. The free area must take into
account restrictions such as louvers and bird
screens.
2.8.2 COMBUSTION AIR FROM INSIDE
THE BUILDING
When combustion air is provided from within the
building, it must be supplied through two permanent openings in an interior wall. Each opening
must have a free area of not less than one
square inch per 1000 BTUH of total input or
1000 square inches of free area. The free area
must take into account any restrictions such as
louvers.
2.8.3 SEALED COMBUSTION
The unit is UL approved for a 100% sealed
combustion application when installed properly.
When a sealed combustion air application is
installed, the sealed combustion air piping must
be deducted from the maximum allowable
discharge piping amounts. Each unit must have a
minimum 6" diameter connection made to the
optional Inlet Air Adapter # GM-18917 available
from AERCO. This Adapter bolts directly on to
the air inlet of the unit blower. See installation
instructions with Adapter. All inlet air ducts must
be sealed air tight.
2-9
CONTROL PANEL OPERATING PROCEDURES
3
1
2
7
4
6
10
8
9
5
11
12
SECTION 3 - CONTROL PANEL OPERATING PROCEDURES
3.1. INTRODUCTION
The information in this Section provides a guide
to the operation of the KC1000 Water Heater
using the Control Panel mounted on the front of
the unit. It is imperative that the initial startup of
this unit be performed by factory trained
personnel. Operation prior to initial startup by
factory trained personnel will void the equipment
warranty. In addition, the following WARNINGS
and CAUTIONS must be observed at all times.
CAUTION:
All initial installation procedures must be
satisfied before attempting to start the unit.
WARNING:
ELECTRICAL VOLTAGES IN THIS
SYSTEM INCLUDE 120 AND 24 VOLTS
AC. IT MUST NOT BE SERVICED OR
ACCESSED BY OTHER THAN FACTORY
CERTIFIED SERVICE TECHNICIANS.
WARNING:
DO NOT ATTEMPT TO DRY FIRE THE
HEATER. STARTING THE UNIT WITHOUT
A FULL WATER LEVEL CAN SERIOUSLY
DAMAGE THE UNIT AND MAY RESULT IN
PERSONNEL INJURY OR PROPERTY
DAMAGE. THIS SITUATION WILL VOID
ANY WARRANTY.
3.2. CONTROL PANEL DESCRIPTION
The KC1000 Control Panel shown in Figure 3-1
contains all of the controls, indicators and
displays necessary to operate, adjust and
troubleshoot the KC1000 Water Heater. These
operating controls, indicators and displays are
listed and described in Table 3-1. Additional
information on these items are provided in the
individual operating procedures provided in this
Section.
Figure 3-1. Control Panel Front View
3-1
CONTROL PANEL OPERATING PROCEDURES
FUNCTION
follows:
COMM
Lights when RS-232 communication is occurring
keypad.
from an Energy Management System
DEMAND
Lights when there is a demand for heat.
Menu Selection
in degrees Fahrenheit or degrees Celsius.
connected to the water heater Control Panel.
5
READY Indicator
Lights when all Pre-Purge conditions have been satisified.
6
ON/OFF Switch
Enables and disables heater operation.
Pressing CLEAR resets the display.
condition occurs. An alarm message will appear in the VFD.
alarms
the Control Panel Menus:
The Menu categories wrap around in the order shown.
category.
Table 3-1. Operating Controls, Indicators and Displays
ITEM
NO.
CONTROL, INDICATOR
OR DISPLAY
1 Four Status LEDs indicate the current operating status as
LED Status Indicators
MANUAL
REMOTE
2 VFD Display Vacuum Fluorescent Display (VFD) consists of 2 lines, each
Lights when the unit is being controlled using the front panel
Lights when the unit is being controlled by an external signal
capable of displaying up to 16 alphanumeric characters. The
information displayed includes:
Startup Messages
Alarm Messages
Operating Status Messages
OUTLET
3
TEMPERATURE
Display
RS-232 Port
4
LOW WATER LEVEL
7
TEST/RESET Switches
FAULT Indicator
8
CLEAR Key
9
10 Consists of 6 keys which provide the following functions for
MENU Keypad
3–Digit, 7–Segment LED display continuously displays the
outlet water temperature. The °F or °C LED next to the
display lights to indicate whether the displayed temperature is
Port permits a Laptop Computer or External Modem to be
Allow the operator to test the operation of the water level
monitor.
Pressing TEST opens the water level probe circuit and
simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit.
Red FAULT LED indicator lights when a heater alarm
Turns off the FAULT indicator and clears trhe alarm message
if the alarm is no longer valid. Lockout type alarms will be
latched and cannot be cleared by simply pressing this key.
Troubleshooting may be required to clear these types of
MENU
BACK
Steps through the main menu categories shown in Figure 3-2.
Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key will
bring you back to the default status display in the VFD. Also,
this key allows you to go back to the top of a main menu
3-2
CONTROL PANEL OPERATING PROCEDURES
FUNCTION
pressing the ▲ arrow key will increment the selected setting.
setting.
flashing will increment or decrement the displayed setting.
display will stop flashing.
Bargraph
Position in 5% increments from 0 to 100%
Table 3-1. Operating Controls, Indicators and Displays - Continued
ITEM
NO.
CONTROL, INDICATOR
OR DISPLAY
10
(Cont.)
11
12
▲ (Up) Arrow When in one of the main menu categories (Figure 3-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
▼ (Down) Arrow
CHANGE
ENTER
AUTO/MAN Switch
VALVE POSITION
When in one of the main menu categories (Figure 3-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the ▼ (Down) arrow key will increment the selected
Permits a setting to be changed (edited). When the
CHANGE key is pressed, the displayed menu item will begin
to flash. Pressing the ▲ or ▼ arrow key when the item is
Saves the modified menu information in memory. The
This switch toggles the water heater between the Automatic
and Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the MANUAL
status LED lights.
When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.
20 segment red LED bargraph continuously shows the Valve
3.3. CONTROL PANEL MENUS
The Control Panel incorporates an extensive
menu structure which permits the operator to set
up, and configure the unit. The menu structure
consists of four major menu categories as
shown in Figure 3-2. Each of the menus shown,
contain options which permit operating
parameters to be viewed or changed. The
menus are protected by a password to prevent
unauthorized use.
Prior to entering the correct password, the
options contained in the Operating, Setup,
Configuration and Tuning Menu categories can
be viewed. However, with the exception of
Internal Setpoint Temperature (Configuration
Menu), none of the viewable menu options can
be changed.
Once the valid password (159) is entered, the
options listed in the Setup, Configuration and
Tuning menus can be viewed and changed, if
desired.
3.3.1. Menu Processing Procedure
Accessing each menu and option is accomplished using the Menu Keys shown in Figure 3-
1. Therefore, it is imperative that you be thoroughly familiar with the following basic steps
before attempting to perform specific menu
procedures.
1. The Control Panel will normally be in the
Operating Menu and the VFD will display the
current unit status. Pressing the ▲ or ▼
arrow key will display the other available data
items in the Operating Menu.
2. Press the MENU key. The display will show
the Setup Menu which is the next menu
category shown in Figure 3-2. This menu
contains the Password option which must be
entered if other menu options will be
changed.
3. Continue pressing the MENU key until the
desired menu is displayed.
3-3
CONTROL PANEL OPERATING PROCEDURES
OPERATION
SETUP
CONFIGURATION
TUNING
PASSWORD
4. With the desired menu displayed, press the
▲ or ▼ arrow key. The first option in the
selected menu will be displayed.
5. Continue to press the ▲ or ▼ arrow key until
the desired menu option is displayed.
Pressing the ▲arrow key will display the
available menu options in the Top-Down
sequence. Pressing the ▼ arrow key will
display the options in the Bottom-Up
sequence. The menu options will wraparound after the first or last available option
is reached.
6. To change the value or setting of a displayed
menu option, press the CHANGE key. The
displayed option will begin to flash. Continue
to press the ▲ or ▼ arrow key for the option
to be changed. The available menu option
choices will be displayed. The menu option
choices do not wrap around.
7. To select and store a changed menu option,
press the ENTER key.
NOTE:
The following paragraphs provide brief
descriptions of the options contained in each
menu. Refer to Appendix A for detailed
descriptions of each menu option. Refer to
Appendix B for listings and descriptions of
displayed startup, status and error messages.
3.4. OPERATING MENU
The Operating Menu displays a number of key
operating parameters for the unit as listed in
Table 3-2. This menu is “Read-Only” and does
not allow personnel to change or adjust any of
the displayed items. Since this menu is “ReadOnly”, it can be viewed at any time without
entering a password. Press the ▲ arrow key to
display the menu items in the order listed (TopDown). Pressing the ▼ arrow key will display
the menu items in reverse order (Bottom-Up).
3.5. SETUP MENU
The Setup Menu (Table 3-3) permits the
operator to set the unit password which is required to change any of the menu options. To
prevent unauthorized use, a previously entered
password entry will time-out after 1 hour. Therefore, the password must be reentered when
required. In addition to permitting password
entries, the Setup Menu is also used to enter
date and time, language to be used for display
messages, units of temperature measurements
and entries required for external communication
and control of the unit via the RS-232 port. A
view-only software version display is also provided to indicate the current Control Box
software version.
3-4
Figure 3-2. Menu Structure
CONTROL PANEL OPERATING PROCEDURES
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Status Message
Active Setpoint
40°F
240°F
Aux Temp
30°F
245°F
Outdoor Temp*
-70°F
130°F
Valve Position In
0%
Max Valve
Position
Flame Strength
0%
100%
Run Cycles
0
999,999
Run Hours
0
999,999
Fault Log 0 9
0
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
0
9999
0
Language
English
English
Time
12:00 am
11:59 pm
Date
01/01/00
12/31/99
Unit of Temp
Fahrenheit
Celsius
Fahrenheit
Comm Address
0
127
0
Software
Ver 0.00
Ver 9.99
NOTE
The Outdoor Temp display item shown with an asterisk in Table
3-2 will not be displayed unless the Outdoor Sensor function has
been enabled in the Configuration Menu (Table 3-4).
Table 3-2. Operating Menu
Table 3-3. Setup Menu
Baud Rate 2400
3.6. CONFIGURATION MENU
The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
9600
4800
9600
19.2K
may or may not be displayed, depending on the
current operating mode setting.
NOTE:
The Configuration Menu settings shown in
Table 3-4 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.
3-5
CONTROL PANEL OPERATING PROCEDURES
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
Boiler
Water Heater
Boiler
Unit Size
0.5 MBTU, 1.0 MBTU
6.0 MBTU
1.0 MBTU
Water Heater Mode
Constant Setpoint
Remote Setpoint
Constant
Setpoint
Remote Signal
4 – 20 mA/1 – 5V
Network
4 – 20 mA,
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
240°F
200°F
Temp Hi Limit
40°F
240°F
215°F
Max Valve Position
40%
100%
100%
Pump Delay Timer
0 min
30 min
0 min
Aux Start On Dly
0 sec
120 sec
0 sec
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
mA Output
Setpoint, Outlet Temp,
Valve Position Out, Off
Off
Lo Fire Timer
2 sec
120 sec
2 sec
Setpt Limiting
Enabled or Disabled
Disabled
Setpt Limit Band
0°F
10°F
5°F
Table 3-4. Configuration Menu
1.5 MBTU, 2.0 MBTU
3.0 MBTU, 3.5 MBTU
4.0 MBTU, 5.0 MBTU
(If Mode = Remote
Setpoint)
(If Outdoor Sensor =
0 -20 mA/0 – 5V
PWM Input (BMS)
1-5V
3-6
CONTROL PANEL OPERATING PROCEDURES
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Min Load Adj
-50°F
50°F
0°F
Max Load Adj
-50°F
50°F
0°F
FFWD Temp
30°F
245°F
Outlet Feedback
On
Off
On
Reset Defaults?
Yes
Are You Sure?
No
3.7. TUNING MENU
The Tuning Menu items in Table 3-5 are Factory
set for each individual unit.
Table 3-5. Tuning Menu
3.8. START SEQUENCE
When the Control Box ON/OFF switch is set to
the ON position, it checks all pre-purge safety
switches to ensure they are closed. These
switches include:
• Safety Shut-Off Valve Proof of Closure
(POC) switch
• Low Water Level switch
• High Water Temperature switch
• High Gas Pressure switch
• Low Gas Pressure switch
If all of the above switches are closed, the
READY light above the ON/OFF switch will light
and the unit will be in the Standby mode.
When there is a demand for heat, the following
events will occur:
NOTE:
Do not change these menu entries unless
specifically requested to do so by FactoryTrained personnel.
No
If any of the Pre-Purge safety device switches
are open, the appropriate fault message will be
displayed. Also, the appropriate fault messages
will be displayed throughout the start sequence,
if the required conditions are not observed.
1. The DEMAND LED status indicator will light.
2. The unit checks to ensure that the proof of
closure switch in the Safety Shut-Off Valve
(SSOV) is closed (Figure 3-3).
Figure 3-3.
Safety Shut-Off Valve
3. With all required safety switches closed, a
purge cycle will be initiated and the following
events will occur:
3-7
CONTROL PANEL OPERATING PROCEDURES
154
155
AIR/FUEL VALVE
BLOWER PROOF
SWITCH
TO FRAME
HARNESS
(a) Blower relay energizes and turns on
blower.
(b) Air/Fuel Valve rotates to the full-open
purge position and closes purge position
switch. The dial on the Air/Fuel Valve
(Figure 3-4) will read 100 to indicate that
the valve is full-open (100%).
(c) The VALVE POSITION bargraph will
show 100%.
STEPPER
MOTOR
BLOWER
DIAL
(DETAIL “A”)
BURNER
Figure 3-5.
Blower Proof Switch
5. Upon completion of the purge cycle, the
Control Box initiates an ignition cycle and the
following events occur:
100
DETAIL "A"
Figure 3-4.
Air/Fuel Valve In Purge Position
4. Next, the blower proof switch (Figure 3-5)
closes and the display will show Purging and
indicate the elapsed time of the purge cycle
in seconds. The normal (default) time for the
purge cycle is 7 seconds.
(a) The Air/Fuel Valve rotates to the low-fire
ignition position and closes the ignition
switch. The dial on the Air/Fuel Valve
(Figure 3-6) will read between 25 and 35
to indicate that the valve is in the lowfire position.
(b) The igniter relay is activated and pro-
vides ignition spark.
(c) The gas Safety Shut Off Valve (SSOV)
is energized (opened) allowing gas to
flow into the Air/Fuel Valve.
6. Up to 7 seconds will be allowed for ignition to
be detected. The igniter relay will be turned
off one second after flame is detected.
7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame
strength will be indicated. After 5 seconds,
the current date and time will be displayed in
place of the flame strength.
3-8
CONTROL PANEL OPERATING PROCEDURES
STEPPER
MOTOR
BLOWER
25
DETAIL "A"
DIAL
(DETAIL “A”)
Figure 3-6.
Air/Fuel Valve In Ignition Position
8. With the unit firing properly, it will be
controlled by the temperature controller circuitry. The VALVE POSITION will be
continuously displayed on the front panel
bargraph.
9. Once the demand for heat has been
BURNER
satisfied, the Control Box will turn off the gas
valve. The blower relay will be deactivated
and the Air/Fuel Valve will be closed.
Standby will be displayed.
3.9. START/STOP LEVELS
The start and stop levels are the valve position
percentages that start and stop the unit, based
on load. These levels are Factory preset as
follows for natural gas and propane units:
• Start Level: 20% (All units)
• Stop Level: 13% (Natural Gas)
• Stop Level: 16% (Propane)
Normally, these settings should not require
adjustment.
Note that the energy input of the boiler is not
linearly related to the valve position percentage
(Air/Fuel Valve position). Refer to Table 3-6 for
the relationship between the energy input and
valve position percentage of a unit running on
natural gas.
Table 3-6.
Relationship Between Air/Fuel Valve Position and Energy Input of a Unit Running on Natural Gas
Valve Position,
Air/Fuel Valve
Position
(% Open)
Energy Input
(BTU/Hr)
Boiler Energy Input
(% of Full Capacity)
0 0 0
10 0 0
13
50,000 5 %
(Stop Level)
20 89,000 9%
30 191,000 19%
40 311.000 31%
50 460,000 46%
60 600,000 60%
70 699,000 70%
80 836,000 84%
90 955,000 96%
100 1,000,000 100%
3-9
SECTION 4 - INITIAL START- UP
4.1 INITIAL START- UP REQUIREMENTS
The initial start-up of the KC-1000 W ater Heater
is comprised of the following steps:
• Installation 100% completed (Section 2)
• Combustion calibration
• Proper setting of controls and limits
• Temperature calibration
• Safety device testing (Section 5)
Installation procedures must be 100% complete
before performing initial start-up. The initial startup must be successfully completed prior to
placing the unit into service. Starting a unit
without the proper piping, venting, or electrical
systems can be dangerous and void the
product’s warranty. These start-up instructions
should be followed precisely in order to safely
operate the unit at a high thermal efficiency, and
with low flue gas emissions.
Initial unit start-up must be performed ONLY by
AERCO factory trained start-up and service
personnel. After following the steps in this
section, it will be necessary to perform the safety
device testing procedures in Section 5 to
complete the initial unit start-up.
An AERCO Gas Fired Startup Sheet included
with each KC-1000 must be completed for each
unit for warranty validation. A copy must be
returned promptly to AERCO at:
AERCO International, Inc.
159 Paris Ave.
Northvale, NJ 07647
WARNING!
DO NOT ATTEMPT TO FIRE THE UNIT
WITHOUT FULL WATER LEVEL. THIS
CAN SERIOUSLY DAMAGE THE UNIT
AND MAY RESULT IN PERSONAL
INJURY OR PROPERTY DAMAGE. THIS
IS NOT COVERED BY WARRANTY.
CAUTION!
All installation procedures in Section 2 must
be completed before attempting to start the
unit.
INITIAL START-UP
4.2 TOOLS AND INSTRUMENTATION
FOR COMBUSTION CALIBRATION
To properly perform combustion calibration, the
proper instruments and tools must be used and
correctly installed on the unit. The following
paragraphs outline the necessary tools and
instrumentation as well as their installation.
4.2.1 REQUIRED TOOLS AND
INSTRUMENTATION
The following tools and instrumentation are
necessary to perform combustion calibration of
the unit:
1. A digital combustion analyzer with oxygen
accuracy to 0.4%, and carbon monoxide in
PPM.
2. *A 16" W.C. manometer and plastic tubing.
3. One 1/4” and two 1/8” NPT-to-barbed fittings
for use with manometers.
4. A flat-tip screwdriver for adjusting the
AERCO differential gas pressure regulator.
5. Small and large flat blade screwdrivers.
6. 7/16" open end wrench and small adjustable
wrenches.
7. Tube of silicone adhesive
*For propane fired units, an additional 8" W.C.
manometer and 1/2" NPT to barbed fitting is
needed.
4.2.2 INSTALLING THE SUPPLY GAS
MANOMETER
1. Close the main manual gas supply valve up
stream of the unit.
2. Remove the 1/4" NPT pipe plug from the
port on the inlet side of the safety shut off
valve (see Figure 4.1).
3. Install a barbed fitting into the pipe plug
tapping.
4. Attach one end of a length of plastic tubing
to the barbed fitting and one end to the 16"
W.C. manometer.
4-1
SSOV
1/4" NPT PLUG
(INSTALL
MANOMETER
HERE)
3/8" - 1/2"
HOLE FOR
COMBUSTION
ANALYZER
PROBE
EXHAUST
MANIFOLD
12" - 18"
INITIAL START-UP
Figure 4.1
1/4” Gas Plug Location
4.2.3 PREPARING THE FLUE VENT
PROBE HOLE
1. If the unit has been installed using the
recommended AL29-4C vent, there will be a
3/8” hole, 18” to 24” above the exhaust
manifold. The outer vent section, that covers
vent section connections must be loosened
and slid down to uncover the hole (see
Fig. 4.2).
2. If equipped with one, adjust the stop on the
combustion analyzer probe so that it extends
into the flue gas flow without hitting the
opposite wall of the flue. Do not insert the
probe at this time.
Figure 4.2
Analyzer Probe Hole Location
IMPORTANT
The unit is shipped from the factory set up for
either natural gas or propane, as specified by the
Style No. on the Sales Order.
For propane units, refer to paragraph 4.4.
4.3 NATURAL GAS COMBUSTION
CALIBRATION
The KC-1000 is shipped combustion calibrated
from the factory. Recalibration as part of a startup is necessary due to altitude, gas BTU
content, gas supply piping and supply regulators.
Factory test data sheets are shipped with each
unit as a reference.
The following combustion calibration procedure
closely follows the factory procedure. By
following this procedure readjustment of
combustion will be kept to a minimum.
1. Open the supply and return valves to the unit
and ensure that the system pumps are
running.
2. Open the gas supply valve(s) to the unit.
3. If a lockup style regulator is installed as a
gas supply regulator, adjust the gas supply
until a reading of 12” W.C. static pressure is
obtained.
4. Set the ON/OFF switch in the OFF position.
Turn on AC power to the unit. The display
will show LOSS OF POWER and the time
and date.
5. Set the unit to the Manual Mode by pressing
the AUTO/MAN switch. A flashing Manual Valve Position message will be displayed
with the present rate in %. Also, the
MANUAL LED will light.
NOTE:
For a review of control panel operating
procedures, see Section 3.
6. Adjust the rate to 0% by pressing the ▼
arrow key.
7. Set the ON/OFF switch to the ON position.
8. Change the valve position to 25% using the
▲ arrow key. This will put the unit into the
starting sequence.
4-2
INITIAL START-UP
Inlet Air
Temp
Oxygen
(+0.2/-1.0)
Carbon
Monoxide
-20°F
7.5 %
<50 ppm
0°F
7.3 %
<50 ppm
10°F
7.2 %
<50 ppm
30°F
6.8 %
<50 ppm
50°F
6.4 %
<50 ppm
60°F
6.2 %
<50 ppm
70°F
6.0 %
<50 ppm
80°F
5.8 %
<50 ppm
90°F
5.6 %
<50 ppm
100°F
5.4 %
<50 ppm
DIFFERENTIAL
PRESSURE
REGULATOR
REGULATOR CAP
CAP GASKET
NOTE:
On initial start-up, or return to service from a
fault condition, the unit will remain at a 29%
valve position for two-minutes.
9. Following the warm-up period, increase the
valve position in 20% increments while
monitoring the gas pressure after every
increase. If gas pressure dips below 8.5”
W.C. for FM gas trains and 8.9” for IRI gas
trains at any input percentage, stop and
raise the pressure. Once 100% is reached,
adjust the gas pressure for 8.5” W.C. or 8.9”
W.C.
NOTE:
If 8.5” W.C. for FM gas trains or 8.9” W.C. for IRI
gas trains cannot be obtained at the 100% valve
position, it will be necessary to stop calibration
and contact the local AERCO representative in
your area. Running the unit on insufficient gas
pressure will void the warranty.
10. Once 8.5” W.C. or 8.9” W.C. is set at the
100% level change the valve position to
30%. Insert the combustion analyzer probe
into the stack.
NOTE:
Always go to a percentage of valve position from
the same direction, (i.e., 100% to 30% or 30% to
20%). Whenever going to a valve position from
below (i.e., 20% to 30%), first go above then
back down to the desired valve position. This is
necessary due to hysteresis in the air/fuel
stepper motor. Hysteresis causes the air/fuel
valve to stop in a slightly different position if the
valve position percentage is approached from
below or above. This results in a difference in
oxygen readings for the same valve position
percentage causing unnecessary recalibration.
11. Allow enough time for the combustion
analyzer to settle. Compare the measured
oxygen level to the oxygen range for intake
air temperature in Table 1.
12. If the measured oxygen level is within the
range in Table 1, no adjustment is
necessary. Proceed to step 19.
13. If the measured oxygen level is not within
the range listed in Table 1, remove the
regulator cap and cap gasket from the
differential pressure regulator (see
Figure 4.3) and proceed to step 14.
Table 1
Combustion Oxygen Levels for a 30%
Valve Position
Figure 4.3
Differential Regulator Adjustment Tool
Installation
14. Use a flat-tip screwdriver to adjust the
differential pressure regulator. Turn the
screwdriver:
•counterclockwise to increase the
oxygen level
•clockwise to decrease the oxygen level
15. Replace the regulator cap and cap gasket
and wait for the analyzer reading to settle.
16. When the analyzer reading settles, compare
the new oxygen reading to Table 1.
4-3
INITIAL START-UP
Inlet Air
Temp
Oxygen
(+0.2/-1.0)
Carbon
Monoxide
-20°F
<12 %
<50 ppm
0°F
<12 %
<50 ppm
10°F
<12 %
<50 ppm
30°F
<12 %
<50 ppm
50°F
<11 %
<50 ppm
60°F
<11 %
<50 ppm
70°F
<11 %
<50 ppm
80°F
<11 %
<50 ppm
90°F
<10 %
<50 ppm
100°F
<10 %
<50 ppm
Inlet Air
Temp
Oxygen
(+0.2/-1.0)
Carbon
Monoxide
-20°F
6.5 %
<150 ppm
0°F
6.3 %
<150 ppm
10°F
6.2 %
<150 ppm
50°F
5.4 %
<150 ppm
60°F
5.2 %
<150 ppm
70°F
5.0 %
<150 ppm
80°F
4.8 %
<150 ppm
90°F
4.6 %
<150 ppm
100°F
4.4 %
<150 ppm
BLOWER
OUTLET
BLOWER
INLET
SCREEN
SHUTTER
SHUTTER
LOCKING NUTS
17. If necessary, repeat the adjustment until the
oxygen level is within the range specified in
Table 1.
18. Replace the regulator cap and cap gasket.
NOTE:
Adjust only the differential regulator at 30%
control signal; do not adjust the air shutter.
Firmly tighten the inlet air shutter locking
nuts when finished.
Table 3
Combustion Oxygen Levels for a 100%
Valve Position
19. Once the oxygen level is within the specified
range at 30%, change the valve position to
13%.
20. Oxygen levels at the 13% valve position
should be as shown in Table 2. No
adjustment should be necessary. Contact
the Factory if the oxygen or carbon
monoxide levels are not within the specified
range.
Table 2
Combustion Oxygen Levels for a 13%
(Natural Gas) and 16% (Propane) Valve
Position
30°F 5.8 % <150 ppm
REMINDER:
At 30% valve position adjust only the differential
pressure regulator. At 100% valve position,
adjust only the inlet air shutter.
21. Change the valve position to 100%. After the
combustion analyzer has settled, compare
the measured oxygen level with the levels in
Table 3.
22. If the measured oxygen reading is below the
oxygen range in Table 3, loosen the two
bolts that secure the inlet air shutter to the
unit using a 7/16” wrench (see Fig. 4.4).
Open the shutter 1/4” to 1/2” to increase the
oxygen level, then tighten the nuts.
23. Wait for the analyzer to settle and then
compare the new oxygen reading to Table 3.
Repeat the inlet air shutter adjustment until
the oxygen is within the specified range.
4-4
Figure 4.4
Air Shutter Locking Nut Location
22. If the measured oxygen reading is above the
oxygen range in Table 3, loosen the two
7/16" locking nuts securing the inlet air
shutter. Close the air shutter 1/4” to 1/2” to
decrease the oxygen level and tighten the
two nuts.
23. Allow the analyzer to settle and then
compare the new oxygen reading to Table 3.
24. Repeat the adjustment until the oxygen is
within the specified range. Firmly tighten the
inlet air shutter locking nuts when finished.
INITIAL START-UP
NOTE:
Adjust the inlet air shutter only at 100% valve
position. Do not adjust the differential pressure
regulator.
25. Change the valve position to 30%. Allow
time for the combustion analyzer to settle.
Check the measured oxygen reading to
insure that it is still within the range as per
Table 1.
26. Continue this procedure until all oxygen
levels are within the ranges specified in
Tables 1, 2 and 3.
27. Record all readings on the AERCO start-up
sheet provided with each unit. Proceed to
paragraph 4.5.
4.4 PROPANE COMBUSTION
CALIBRATION
For propane units it will be necessary to install
an additional 8” W.C. manometer. This
manometer will be used to measure the
pressure drop across the air/propane mixing
orifice. After performing the setup procedures in
paragraphs 4,2.2 through 4.2.4, install the 8”
W.C. manometer as described in steps 1, 2 and
3 which follow.
1. Referring to Fig. 4.5, remove the 1/8” NPT
plug from the gas inlet pipe ahead of the
burner and install a 1/8” NPT barbed fitting.
2. Remove the 1/2” NPT plug from the tee
located after the air pressure regulator and
install a 1/2” barbed fitting (see fig. 4.5).
3. Attach the 8” W.C. manometer to the barbed
fittings installed in steps 1 and 2.
NOTE:
The combustion calibration data in Tables 1, 2
and 3 apply to both natural gas and propane
units. Therefore, refer to these Tables when
performing propane combustion calibration.
For propane, combustion calibration data will be
checked at 30%, 16% and 100%. Note that the
data In Table 2 is applicable to a valve position
of 16% for propane and 13% for natural gas.
4. While performing the combustion calibration
procedure in paragraph 4.3, measure the
pressure drop across the air/propane mixing
orifice using the 0-8” W.C. manometer.
5. This reading should remain a constant 3.8”
to 4” W.C. throughout the operating range.
6. If the pressure drop is not within this range,
remove the cap from the air pressure
regulator.
7. Using a flat blade screwdriver adjust the
regulator until 3.8”-4.0” W.C. is obtained.
Clockwise will increase the reading and
counter-clockwise will decrease the reading.
8. If adjustments are made to this regulator it
will be necessary to recheck oxygen settings
at 16%, 30%, and 100% valve positions.
NOTE:
After an adjustment is made to the air regulator,
the cap must be put back on securely to obtain
an accurate reading.
Figure 4.5
Propane Air Differential Pressure Taps
4.5 UNIT REASSEMBLY
Once combustion calibration is set properly, the
unit can be re-assembled for permanent
operation.
1. Set the ON/OFF switch to the OFF position.
Disconnect the AC power supply from the
unit.
2. Shut off the gas supply to the unit.
3. Remove the differential pressure regulator
cap and cap gasket (see Figure 4.3).
4. Apply a drop of silicone to the regulator
adjusting screw to lock its setting.
4-5
INITIAL START-UP
5. Reinstall the regulator cap and gasket on the
regulator. Tighten the cap using a
screwdriver or wrench.
6. Remove all of the manometers and barbed
fittings and reinstall the pipe plugs using a
suitable thread compound.
7. Remove the combustion analyzer probe
from the vent hole. Seal the probe hole and
replace the vent connection cover.
8. Replace the unit’s panels and hood.
4.6 TEMPERATURE CONTROL
CALIBRATION
Although the unit comes factory set and
calibrated for a 130°
necessary to recalibrate temperature control.
There are two primary adjustments for
performing temperature calibration. These are
Min Load Adj and Max Load Adj (minimum and
maximum load adjustment).
Adjustments to these settings are made at
minimum and maximum load conditions and
should be made in small increments from 1 to 3
degrees. After making an adjustment, outlet
water temperature must be allowed to settle for
several minutes prior to making further
adjustments.
When calibrating temperature control, observe
the following:
1. The unit must be in the Auto mode of
operation.
2. The Outlet Feedback option in the Tuning
Menu must be off while performing
calibration.
3. Monitor the OUTLET TEMPERATURE
display and VALVE POSITION bar-graph
display to set load conditions and see the
effect of adjustments.
4. Perform the calibration using the Tuning
Menu of the Control Box.
5. Make small adjustments and allow time
between adjustments for the outlet
temperature to stabilize.
6. Maintain water flow as constant as possible
during these adjustments.
7. Ensure that recirculation loops are
operational while the calibration is being
performed.
F setpoint it is usually
4.6.1 SETTING THE OUTLET WATER
TEMPERATURE SETPOINT
The setpoint temperature of the unit may be
changed by following the procedure below.
However, once a setpoint has been changed,
recalibration may be necessary. The
temperature calibration procedures are provided
in paragraphs 4.6.2 and 4.6.3
To adjust the unit’s setpoint, proceed as follows:
1. Press the MENU key until ConfigurationMenu is displayed.
2. Press the ▲ or ▼ arrow key until Internal Setpt is displayed along with the present
setpoint temperature.
3. To change the setpoint, press the CHANGE
key. The display will begin to flash.
4. Press the ▲ or ▼ arrow key until the desired
setpoint is displayed.
5. Press the ENTER key to save the change.
4.6.2 MINIMUM LOAD ADJUSTMENT
With the unit in operation, check the temperature
control at minimum load as follows:
1. While monitoring the VALVE POSITION
display, create a minimum load on the
system that will yield a steady valve position
between 25% and 35%.
NOTE:
It may be desirable to shut off the outlet valve and
use the hose bib to simulate a minimum flow load
condition.
2. Wait several minutes to allow the outlet
temperature to stabilize under load
conditions.
3. Once stabilized, the OUTLET TEMPERATURE display should read no
more than 2 to 3 degrees above the unit’s
setpoint.
4. If the outlet temperature is stabilized,
proceed to the Maximum Load Adjustment
procedure in paragraph 4.6.3. If the unit is
not stabilized, proceed to step 5.
5. Press the MENU key and select the Tuning Menu.
6. Press the ▲ or ▼ arrow key until Min Load Adj is displayed.
4-6
INITIAL START-UP
7. Press the CHANGE key. The display will
begin to flash.
8. Raise or lower the minimum load adjustment
in increments of one or two using the ▲ or ▼ arrow key. Increasing this value will
increase the outlet water temperature, while
decreasing it will decrease the water
temperature.
9. Press ENTER to save the change. Allow
time for the system to stabilize between
adjustments
10. Repeat steps 5 through 9 as needed until
the temperature is stabilized at no more than
2 to 3 degrees above the setpoint.
4.6.3 MAXIMUM LOAD ADJUSTMENT
Check the temperature control at minimum load
as follows:
1. While monitoring the VALVE POSITION
display, create a maximum load on the
system that will yield a steady valve position
between 80% and 90%.
NOTE:
It may be necessary to open the outlet valve if it
was closed during minimum load adjustment to
obtain a sufficient flow rate for maximum
adjustment.
2. Wait several minutes to allow the outlet
temperature to stabilize under load
conditions.
3. Once the temperature has stabilized, the
OUTLET TEMPERATURE display should
read no more than 2 to 3 degrees below the
unit’s setpoint.
4. If the outlet temperature is stabilized, no
adjustment is necessary. If the unit is not
stabilized, proceed to step 5.
5. Press the MENU key and select the Tuning Menu.
6. Press the ▲ or ▼ arrow key until Max Load Adj is displayed.
7. Press the CHANGE key. The display will
begin to flash.
8. Raise or lower the maximum load
adjustment using the ▲ or ▼ arrow key.
Increasing this value will increase outlet
water temperature, while decreasing it will
decrease water temperature.
9. Press ENTER to save the change. Allow
time for the system to stabilize between
adjustments.
10. Repeat steps 5 through 9 as needed until
the temperature is stabilized 2 to 3 degrees
below the setpoint.
11. If the outlet temperature does not maintain
setpoint after a reasonable amount of time
and adjustment, contact your local AERCO
representative.
NOTE:
After performing Temperature Calibration and
prior to placing the water heater in service, be
sure to turn the Outlet Feedback option in the
Tuning Menu back to ON.
4.7 OVER-TEMPERATURE LIMIT
SWITCH ADJUSTMENTS
There are two Over-Temperature Limit switches
that turn off the unit when the outlet water
temperature becomes too hot. The lower overtemperature limit switch is adjustable and should
be adjusted 20°F to 40°F above the operating
header temperature. The upper overtemperature limit switch is a manual reset device
and is not adjustable. It will shut the unit off if the
water temperature reaches 200°F. DO NOT
attempt to adjust its setpoint.
To adjust the lower over temperature switch limit
h:
switc
1. Remove the wing nut from the top center of
the shell cap. Lift the cap off the shell.
2. The two over-temperature limit switches are
located at the top of the shell (see Fig. 4.6).
Do not adjust the upper switch it has been
factory preset. Adjust the lower switch
between 20° to 40°F higher than the
maximum header temperature the unit may
see.
3. Replace the shell cap and wing nut.
4-7
INITIAL START-UP
OVER-TEMPERATURE
SWITCHES
209
TEMPERATURE SWITCH DETAILS
137
HARNESS
136
FROM SHELL
NC
NC
CNO
C
25
OVER TEMP. SWITCH
(SEE DETAIL)
Figure 4.6
Over Temperature Limit Switch Location
4-8
SAFETY DEVICE TESTING
1/4" NPT PLUG
(INSTALL
MANOMETER
HERE)
SSOV
SECTION 5 - SAFETY DEVICE TESTING PROCEDURES
5.1 TESTING OF SAFETY DEVICES
Periodic testing of all controls and safety devices
is required to insure that they are operating as
designed. Precautions must be taken while tests
are being performed to protect against bodily
injury and property damage.
Systematic and thorough testing of the operating
and safety controls should be performed on a
scheduled basis, or whenever a control component has been serviced or replaced. All testing
must conform to local jurisdictions or codes such
as ASME CSD-1.
NOTE:
MANUAL and AUTO modes are required to
perform the following tests. For a complete
explanation of these modes, see Section 3.
NOTE:
It will be necessary to remove the sheet metal
covers and cap from the unit to perform the
following tests.
WARNING!
ELECTRICAL VOLTAGES IN THIS
SYSTEM INCLUDE 120 AND 24 VOLTS
AC. POWER MUST BE REMOVED PRIOR
TO PERFORMING WIRE REMOVAL OR
OTHER TESTING PROCEDURES THAT
CAN RESULT IN ELECTRICAL SHOCK.
5.2 LOW GAS PRESSURE FAULT TEST
1. Shut off the gas supply to the unit.
2. Install a 0-16” W.C. manometer in the gas
pipe assembly below the low gas pressure
switch. (See Fig. 5.1)
3. Open the gas supply to the unit and depress
the CLEAR button to clear any fault messages..
4. Place the unit in Manual Mode and fire the
unit at a valve position between 25% and
30%.
5. Slowly close the manual gas supply valve
while monitoring the gas pressure. The unit
should fault and shutdown on LOW GAS PRESSURE when the manometer indicates
approximately 6.5” W.C.
6. Open the gas supply to the unit and press
the CLEAR button on the Control Box.
7. The unit should restart.
Figure 5.1
1/8” Pipe Plug Position for Manometer
Installation
NOTE:
After faulting the unit, the fault message will be
displayed and the fault indicator light will flash
until the CLEAR button is pressed.
5.3 HIGH GAS PRESSURE TEST
1. Start the unit in manual mode and fire between 25% and 30%.
2. Remove either wire # 150 or wire #151 from
the high gas pressure switch. See Fig. 5.2.
3. The unit should shut down on a HIGH GAS PRESSURE FAULT.
4. Reconnect the wire previously removed from
the high gas pressure switch and depress
the CLEAR button.
5. The unit should restart.
5-1
SAFETY DEVICE TESTING
HIGH GAS
PRESSURE
SWITCH
209
13
7
HARNESS
1
3
6
FROM SHELL
NC
NC
CNO
C
120
180
150
DIAL
Figure 5.2
High Gas Pressure Switch
10. After the shell is full, press the LOW
WATER LEVEL RESET button to reset the
low water cutoff. Press the CLEAR button to
reset the FAULT LED and clear the error
message.
11. Set the ON/OFF switch to the ON position.
The unit is now ready for operation.
5.5 WATER TEMPERATURE FAULT
TEST
1. In the normal operating mode, allow the unit
to stabilize at its setpoint.
2. Lower the adjustable temperature limit
switch setting to match the outlet water temperature. (See Fig. 5.3).
5. 4 LOW WATER LEVEL FAULT TEST
1. Set the ON/OFF switch in the OFF position.
2. Close the shut-off valves in the supply and
return piping to the unit.
3. Open the drain valve on the unit.
4. Allow air flow into the unit by either opening
the relief valve or by removing the 1/4” plug
in the top of the unit.
5. The LOW WATER LEVEL message will be
displayed and the FAULT LED will flash after
the water level has gone below the level of
the probe.
6. Set the ON/OFF switch to ON. The READY
light should remain off and the unit should
not start. If the unit does start, shut the unit
off immediately and refer fault to qualified
service personnel.
7. Close the drain and pressure relief valve or
reinstall the plug in the top of the unit if
removed.
8. Open the water shut-off valve in the return
piping to the unit to fill the shell.
9. Open the water shut-off valve in the supply
piping to the unit.
5-2
Figure 5.3
Temperature Limit Switch Setting
3. Once the switch setting is approximately at
the actual water temperature, the unit should
shutdown. The FAULT LED should be
flashing and the message HIGH WATER TEMP SWITCH OPEN should be displayed.
The unit should not start.
4. Reset the temperature limit switch setting to
its prior setting.
5. The unit should start once the adjustable
temperature limit switch setting is above the
actual outlet water temperature.
SAFETY DEVICE TESTING
5.6 INTERLOCK TESTS
The unit is equipped with two interlock circuits
called the Remote Interlock and Delayed Interlock. Terminal connections for these circuits are
located in the I/O Box and are labeled REMOTE
INTL’K IN and DELAYED INTL’K IN. These
circuits can shut down the unit in the event that
an interlock is opened. These interlocks are
shipped from the factory jumped (closed).
However, each of these interlocks may be
utilized in the field as a remote stop and start, an
emergency cut-off, or to prove that a device such
as a pump gas booster, or louver is operational.
5.6.1 REMOTE INTERLOCK
1. Remove the cover from the I/O Box and
locate the REMOTE INTL’K IN terminals.
2. Start the unit in manual mode and fire at
25% to 30% valve position.
3. If there is a jumper across the REMOTE
INTL’K IN terminals, remove one side of the
jumper. If the interlock is being controlled by
an external device, either open the interlock
via the external device or disconnect one of
the wires leading to the external device.
4. The unit should shut down and display
INTERLOCK OPEN.
5. Once the interlock connection is reconnected, the INTERLOCK OPEN message
should automatically clear and the unit
should resume running.
5.6.2 DELAYED INTERLOCK
1. Remove the cover from the I/O Box and
locate the DELAYED INTL’K IN terminals.
2. Start the unit in manual mode and fire at a
25% to 30% valve position.
3. If there is a jumper across the DELAYED
INTL’K IN terminals, remove one side of the
jumper. If the interlock is connected to a
proving switch of an external device, disconnect one of the wires leading to the proving
switch.
4. The unit should shut down and display
DELAYED INTERLOCK OPEN. The FAULT
LED should be flashing.
5. Once the interlock connection is reconnected, depress the CLEAR button. The
unit should start.
5.7 FLAME FAULT TEST
1. Place the ON/OFF switch in the OFF
position.
2. Place the unit in the Manual Mode and set
the valve position between 25% and 30%.
3. Close the manual leak detection valve
located between the safety shut-off valve
and the differential regulator (see Fig. 5.4).
4. Start the unit.
5. The unit should shut down after reaching the
Ignition cycle and display FLAME LOSS
DURING IGN.
6. Open the valve previously closed in step 3
and depress the CLEAR button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual leak
detection valve located between the safety
shut-off valve and the differential regulator.
9. The unit should shut down and display
FLAME LOSS DURING RUN.
10. Open the valve previously closed in step 8
and depress the CLEAR button. The unit
should restart and fire.
Figure 5.4
Manual Leak Detection Valve
5-3
SAFETY DEVICE TESTING
154
155
AIR/FUEL VALVE
BLOWER PROOF
SWITCH
TO FRAME
HARNESS
SSOV
ACTUATOR
COVER
SSOV
COVER
SCREW
5.8 AIR FLOW FAULT TEST
1. Start the unit in manual mode and set the
valve position between 25% and 30%.
2. Once the unit has proved flame, remove
either wire #154 or #155 from the blower
proof switch (see Fig. 5.5) located on the
air/fuel valve.
3. The unit should shut down and display
AIRFLOW FAULT DURING RUN.
4. Replace the wire previously removed from
the blower-proof switch and depress the
CLEAR button. The unit should restart.
WARNING!
ELECTRICAL VOLTAGES IN THIS
SYSTEM INCLUDE 120 AND 24 VOLTS
AC. POWER MUST BE REMOVED PRIOR
TO PERFORMING WIRE REMOVAL OR
OTHER TESTING PROCEDURES THAT
CAN RESULT IN ELECTRICAL SHOCK.
5.9 SSOV PROOF OF CLOSURE
SWITCH
1. Set the unit’s ON/OFF switch to the OFF
position. Place the unit in manual mode and
set the valve position between 25% and
30%.
2. Remove the Safety Shut-Off Valve (SSOV)
cover to access the terminal connections.
See Fig. 5.6. For units with IRI gas trains,
access the terminal connections of the
downstream SSOV (see drawing SD-A-606
in Appendix E).
3. Remove either wire #149 or #148 from the
SSOV.
4. The unit should fault and display SSOV SWITCH OPEN.
5. Replace the wire previously removed and
depress the CLEAR button.
6. Start the unit.
7. Remove the wire again when the unit
reaches the purge cycle.
8. The unit should shut down and display
SSOV FAULT DURING PURGE.
9. Replace the wire on the SSOV and depress
the CLEAR button. The unit should restart.
Figure 5.5
Blower Proof Switch Location and Wiring
5-4
Figure 5.6
SSOV Actuator Cover Screw Location
SAFETY DEVICE TESTING
VALVE
COVER
IGNITION
POSITION
SWITCH
PURGE
POSITION
SWITCH
169
170
172
171
STEPPER
MOTOR
DIAL
BLOWER
BURNER
5.10 PURGE SWITCH OPEN DURING
PURGE
1. Set the unit’s ON/OFF switch to the OFF
position. Place the unit in manual mode and
set the valve position between 25% and
30%.
2. Remove the air/fuel valve cover by rotating
the cover counterclockwise to unlock it and
then pulling it towards you. See Fig. 5.7.
3. Remove one of the two wires from the purge
switch (Fig. 5.8) and start the unit.
4. The unit should begin to start, then shut
down and display PRG SWITCH OPEN DURING PURGE.
5. Replace the wire on the purge switch and
depress the CLEAR button. The unit should
restart.
5.11 IGNITION SWITCH OPEN DURING
IGNITION
1. Set the unit’s ON/OFF switch to the OFF
position. Place the unit in manual mode and
set the valve position between 25% and
30%.
2. Remove the air/fuel valve cover (Fig. 5.7) by
rotating the cover counterclockwise to
unlock it then pulling it towards you.
3. Remove one of the two wires from the
ignition switch (Fig. 5.8) and start the unit.
4. The unit should begin to start and then shut
down and display IGN SWITCH OPEN DURING IGNITION.
5. Replace the wire on the ignition switch and
depress the CLEAR button. The unit should
restart.
Figure 5.7
Air/Fuel Valve Cover Location
Figure 5.8
Air/Fuel Valve Purge and Ignition Switch
Locations
5-5
SAFETY DEVICE TESTING
5.12 SAFETY PRESSURE RELIEF VALVE
TEST
Test the safety Pressure Relief Valve in
accordance with ASME Boiler and Pressure
Vessel Code, Section VI.
5-6
MAINTENANCE
SECTION 6 – MAINTENANCE
6.1 MAINTENANCE SCHEDULE
The KC1000 Heater requires regular routine maintenance to maintain efficiency and reliability. For best
operation and life of the unit, the following routine maintenance procedures should be performed in the
time periods specified in Table 6-1.
Appendix I contains recommended spare parts lists for maintenance of the KC1000 Heater.
WARNING!
TO AVOID PERSONAL INJURY, BEFORE SERVICING:
(A) DISCONNECT AC POWER TO THE UNIT
(B) SHUT OFF THE GAS SUPPLY TO THE UNIT
(C) ALLOW THE UNIT TO COOL TO A SAFE TEMPERATURE
6.2 SPARK IGNITOR
The spark ignitor (part no.GP-122435-S) is located in the body of the burner (see Fig. 6.1). The ignitor
may be HOT. Care should be exercised. It is easier to remove the ignitor from the unit after the unit has
cooled to room temperature.
CAUTION!
The ignitor must be removed and installed using the ignitor removal tool provided with the unit(s). Damage
to the burner due to using a socket for removal and installation of the ignitor is not covered under warranty
To inspect/replace the Ignitor:
1. Set the ON/OFF switch on the control panel to the OFF position and disconnect AC power from the
unit.
2. For access to the spark ignitor, remove the unit’s right side panel. Access can also be gained tby
removing the rear panels and condensate drainage system
3. Disconnect the ignitor cable from the ignitor extension. Remove the silicone ignitor plug from the
burner shell by simultaneously twisting and pulling downward.
4. Insert the ignitor removal tool into the burner shell, where the ignitor plug was removed. Screw the
outer barrel of the tool into the burner shell. Push the inner barrel up and fit the hexagonal end of the
tool over the ignitor. Unscrew the ignitor from the burner head and then the tool from the burner shell.
5. The ignitor is gapped at 1/8-inch. If there is a substantial erosion of the spark gap or ground electrode,
the ignitor should be replaced. If carbon build-up is present, clean the ignitor using fine emery cloth.
Repeated carbon build-up on the ignitor is an indication that a check of the combustion settings is
required (refer to Section 4 for Combustion Calibration).
6. Prior to reinstalling the ignitor, a very light coating of anti-seize compound must be applied to the
ignitor threads.
CAUTION!
The ignitor must be removed and installed using the ignitor removal tool provided with the unit(s). Damage
to the burner due to using a socket for removal and installation of the ignitor is not covered under
warranty.
7. Reinstall the ignitor assembly using the ignitor removal tool. Do not over tighten the ignitor. A slight
snugging up is sufficient.
8. Reinstall the ignitor plug into the burner shell by simultaneously twisting and pushing it into the shell.
9. Reattach the ignitor cable to the extension and verify that it “clicks” into place.
10. Replace the rear cover panels or right side panel. Replace the condensate cup to drain tubing.
6-1
MAINTENANCE
SPARK IGNITOR
ASSEMBLY
BURNER
SHELL
FLAME
DETECTOR
SILICONE
PLUG
Section
Item
6 Mos.
12 Mos.
24 Mos.
Labor Time
Spark Ignitor
(GP-122435-S)
Flame Detector
(GM-123428)
Combustion
Adjustments.
Testing of Safety
Controls
BTU Transmitter
Pump
Inspect & clean if
necessary
*Manifold &
Tubes
Inspect & clean if
necessary
Inspect and
required)
Spark Ignitor and Flame Detector Location
Table 6-1. Maintenance Schedule
Figure 6.1
6.2
6.3
6.4
6.5
6.6
6.7 BTU Transmitter
6.8
6.9 Heat Exchanger
6.10
6.11
Condensate
Drain
Low Water Cutoff
Probe (69126)
Inspect Replace 15 mins.
Inspect Replace 15 mins.
Check Check 1 hr.
Test 20 mins.
Oil 15 mins.
50 mins.
**Inspect
Inspect
Clean (as
Inspect &
Clean
Inspect Inspect
Inspect and Clean
(as required)
30 mins.
Replace (Every 24
Mos.)
4 hrs.
1.5 to 3.5 hrs.
20 mins.
*
Recommended only when unit will be run in an extreme condensing mode for prolonged periods of time.
** In areas where water quality is poor or not qualified, inspection and cleaning may be required to assure
trouble-free operation. Hard water deposits must be removed to prevent corrosion and leaking. Checking
at more frequent intervals may be required to prevent scale buildup. See page 6-13 for information about
removing scale deposits using AERCO HydroSkrub scale remover.
6.3 FLAME DETECTOR
The flame detector (part no. GM-123428) is located in the body of the burner (see Fig. 6.1). The flame
detector may be HOT. Allow the unit to cool sufficiently before removing the flame detector.
To inspect or replace the flame detector:
1. Set the ON/OFF switch on the control panel, to the OFF position and disconnect AC power from the
unit.
6-2
MAINTENANCE
2. Remove the left side panel from the unit.
3. Disconnect the flame detector lead wire and unscrew the flame detector and remove it from the
burner.
4. Inspect the detector thoroughly. If eroded, the detector should be replaced. A white coating is an
indication of oxidation, which may be removed with an abrasive cloth (such as Scotch Brite).
Although flame strength may be checked using the C-More controller display (see OPERATING
MENU, Section 3.4 on page 3-5 and Table 3.2), it is strongly recommended that you instead use the
procedure as described in Section 6.3, page 6-18 for accurate flame strength measurement and to
assure trouble free operation of the flame detection circuit.
5. Reinstall the flame detector hand tight only, and reconnect the flame detector lead wire.
6. Replace any panels previously removed.
6.4 COMBUSTION CALIBRATION
Combustion settings must be checked at the intervals shown in Table 6-1 as part of the maintenance
requirements. Refer to Section 4 for combustion calibration instructions.
6.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating and safety devices should be performed to ensure that
they are operating as designed. Certain code requirements, such as ASME CSD-1, require that these
tests be performed on a scheduled basis. Test schedules must conform to local jurisdictions. The results
of the tests should be recorded and preserved as directed by ruling jurisdictions. See Section 5-Safety
Device Testing Procedures.
NOTE:
6.6 BTU TRANSMITTER PUMP LUBRICATION
The BTU Transmitter pump should be lubricated every six months. There are two oil ports located on the
top of the pump, (see Fig. 6.2). Oil using 4 to 5 drops of SAE20 weight non-detergent oil at each port. DO
NOT OVER OIL.
Figure 6.2
BTU Transmitter Pump Oil Port Locations
6.7 BTU TRANSMITTER ASSEMBLY
The BTU Transmitter is a crucial part of the unit’s temperature control system. It must be inspected and
kept free of scale and debris in order for the unit to maintain accurate outlet water temperatures.
To inspect the transmitter:
1. Place the ON/OFF switch in the OFF position.
2. Remove the sheet metal side panels and hood from the unit.
6-3
MAINTENANCE
COMPRESSION
FITTINGS
LOWER TUBING ASSEMBLY
3. Shut the water inlet, outlet and recirculation valves to the unit.
4. Open the drain valve on the unit.
5. Slowly open the pressure relief valve to allow air-flow into the unit.
6. Fully drain the unit.
7. Disconnect electrical power from the unit.
8. Remove the 4 screws holding the BTU transmitter pump to the impeller housing. Remove and set the
pump aside, (See Fig. 6.3).
NOTE:
It is not necessary to disconnect the electrical wires to the pump.
Figure 6.3
BTU Transmitter Pump Disassembly
9. Using a 5/8” and 9/16” wrench, loosen the 4 compression fittings holding the lower tubing assembly in
place, (See Fig. 6.4).
Figure 6.4
Compression Fitting Locations
6-4
MAINTENANCE
HYDRAULIC ZERO &
CONTROL ORIFICE
TUBING ASSEMBLY
COLD WATER
MIXING ORIFICE
HOT WATER
MIXING ORIFICE
HYDRAULIC ZERO
NEEDLE VALVE
LOWER TUBING ASSEMBLY
COMPRESSION
10. Carefully remove the lower tubing assembly taking care not to lose either the cold water or hot water
mixing orifice, (See Fig. 6.5).
11. Loosen the compression fitting holding the hydraulic zero and control orifice tube assembly to the
pump’s impeller housing, (See Fig. 6.6).
NOTE:
The cold water mixing orifice (P/N GP-122401) is slightly larger than the hot water mixing orifice (P/N GP-
122760). Each orifice must be correctly installed for proper temperature control.
12. Remove the compression fitting at the top of the impeller housing and remove the impeller housing,
(See Fig. 6.6).
Figure 6.7
BTU Transmitter Hot Water Tube Disassembly
13. Remove the compression fitting securing the pump outlet tube to the ball valve and remove the pump
outlet tube.
14. Remove the ball valve connected to the hot water tube coming from the top of the shell by loosening
the compression fitting securing it to the hot water tube, (See Fig. 6.7).
15. Loosen the compression fitting at the top of the shell holding the hot water tube, (See Fig. 6.8). Slide
16. Inspect all fittings and tubing for blockage due to scale or debris. Clean or replace as necessary.
17. Inspect the mixing orifice for blockage or degradation due to erosion, (See Fig. 6.5). Clean or replace
18. The pump impeller may be checked by removing the 4 screws from the cover encasing the impeller in
the hot water tube down slightly but do not remove it from the unit. Remove the
as necessary.
the housing, (See Fig. 6.9).
fitting.
6-6
Figure 6.8
BTU Transmitter Shell Components
MAINTENANCE
IMPELLER HOUSING
COVER
GP-122537
Exhaust Manifold to
Gasket
GP-18900
Manifold to Tubesheet
Gasket
GP-18899
Burner Gasket
GP-122551
Burner Release Gasket
GP-161151
Combustion Chamber Liner
Figure 6.9
Impeller Housing Disassembly
19. Once the BTU transmitter has been inspected and cleaned, reassemble in the reverse order.
NOTE:
Do not attempt to adjust the Hydraulic Zero Needle Valve. This is a factory-preset item. Refer to Figure
6.5. If setting has been tampered with or BTU transmitter is being replaced, see procedure in Section
6.12, page 6-17.
Compression fittings are nickel-plated and should be replaced only with nickel-plated fittings. Do not use
6.8 MANIFOLD AND EXHAUST TUBES
The presence of even trace amounts of chlorides and/or sulfur, in the combustion air and fuel sources,
can lead to the formation of deposits on the inside of the exchanger tubes, the exhaust manifold, and/or
the condensate cup. The degree of deposition is influenced by the extent of the condensing operation and
the chloride and sulfur levels that vary significantly from application to application.
The following parts will be necessary for reassembly after inspection:
To remove the manifold for inspection:
1. Disconnect AC power and turn off the gas supply to the unit.
2. Remove the sheet metal covers from the unit.
3. Disconnect the plastic tubing from the condensate cup to drain and remove the rear covers.
4. Remove the condensate cup from under the unit and the condensate drainage tubing from the
5. Disconnect the flame detector and ignition cable wires from the flame detector and ignitor contactor.
NOTE:
brass fittings.
Combustion Chamber
manifold.
Remove the flame detector and ignitor as per paragraphs 6.2, and 6.3.
6-7
MAINTENANCE
6. Remove the grounding terminal from the burner by loosening the upper screw and sliding the
connector from the grounding rod, (See Fig. 6.10).
7. Using a 7/16” socket or open end wrench, remove the four 1/4”-20 nuts on the gas inlet pipe flange at
the burner, (See Fig. 6.11).
8. Using two 9/16” wrenches, remove the 3/8"-16 hex nuts and bolts on the gas inlet pipe flange at the
air/fuel valve, (see Fig. 6.11).
Figure 6.10
Grounding Terminal Location
9. Loosen the hose clamp at the air/fuel valve outlet and slide the clamp back towards the burner, (see
Fig. 6.11).
10. Using a 1/2” socket wrench remove six 5/16-18 hex nuts supporting the burner, (see Fig. 6.11).
Figure 6.11
Burner Disassembly Diagram
11. Lower the burner while sliding the air hose off the air/fuel valve. Remove the burner through the rear
of the unit.
12. Disconnect the exhaust temperature sensor by unscrewing it from the exhaust manifold, (See Fig.
6.12).
6-8
TO FRAME
HARNESS
BLOWER PROOF
SWITCH
AIR/FUEL VALVE
To Frame
Figure 6.12
Exhaust Sensor Connector Location
13. Disconnect the air/fuel valve wiring harness connector from the control panel.
14. Disconnect wires #24 and #17 from the blower proof switch (See Fig. 6.13).
MAINTENANCE
Harness
Figure 6.13
Blower Proof Switch Wire Location
(older style switch shown at left, newer style at right)
15. Loosen the hose clamp on the air/fuel valve inlet and slide the clamp back towards the blower, (See
Fig. 6.14).
6-9
MAINTENANCE
Figure 6.14
Air/Fuel Valve Inlet Hose Clamp
16. Using an 11/16” wrench, loosen the compression fittings on the feedback tube between the air/fuel
valve and the differential pressure regulator. Remove the feedback tube, (See Fig. 6.15).
17. Using two 9/16” wrenches remove the two 3/8-16 hex nuts and bolts securing the air/fuel valve to the
differential pressure regulator, (See Fig. 6.15).
18. Remove the air/fuel valve, taking care not to damage the flexible tubing on the throat of the air/fuel
valve.
Figure 6.15
Feedback Tube and Air/Fuel Valve to Differential Regulator Bolts
19. Remove the flue venting from the exhaust manifold.
20. Removing the exhaust manifold insulation will prevent it from being damaged and will make it easier
to handle the exhaust manifold once it is removed. Using a 7/16” wrench or socket, remove the 3 bolts
and fender washers securing the insulation to the exhaust manifold.
6-10
MAINTENANCE
21. Loosen the three 1-1/16” nuts that hold the manifold. Remove the two side nuts. DO NOT REMOVE
THE FRONT NUT, (See Fig. 6.16).
22. Carefully pull the manifold down and back, removing it through the back of the unit.
23. Inspect the exhaust manifold and exhaust tubes for debris. Clean out any debris as necessary.
24. Inspect the combustion chamber and the combustion chamber liner. Replace the liner if any signs of
cracking or warpage are evident.
NOTE:
See Figure 6.21 on page 6-19 for a drawing showing manifold gasket locations and part numbers.
NOTE:
Install the combustion chamber liner prior to reinstalling the exhaust manifold.
EXHAUST
MANIFOLD
Figure 6.16
Manifold Nut and Bolt Locations
25. Replace the gasket between the manifold and the combustion chamber (P/N GP-122537). The use of
Permatex or a similar gasket adhesive is recommended.
26. Replace the gasket between the manifold and tubesheet (P/N GP-18900). Do not use any gasket
adhesive; this gasket has an adhesive backing
27. Beginning with the manifold, reinstall all the components in the reverse order that they were removed.
Replace the o-ring seals removed with the air/fuel valve. AERCO recommends that NEW o-ring seals
be used when reassembling.
6.8.1 PROPANE UNITS
For propane units it will be necessary to remove the air mix assembly, in addition to the steps outlined in
paragraph 6.8. Proceed as follows:
1. Follow steps 1 through 5 in paragraph 6.8.
2. Using a wrench, loosen the two compression fittings holding the 1/4” feedback tube between the
burner and air regulator and remove the feedback tube. (See Fig. 6.17)
3. Using a 1-1/16” wrench or an adjustable wrench loosen and remove the 12” flexible gas hose.
4. Proceed back to paragraph 6.8 and continue at Step #6.
NOTE:
Older propane units have a 1/8” Feedback Tube and 1/8” OD tube compression fittings.
6-11
MAINTENANCE
Figure 6.17
Propane Air Regulator Measuring Taps
6.9 HEAT EXCHANGER INSPECTION AND CLEANING
Inspecting the Heat Exchanger
The water-side of the heating surfaces may be inspected by removal of the top heater head. (See Fig.
6.18). The following gaskets will be needed prior to performing the inspection:
GP-18556 Release Gasket
GP-18532 Shell Gasket
To inspect the heat exchanger watersides:
1. Disconnect the electrical power to the unit.
2. Close the water inlet, outlet, and recirculation shut-off valves to the unit.
3. Open the drain valve carefully while opening the relief valve on the right side of the unit shell to relieve
pressure and allow air into the shell.
CAUTION!
Do not drain the unit without venting the shell! A vacuum in the unit may displace the liner causing serious
4. Remove the wing nut from the top center of the shell cap and remove the cap.
5. Remove the nuts and cap screws from the upper head. Remove the upper head and upper head-liner,
(See Fig. 6.18). Remove scale from all shell penetration points and sensors.
6. Inspect and, if necessary, clean the heat exchanger tubes of scale and all gasket surfaces thoroughly
before reassembling the upper head. Refer to heat exchanger cleaning steps on page 6.13. AERCO
recommends that NEW gaskets be used when reassembling.
7. Place a shell head gasket on top of the shell ring first, then place the release gasket on top of the shell
head gasket. Align the gasket holes with those in the shell ring.
8. Place the upper head liner on top of the gaskets.
9. Place the upper head on next aligning the holes.
damage not covered by warranty.
6-12
MAINTENANCE
5/8-11 HEX NUT
5/8-11 X 3" CAP SCREW
KC1000 SS HEATER
5/8 EYE NUT
5/8-11 X 4-1/2" STUD
UPPER HEAD
(P.N. 18842)
UPPER HEAD LINER
RELEASE GASKET
(P.N. 18556)
SHELL GASKET
(P.N. 18532)
SHELL RING
Figure 6.18b
Configuration
Figure 6.18a
Configuration
HOLE
THRU-HOLE
10. Reassemble the cap screws and nuts through the upper head and shell ring. Cross tighten the nuts to
approximately 75 ft./lb. torque to obtain a uniform seating, then progressively tighten the nuts to 150
ft./lb.
11. Replace the unit Cap. Close the drain valve and reopen the inlet, outlet, and recirculation valves to
refill the unit.
5/8-11 x 4-1/2” STUD
MOUNTED IN THREADED
Do not
remove
if using a
chain
hoist
Do not
remove
if using a
chain
hoist
5/8-11 x 3” BOLT
MOUNTED IN
SS Water Heater Head
Carbon Water Heater Head
Cleaning the Heat Exchanger
Precautions:
Please review MSDS, specifications, and our website www.aerco.com for additional information, or call
technical service at (800) 526-0288.
NOTICE
Mix the HydroSkrub with an equal volume of water to obtain a 50% concentration (11.5 gallons of each =
23 gallons total).
NOTICE
If the isolation valves are located more than one foot from the supply and return ports of the exchanger,
add in the piping volume from the exchanger to the valves.
Do not drain the unit without venting the shell! A vacuum in the unit may displace the liner causing serious
CAUTION!
damage not covered by warranty.
6-13
MAINTENANCE
Figure 6.19 – HydroSkrub Pumping System Set-Up Diagram for KC-1000
Pumping System Set-Up Directions
1. Turn off the water heater and close all isolation valves.
2. Drain at least half of the Heat Exchanger water-side volume. The KC-1000 heat exchanger holds a
total volume of 23 gallons. Use 11.5 gallons of HydroSkrub mixed with an equal volume of water (23
gallons of HydroSkrub/water solution) to clean.
3. Close the Drain Valve.
4. Check that all connections are secure and all appropriate equipment valves are open.
Cleaning Procedure
5. Slowly add prescribed amount of HydroSkrub to the circulating bucket.
6. If recommended quantity exceeds volume of the bucket, turn on pump at this stage.
7. Plug in the pump and periodically check for leaks. Maintain liquid level in the bucket, as a lowering
volume indicates an open drain or system. Operating level should be 1/3 of the receiving bucket, the
remaining space is for foaming and expansion.
8. Check circuit again. The HydroSkrub solution should flow from the circulation bucket, through the
pump and the equipment and back to the top of the bucket.
9. Return discharge foaming indicates active HydroSkrub solution and presence of mineral deposits.
10. Additional HydroSkrub and/or water may be required to maintain circulation and to prevent the pump
from cavitating.
11. Circulate through the Heat Exchanger and piping for 1 to 3 hours. Estimate circulation period based
on the time in service and water hardness. If heating equipment is more than 40 gallons, circulation
time may need to be extended to complete cleaning. When foaming action stops, HydroSkrub
6-14
MAINTENANCE
strength is depleted (two pounds of deposits removed per gallon used) or the equipment is free from
calcium and other water formed mineral deposits.
12. Periodically test the solution for effectiveness to determine if more HydroSkrub is needed—refer to
“Testing hydroSkrob Effectiveness” for details. If the cleaning solution is expended before circulation
time is up, additional HydroSkrub will be needed and circulation time may be extended to complete
the cleaning.
13. Upon completion, begin flushing procedure by adding water to the circulation bucket, then disconnect
return valve from the circulating bucket and thoroughly flush. Continue water flushing the equipment
for a minimum of 10 minutes or until discharge runs clear.
14. HydroSkrub is biodegradable, and in most instances may be purged down sewers. Check with local
authorities before disposing of any complex compositions.
15. Turn off water, unplug pump and immediately close discharge valves to prevent backflow.
16. Completely drain pump bucket. Disconnect hoses from equipment and liberally rinse bucket, pump,
and associated hosing before neatly stowing.
Testing HydroSkrub Effectiveness
There are two methods of testing the effectiveness of HydroSkrub during cleaning: the calcium carbonate
spot test of the circulating solution and the charting of a trend in the pH of the cleaning solution.
Calcium Carbonate Spot Test
A calcium carbonate spot test is performed by exposing a form of calcium carbonate to the HydroSkrub
solution. Samples of the deposit, a Tums or Rolaids tablet, or bare concrete can be used. Observe the
reaction of the HydroSkrub solution on the calcium carbonate. Foaming and bubbling indicates the
solution is still active. Little or no reaction indicates that the solution is expended. This test should be
performed near the end of the circulating time. If the solution has been expended, more HydroSkrub will
be required to complete the job. If the solution is still active at the end of the time, all the scale has been
dissolved.
pH Trend Charting
The initial pH of the cleaning solution will measure between 1-3 (See pH sheet on HydroSkrub
packaging). To test the effectiveness of the circulating solution as a function of pH, take readings at
regular intervals and chart as a trend. Note that the deposits can cause a premature jump in the pH.
After circulating for approximately 75% of the cycle time, begin testing the pH at 10-15 minute intervals.
Once the solution’s pH reads 6.0-7.0 on three or more consecutive readings, the solution is expended. If
the pH reads below 6.0 after the circulating time, the application is clean.
6.10 CONDENSATE DRAIN ASSEMBLY
KC Heaters contain a condensate drain cup (Figure 2.5) which should be inspected and cleaned annually
to ensure proper operation.
To inspect and clean, proceed as follows:
1. Remove the left side panel and left rear cover to provide access to the condensate drain components
(see Figure 2.6).
2. Disconnect the drain hose attached to the exhaust manifold.
3. Disconnect the plastic tubing from the condensate cup drain tube to the drain
4. Remove the condensate cup from under the unit. Thoroughly clean the cup and inspect drain tube for
blockage.
5. Check to ensure that the condensate drain opening in the exhaust manifold is not blocked.
6. Flush out the drain hose and plastic tubing.
7. After the above items have been cleaned and inspected, reassemble the condensate drain
components by reversing the previous steps.
6-15
MAINTENANCE
LWCO Sensor
Probe
LWCO
(P/N 69126)
6.11 LOW WATER CUTOFF PROBE INSPECTION AND CLEANING
KC Heaters feature a Low Water Cutoff sensor probe (P/N 122843 as part of probe/capacitor assembly
P/N 69126) which should be inspected and, if needed, cleaned every six months or replaced (if damaged)
to ensure proper operation. See Figure 6.20.
To inspect and clean, proceed as follows:
1. Disconnect power to the boiler and drain the water from the boiler system.
CAUTION!
Do not drain the unit without venting the shell! A vacuum in the unit may displace the liner causing
serious damage not covered by warranty.
2. The LWCO probe is installed near the top of the heat exchanger. Unscrew the brass coupling in
which the probe is installed and remove the probe/coupling assembly from the recess. Take care
to not damage the wire connected to the probe. See Figure 6.20 for a picture of the probe
installed and uninstalled (shown with brass coupling attached and wire/hardware removed).
3. Inspect the metal end of the probe for scale and/or corrosion.
4. If the probe needs cleaning, use sandpaper of 100 grit or more to remove any scale or corrosion.
5. If the probe is heavily pitted or is damaged in any way, replace with a new probe.
6. Reinstall the probe, refill boiler system with water, reapply electrical power, and test to ensure
probe is working.
Probe/Capacitor
assembly
6-16
Figure 6.20 – Low Water Cutoff Probe and Brass Coupling
MAINTENANCE
6.12 HYDRAULIC ZERO NEEDLE VALVE ADJUSTMENT (C-MORE CONTROL BOX)
The Hydraulic Zero Needle Valve is factory set in new equipment and should not be changed unless the
BTU Transmitter is being replaced. If adjustment is necessary, the following procedure must be followed
to assure optimum temperature control.
NOTES:
1) The BTU Transmitter assembly must be thoroughly cleaned prior to adjusting the Hydraulic Zero
Hydraulic Zero Needle Valve Adjustment Instructions
Needle Valve.
2) The lock nut on the needle valve must be loosened prior to adjustment. The needle valve must be
open approximately 2-1/2 CCW turns prior to starting this procedure.
3) It is recommended that the unit’s outlet be closed off and the hose bib be used to set the 3 to 6 GPM
flow rate.
4) It is mandatory that the 3 to 6 GPM be steady. VARYING flow rates will result in improper setting of
the Hydraulic Zero Needle Valve and temperature control inconsistencies.
1) Enter SETUP menu and change the password from 0 to 159, then press the ENTER key to activate
Level 1 access.
2) Scroll through the TUNING menu until Outlet Feedback/YES is displayed. Press the CHANGE key,
then using the UP or DOWN arrow keys, toggle the Outlet Feedback to NO and press ENTER to
accept the change.
3) Using a 7/16” wrench, loosen the locking nut on the hydraulic zero needle valve.
4) Rotate the needle valve fully clockwise, opening the valve.
5) Start the 3 to 6 GPM flow rate through the unit.
6) Place the temperature controller in MANUAL mode and set a 20% firing rate.
7) Maintain an outlet temperature between 135° and 140° F. Adjust firing rate as necessary to maintain
the above outlet temperature.
8) Scroll through the TUNING menu to get FFW Temp (Feed Forward Temperature) displayed on the
top line. The temperature value is displayed on the bottom line. This is a measurement of the water
temperature at the BTU transmitter sensor.
9) Adjust the needle valve until the FFW Temp is 18° to 24° F below the outlet temperature and stable
(i.e., if the outlet temperature is 135° F, then the FFWTemp should read between 117° to 111° F.
Close the needle valve CW to lower the Feed Forward Temperature and open the needle valve CCW to
Once the hydraulic zero needle valve has been set, gently lock it in place using the locking nut.
Now complete the Temperature Control Calibration per Section 4.6 in this manual. At the end of that
procedure, the Feedback will be turned on prior to heater operation in automatic control.
raise the Feed Forward Temperature.
NOTE
6-17
6.13 FLAME STRENGTH MEASURMENT
The flame sensor is a very important safety device. Its function is to sense the absence of a flame (over a
certain amount of time) and so shut off the flow of gas to avoid the build up of unburned fuel within the
burner assembly.
Defining Flame Strength
A flame sensor works by alternating a very small electrical DC signal through the flame sensor rod and the
flame base (ground). Electrical ions travel from the base, through the flame itself, and into the sensor
completing an electrical circuit. When the flame is extinguished, there is a disruption of this electrical
circuit, which the controller senses and so initiates shutdown procedures. This current is referred to by
AERCO as the flame strength (also known as flame current or flame signal).
CAUTION!
There is a very low AC current used to energise the flame sensor when power is applied to the system
(should be between 90 and 110 volts), so touching the energized sensor may cause a mild electric shock.
Determining Flame Strength
Reading the flame strength through the C-More Display is not a reliable way to determine if there is
acceptable flame strength. Only by using a Digital Multimeter sensitive enough to measure current in
microamps (µA) can the flame strength be properly measured. The meter must at least be capable of
measuring between 0.1 µA and 10.0 µA of DC current with a minimum measurement resolution of 0.1 µA.
Typically, the operating range of the flame strength will be between 3.4 µA and 12.0 µA. Anything below
the minimum indicates insufficient flame strength. A reading of 2 µA or less probably indicates dirty rods or
calibration issues and requires investigation. A reading of more than 8.5 µA is acceptable and should not
cause concern.
NOTE:
Ensure that the multimeter probes are in the common (ground) and µA connections and that the
multimeter fuse is not burned out.
Instructions for Measuring Flame Strength
Disconnect the flame rod connector from the flame rod. Next, connect the multimeter probes in series
between the Flame Rod and the Flame Rod Connector as shown in Figure 6.21. Polarity is not a concern
in this measurement, so you may connect the probes without regard to polarity and ignore whether the
measurement indicates a positive or negative reading.
Figure 6.21 – Connecting the Multimeter to Measure Flame strength
MAINTENANCE
Check for the following during the reading:
•Measure the voltage in µA between the flame rod and the flame connector. If the flame senser is
operating correctly, the reading will be between 3.4 µA and 12.0 µA. If there is a lower voltage
reading or no voltage, check to make sure that the wires from the control module to the flamesensing rod are correctly connected and ensure the the flame rod or the wire connected to it is
grounded properly.
•If the reading is still too low, ensure that the flame rod and burner are clean and free of dust, dirt,
or debris. If they are not, take them out, clean them, and reinstall. Cleaning removes impedance
from the current circuit and thus should increase the flame current.
•If a low reading is still observed, replace the flame-sensing rod. A new flame sensing rod should
now produce the correct measurement. However, if an acceptable measurement is still not
observed, the problem may lie in the controller.
•Chassis grounds on the shell and on the back of the C-More controller should be checked for
continuity. Resistance must not exceed 1 Ω (ohm) on any ground attached to the heat exchanger
and the C-More controller.
Figure 6.22 – Manifold Gasket Part Numbers and Locations
6-19
TROUBLESHOOTING
SECTION 7- TROUBLESHOOTING GUIDE
7.1 INTRODUCTION
This troubleshooting guide is intended to aid
service/maintenance personnel in isolating the
cause of a fault in a KC 1000 Water Heater. The
troubleshooting procedures contained herein are
presented in tabular form on the following pages.
These tables are comprised of three columns
labeled: Fault Indication, Probable Cause and
Corrective Action. The numbered items in the
Probable Cause and Corrective Action columns
correspond to each other. For example,
Probable Cause No. 1 corresponds to Corrective
Action No. 1, etc.
When a fault occurs in the KC1000 Water
Heater, proceed as follows to isolate and correct
the fault:
1. Observe the fault messages displayed in the
Control Box display.
2. Refer to the Fault Indication column in the
following troubleshooting tables and locate
the Fault that best describes the existing
conditions.
3. Proceed to the Probable Cause column and
start with the first item (1) listed for the Fault
Indication.
4. Perform the checks and procedures listed in
the Corrective Action column for the first
Probable Cause candidate.
5. Continue checking each additional Probable
Cause for the existing fault until the fault is
corrected.
6. If the fault cannot be corrected using the
information provided in the Troubleshooting
Tables, contact your local AERCO
Representative.
7-1
TROUBLESHOOTING
FAULT INDICATION
greater than zero ohms, replace switch.
present refer to qualified service personnel.
rough, perform combustion calibration.
KC1000 WATER HEATER TROUBLESHOOTING TABLE
PROBABLE CAUSES CORRECTIVE ACTION
AIRFLOW FAULT
DURING IGNITION
1. Blower stopped running
due to thermal or current
overload
2. Blocked Blower inlet or
inlet ductwork
3. Blocked airflow switch
4. Defective airflow switch
1. Check combustion blower for signs of excessive
heat or high current drain that may trip thermal or
current overload devices.
2. Inspect the inlet to the combustion blower
including any duct work leading up to the
combustion blower for signs of blockage.
3. Remove the airflow switch and inspect for signs
of blockage, clean or replace as necessary.
4. Measure the airflow switch for continuity with the
combustion blower running. If there is an erratic
resistance reading or the resistance reading is
AIRFLOW FAULT
DURING PURGE
AIRFLOW FAULT
DURING RUN
1. Blower not running
2. Defective Air Flow Switch
3. Blocked Air flow Switch
4. Blocked Blower inlet or
inlet ductwork.
5. No voltage to switch from
control box.
1. Blower stopped running
due to thermal or current
overload
2. Blocked Blower inlet or
inlet ductwork
3. Blocked airflow switch
4. Defective airflow switch
5. Combustion oscillations
1. Start the unit. If the blower does not run check the
blower solid state relay for input and output
voltage. If the relay is okay, check the blower.
2. Start the unit. If the blower runs, check the airflow
switch for continuity. Replace the switch if there is
no continuity.
3. Remove the air flow switch and inspect for signs of
blockage, clean or replace as necessary.
4. Inspect the inlet to the combustion blower
including any ductwork leading up to the
combustion blower for signs of blockage.
5. Measure for 24 VAC during start sequence from
each side of the switch to ground. If 24VAC is not
1. Check combustion blower for signs of excessive
heat or high current draw that may trip thermal or
current overload devices.
2. Inspect the inlet to the combustion blower
including any ductwork leading up to the
combustion blower for signs of blockage.
3. Remove the airflow switch and inspect for signs of
blockage, clean or replace as necessary.
4. Measure the airflow switch for continuity with the
combustion blower running. If there is an erratic
resistance reading or the resistance reading is
greater than zero ohms, replace the switch.
5. Run unit to full fire. If the unit rumbles or runs
7-2
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued
DELAYED
INTERLOCK OPEN
DIRECT DRIVE
SIGNAL FAULT
FLAME LOSS
DURING IGN
1. Delayed Interlock
Jumper not installed or
removed.
2. Device proving switch
hooked to interlocks is
not closed
1. Unit “Type” is
improperly set up as
Boiler instead of
Water Heater.
1. Worn flame detector
2. No spark from Spark
Plug
3. Defective Ignition
Transformer
4. Defective
Ignition/Stepper (IGST)
Board
5. Defective SSOV
6. Defective Differential
Pressure Regulator
7. Carbon or other debris
on Burner
1. Check for a jumper properly installed across
the delayed interlock terminals in the I/O box.
2. If there are 2 external wires on these terminals,
check to see if an end switch for a device such
as a pump, louver, etc. is tied these interlocks.
Ensure that the device and or its end switch
are functional. (jumper may be temporarily
installed to test interlock)
1. Check the “Unit Type” menu option in the
Configuration Menu to ensure that the Unit
Type is set to Water Heater. Change menu
option if necessary.
1. Remove and inspect the flame detector for
signs of wear. Replace if necessary.
2. Close the internal gas valve in the boiler. Install
and arc a spark ignitor outside the unit.
3. If there is no spark, check for 120VAC at the
primary side to the ignition transformer during
the ignition cycle.
4. If 120VAC is not present, the IGST Board in
the Control Box may be defective. Refer fault to
qualified service personnel.
5. While externally arcing the spark ignitor,
observe the open/close indicator in the Safety
Shut-Off Valve to ensure it is opening. If the
valve does not open, check for 120VAC at the
valves input terminals. If 120VAC is not
present, the IGST board in the Control Box
may be defective. Refer fault to qualified
service personnel.
6. Check gas pressure readings using a gauge or
manometer into and out of the Air/Fuel Valve to
ensure gas is getting to the burner.
7. Remove the burner and inspect for any carbon
or debris. Clean and reinstall
7-3
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
not in Demand
calibration
repair as necessary.
KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued
FFWD TEMP
SENSOR FAULT
FLAME LOSS
DURING RUN
HEAT DEMAND
FAILURE
1. Loose or broken wiring.
2. Defective Sensor.
3. Incorrect Sensor.
1. Worn Flame Detector
or cracked ceramic.
2. Defective Differential
Regulator.
3. Poor combustion
calibration.
4. Debris on burner.
5. Blocked condensate
drain.
1. The Heat Demand
Relays on the
Ignition/Stepper (IGST)
board failed to activate
when commanded
2. Relay is activated when
1. Inspect feed forward (BTU transmitter) sensor
for loose or broken wiring.
2. Check resistance of sensor to determine if it is
within specification.
3. Ensure that the correct sensor is installed.
1. Remove and inspect the Flame Detector for
signs of wear or cracked ceramic. Replace if
necessary.
2. Check gas pressure readings using a gauge or
manometer into and out of the Air/Fuel Valve to
ensure that the gas pressure into and out of the
valve is correct.
3. Check combustion calibration. Adjust as
necessary.
4. Remove the burner and inspect for any carbon
or debris. Clean and reinstall.
5. Remove blockage from condensate drain.
1. Press CLEAR button and restart the unit. If the
fault persists, replace IGST Board.
2. Defective relay. Replace IGST Board.
HIGH EXHAUST
TEMPERATURE
HIGH GAS
PRESSURE
7-4
1. Defective exhaust
sensor.
2. Carboned heat
exchanger due to
incorrect combustion
1. Incorrect supply gas
pressure.
2. Defective Supply
Regulator or Wrong
Style Regulator
1. Measure the actual exhaust temperature and
continuity of the exhaust sensor. If the exhaust
temperature is less than 500
exhaust sensor shows continuity replace the
sensor.
2. If exhaust temperature is greater than 500 o F,
check combustion calibration. Calibrate or
1. If using a non-lock up style regulator for the gas
supply, measure static gas pressure
downstream, it should be 14”WC or less. Adjust
as necessary.
2. If gas supply pressure cannot be lowered, a
lock-up style regulator may be required or the
supply regulator may be defective.
o
F and the
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued
(continued)
HIGH WATER TEMP
SWITCH OPEN
HIGH WATER
TEMPERATURE
3. Defective High Gas
Pressure Switch
1. Scaled BTU
Transmitter.
2. Faulty Water
Temperature Switch.
3. Faulty Temperature
Sensor
4. Unit in MANUAL Mode
5. Unit setpoint is greater
than Over Temperature
Switch setpoint
1. See HIGH WATER
TEMP SWITCH OPEN.
2. Temp HI Limit setting is
too low.
3. Remove the leads from the high gas
pressure switch and measure continuity
across the common and normally closed
terminals with the unit not firing. Replace
the switch if it does not show continuity.
1. Inspect and clean the BTU transmitter per
Maintenance Section.
2. Test the temperature switch to insure it
trips at its actual water temperature setting.
3. Using the resistance charts in Appendix C,
measure the resistance of Shell sensor and
BTU sensor at a known water temperature.
4. If unit is in Manual Mode, switch to Auto
Mode.
5. Check setpoint of unit and setpoint of
Temperature Switch. Ensure that the
temperature switch is set 20 degrees
higher than the unit’s setpoint.
1. See HIGH WATER TEMP SWITCH OPEN
2. Check Temp HI Limit Setting.
IGN BOARD
COMM FAULT
7-5
1. Communication fault
has occurred between
the PMC board and
Ignition/Stepper (IGST)
board
1. Press CLEAR button and restart unit. If
fault persists, contact qualified Service
Personnel.
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
5. Defective IGST Board
ON & OFF every second. If not, replace IGST Board.
not closed.
KC1000WATER HEATER TROUBLESHOOTING TABLE – Continued
IGN SWTCH CLOSED
DURING PURGE
1. Air/Fuel Valve not
rotating
2. Defective or shorted
switch
3. Switch wired incorrectly
4. Defective Power Supply
Board or fuse
1. Start the unit. The Air/Fuel Valve should rotate to the
purge (open) position. If the valve does not rotate at all
or does not rotate fully open, check the Air/Fuel Valve
calibration. If calibration is okay, the problem may be
in the Air-Fuel Valve or the Control Box. Refer to
qualified service personnel.
2. If the Air/Fuel Valve does rotate to purge, check the
ignition switch for continuity between the N.O. and
COM terminals. If the switch shows continuity when
not in contact with the cam replace the switch.
3. Check to ensure that the switch is wired correctly
(correct wire numbers on the normally open terminals).
If the switch is wired correctly, replace the switch
4. Check DS1 & DS2 LEDs on Power Supply Board. If
they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is blinking
ON & OFF every second. If not, replace IGST Board.
IGN SWTCH OPEN
DURING IGNITION
INTERLOCK
OPEN
1. Air/Fuel Valve not
rotating to ignition
position.
2. Defective ignition switch
3. Defective Power Supply
Board or fuse
4. Defective IGST Board
1. Interlock jumper not
installed or removed
2. Energy Management
System does not have
boiler enabled.
3. Device proving switch
hooked to interlocks is
1. Start the unit. The Air/Fuel Valve should rotate to the
purge (open) position, then back to ignition position
(towards closed) during the ignition cycle. If the valve
does not rotate back to the ignition position, check the
Air/Fuel Valve calibration. If calibration is okay, the
problem may be in the Air/Fuel Valve or the Control
Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition position,
check the ignition position switch for continuity
between the N.O. and COM terminals when in contact
with the cam.
3. Check DS1 & DS2 LEDs on Power Supply Board. If
they are not steady ON, replace Power Supply Board.
4. Check “Heartbeat” LED DS1 and verify it is blinking
1. Check for a jumper properly installed across the
interlock terminals in the I/O box
2. If there are two external wires on these terminals
check any Energy Management system to see if they
have the units disabled (a jumper may be temporarily
installed to see if the interlock circuit is functioning).
3. Check that proving switch for any device hooked to the
interlock circuit is closing and that the device is
operational.
7-6
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
necessary.
probe.
open terminals).
KC1000WATER HEATER TROUBLESHOOTING TABLE – Continued
LINE VOLTAGE
OUT OF PHASE
LOW GAS
PRESSURE
LOW WATER
LEVEL
1. Line and Neutral
switched in AC Power
Box.
2. Incorrect power supply
transformer wiring.
1. Incorrect supply gas
pressure.
2. Defective or incorrectly
sized Gas Supply
Regulator.
3. Defective Low Pressure
Gas Switch
1. Insufficient water level in
system
2. Defective water level
circuitry.
3. Defective water level
1. Check hot and neutral in AC Power Box to
ensure they are not reversed
2. Check transformer wiring, in AC Power Box,
against the power box transformer wiring
diagram to ensure it is wired correctly
1. Measure gas pressure upstream of the supply
gas regulator with the unit firing ensure it is 14”
WC or greater.
2. Measure gas pressure downstream of the supply
regulator with unit firing and adjust the gas
supply regulator to increase the outlet gas
pressure; if outlet gas pressure cannot be
increased, check the sizing of the Supply
regulator.
3. Measure gas pressure at the low gas pressure
switch, if it is greater than 5” WC measure
continuity across the switch and replace if
1. Check system for sufficient water level.
2. Test water level circuitry using the Control Box
front panel LOW WATER TEST and RESET
buttons. Replace water level circuitry if it does
not respond.
3. Check continuity of probe end to the shell,
change probe if there is no continuity.
MODBUS COMM
FAULT
PRG SWTCH CLOSED
DURING IGNITION
1. Water Heater not seeing
information from modbus
network
1. A/F Valve rotated open to
purge and did not rotate
to ignition position
2. Defective or shorted
switch.
1. Check network connections. If fault persists,
contact qualified Service Personnel.
1. Start the unit. The Air/Fuel Valve should rotate to
the purge (open) position, then back to ignition
position (towards closed) during the ignition
cycle. If the valve does not rotate back to the
ignition position, check the Air/Fuel Valve
calibration. If calibration is okay, the problem
may be in the Air/Fuel Valve or the Control Box.
Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition
position, check the purge switch for continuity
between the N.O. and COM terminals. If the
switch shows continuity when not in contact with
the cam, check to ensure that the switch is wired
correctly (correct wire numbers on the normally
7-7
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
replace IGST Board.
replace IGST Board.
(voltage or current).
Configuration Menu.
2. Replace Flame Detector.
KC1000WATER HEATER TROUBLESHOOTING TABLE – Continued
(continued)
PRG SWTCH OPEN
DURING PURGE
REMOTE SETPT
SIGNAL FAULT
3. Switch wired incorrectly.
4. Defective Power Supply
Board or fuse
5. Defective IGST Board
1. Defective purge switch.
2. No voltage present at
switch.
3. Switch wired incorrectly.
4. Defective Power Supply
Board or fuse
5. Defective IGST Board
1. Remote setpoint signal not
present:
Not yet installed.
Wrong polarity.
Signal defective at source.
Broken or loose wiring.
2. Signal is not isolated
(floating) if 4 to 20 mA.
3. Control Box signal type
selection switches not set
for correct signal type
3. If the switch is wired correctly, replace the
switch.
4. Check DS1 & DS2 LEDs on Power Supply
Board. If they are not steady ON, replace
Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is
blinking ON & OFF every second. If not,
1. If the air-fuel valve does rotate, check the
purge switch for continuity when closing.
Replace switch if continuity does not exist.
2. Measure for 24 VAC from each side of the
switch to ground. If 24VAC is not present,
refer fault to qualified service personnel.
3. Check to ensure that the switch is wired
correctly (correct wire numbers on the
normally open terminals).
4. Check DS1 & DS2 LEDs on Power Supply
Board. If they are not steady ON, replace
Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is
blinking ON & OFF every second. If not,
1. Check I/O Box to ensure signal is hooked up.
Hook up if not installed.
If installed, check polarity.
Measure signal level.
Check continuity of wiring between source and
boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it
is set correctly for the type of signal being
sent. Check control signal type set in
RESIDUAL
FLAME
7-8
1. SSOV not fully closed.
2. Defective Flame Detector.
1. Check open/close indicator window of Safety
Shut-Off Valve (SSOV) and ensure that the
SSOV is fully closed. If not fully closed,
replace the valve and or actuator.
Close gas shut-off valve downstream of
SSOV. Install a manometer or gauge in a gas
test port between the SSOV and the gas shut
off valve. If a gas pressure reading is
observed replace the SSOV valve and or
actuator.
TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
DURING PURGE
OPEN
DURING RUN
15 seconds during run.
replace Ignition/Stepper (IGST) Board.
KC1000WATER HEATER TROUBLESHOOTING TABLE – Continued
SSOV FAULT
SSOV FAULT
SSOV RELAY
FAILURE
SSOV
SWITCH OPEN
1. See SSOV SWITCH
1. SSOV switch closed for
1. SSOV relay failed on
board.
1. Actuator not allowing for
full closure of gas valve
2. SSOV powered when it
should not be
3. Defective Switch or
Actuator
4. Incorrectly wired switch.
1. Replace SSOV actuator.
1. Ensure that Neutral and Earth Ground are connected
at the source and there is no voltage measured
between them. Measurement should indicate near
zero or no more than a few millivolts.
2. Check the SSOV power wiring.
3. Press CLEAR button and restart unit. If fault persists,
1. Observe operation of the Safety Shut-Off Valve
(SSOV) through indicator on the Valve actuator and
ensure that the valve is fully and not partially closing.
2. If the SSOV never closes, it may be powered
continuously. Close the gas supply and remove
power from the unit. Refer fault to qualified service
personnel.
3. Remove the electrical cover from the SSOV and
check switch continuity. If the switch does not show
continuity with the gas valve closed, either adjust or
replace the switch or actuator.
4. Ensure that the SSOV Proof of Closure switch is
correctly wired.
STEPPER MOTOR
FAILURE
1. Air/Fuel Valve out of
calibration.
2. Air/Fuel Valve
unplugged.
3. Loose wiring connection
to the stepper motor.
4. Defective Air/Fuel Valve
stepper motor.
5. Defective Power Supply
Board or fuse
6. Defective IGST Board
1. Refer to GF-112 and perform Stepper Test (para.
6.3.5) to ensure stepper motor rotates properly
between the 0% (fully closed) and 100% (fully open)
positions. Verify that the FIRE RATE bargraph and
the dial on the Air/Fuel Valve track each other to
indicate proper operation. If operation is not correct,
perform the Stepper Feedback Calibration (GF-112,
para. 6.2.1).
2. Check to ensure that the Air/Fuel Valve is connected
to the Control Box.
3. .Inspect for loose connections between the Air/Fuel
Valve motor and the wiring harness.
4. Replace stepper motor.
5. Check DS1 & DS2 LEDs on Power Supply Board. If
they are not steady ON, replace Power Supply Board.
6. Check “Heartbeat” LED DS1 and verify it is blinking
ON & OFF every second. If not, replace IGST Board.
7-9
WATER HEATER MENU ITEM DESCRIPTIONS
MENU LEVEL & FUNCTION DESCRIPTION
OPERATING MENU
Active Setpoint This is the setpoint temperature to which the control
is operating when operating in the Constant Setpoint
or Remote Setpoint Mode. When in the Constant
Setpoint Mode, this value is equal to the Internal
Setpoint setting in the Configuration Menu. When in
the Remote Setpoint Mode, this value is the setpoint
equivalent to the remote analog signal supplied to the
unit.
Aux Temp For monitoring purposes only
Outdoor Temp Displayed only if outdoor sensor is enabled in the
Configuration Menu.
Flow Rate Flow rate in GPM is displayed only if flow sensor is
enabled.
APPENDIX A
Fire Rate Out Actual fire rate as shown on bar-graph. This function
must be factory-enabled.
Flame Strength Displays flame strength from 0 to 100%.
Run Cycles Displays the total number of run cycles from 0 to
999,999.
Run Hours Displays total run time of unit in hours from 0 to
999,999.
Fault Log Displays information on the last 9 faults.
A-1
APPENDIX A
WATER HEATER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
SETUP MENU
Password Allows password to be entered.
Language English Only
Time Displays time from 12:00am to 11:59pm.
Date Displays dates from 01/01/00 to 12/31/99
Unit of Temp Permits selection of temperature displays in
Comm Address For RS-485 communications (0 to 127). Default
Baud Rate Allows communications Baud Rate to be set
Software Version Identifies the current software version of the
Once the valid password (159) is entered, options
in the Setup, Configuration and Tuning Menus
can be modified.
degrees Fahrenheit (°F) or degrees Celsius (°C).
Default is °F.
address is 0. RS-232 should have its own
(programmable) password.
(2400 to 19.2K). Default is 9600.
control box (Ver 0.00 to Ver 9.99).
A-2
APPENDIX A
WATER HEATER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
CONFIGURATION MENU
Internal Setpoint Allows internal setpoint to be set. Default is 130°F.
Unit Type Allows selection of Boiler or Water Heater.
Unit Size Sets unit size from 0.5 to 3.0 MBTUs. Default is 1.0
Heater Mode It allows selection of either the Constant Setpoint or
Remote Signal Used to set the type of external signal which will be
Setpoint Lo Limit Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit Used to set the maximum allowable setpoint
Temp Hi Limit This is the maximum allowable outlet temperature
MBTU.
Remote Setpoint Mode. Default is Constant
Setpoint.
used when operating in the Remote Setpoint Mode.
The factory default is 4-20 mA/1-5V.
Setpoint Hi Limit). Default is 60°F
(Setpoint Lo Limit to 240°F). Default is 200°F.
(30 to 230°F). Any temperature above this setting
will turn off the unit. The temperature must then drop
5° below this setting to allow the unit to run. Default
Hi Limit is 215°F.
Max Fire Rate Sets the maximum allowable fire rate for the unit
(40% to 100%). Default is 100%.
Aux Start On Dly Specifies the amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a demand)
and checking the pre-purge string to start the boiler.
Default is 0 sec.
Failsafe Mode Allows the Failsafe mode to be set to either Constant
Setpoint or Shutdown. Default is Shutdown.
mA Output Can be set to allow this output to monitor Setpoint,
Outlet Temperature, Fire Rate Out or be set to OFF.
Default is OFF.
Lo Fire Timer Specifies how long (2 to 120 sec.) to remain in the
low fire position after ignition, before going to the
desired output. Default is 2 sec.
Setpt Limiting Allows Setpt Limiting to be enabled or disabled.
Default is disabled.
Setpt Limit Band When Setpt Limiting is enabled, this menu item
allows the Setpt Limit Band to be set from 0°F to
10°F. Default is 5°F.
A-3
APPENDIX A
WATER HEATER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
TUNING MENU
Prop Band Generates a fire rate based on the error that exists
Integral Gain This sets the fraction of the output, due to setpoint
Derivative Time This value (0.0 to 2.0 min.) responds to the rate of
Min Load Adj Setting is adjustable from -50°F to +50°F (Default is
between the setpoint temperature and the actual
outlet temperature. If the actual error is less than the
proportional band setting (1 to 120°F), the fire rate
will be less than 100%. If the error is equal to or
greater than the proportional band setting, the fire
rate will be 100%. (Default is 8°F for a Water Heater)
error, to add or subtract from the output each minute
to move towards the setpoint. Gain is adjustable
from 0.00 to 2.00 (Default is 1.60 for a Water
Heater).
change of the setpoint error. This is the time that this
action advances the output. (Default is 0.10 min. for
a Water Heater)
zero). It adjusts the output by adding an offset to the
breakpoint chart at minimum flow. This is used to
fine tune Feed-Forward (FFWD) output at low flow
levels.
Max Load Adj Setting is adjustable from -50°F to +50°F (Default is
zero). It adjusts the output by changing the scaling of
the breakpoint chart at maximum flow.
FFWD Temp Displays the Feed-Forward temperature.
Outlet Feedback Used to Enable or Disable feedback. Disable this
function for Feed-Forward control only.
Feedback Gain* Adjustable from 0.01 to 1.00 (Default is 0.05).
Breakpoint at 100%
Thru
Breakpoint at 0%
Reset Defaults? Allows all Tuning Menu items to be reset to their
*Only displayed when Heater Tuning Display is enabled by factory authorized
personnel.
Allows breakpoint temperature settings (30°F to
240°F) to be entered for 100% to 0% in 10%
increments. See Appendix D for default values.
Factory Default values.
A-4
APPENDIX B
MESSAGE
DESCRIPTION
DISABLED
HH:MM pm MM/DD/YY
Displayed if ON/OFF switch is set to OFF. The display also
shows the time and date that the unit was disabled.
STANDBY
Displayed when ON/OFF switch is in the ON position, but
displayed.
XX sec
PURGING
XX sec
Displayed during the purge cycle during startup. The
duration of the purge cycle counts up in seconds.
IGNITION TRIAL
XX sec
Displayed during ignition trial of startup sequence. The
duration of cycle counts up in seconds.
FLAME PROVEN
Displayed after flame has been detected for a period of 2
of flame strength.
WARMUP
XX sec
Displayed for 2 minutes during the initial warmup only.
WAIT
Prompts the operator to wait.
STARTUP, STATUS AND FAULT MESSAGES
STARTUP AND STATUS MESSAGES
there is no demand for heat. The time and date are also
DEMAND DELAY
Displayed if Demand Delay is active.
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place
APPENDIX A
FAULT MESSAGE
FAULT DESCRIPTION
HIGH WATER TEMP
SWITCH OPEN
The High Water Temperature Limit Switch is open.
LOW WATER
LEVEL
The Water Level Control board is indicating low water level.
LOW GAS
PRESSURE
The Low Gas Pressure Limit Switch is open.
HIGH GAS
PRESSURE
The High Gas Pressure Limit Switch is open.
INTERLOCK
OPEN
The Remote Interlock is open.
DELAYED
INTERLOCK OPEN
The Delayed Interlock is open.
DURING PURGE
PRG SWTCH OPEN
DURING PURGE
The Purge Position Limit switch on the air/fuel valve opened
during purge.
IGN SWTCH OPEN
DURING IGNITION
The Ignition Position Limit switch on the air/fuel valve opened
during ignition.
IGN SWTCH CLOSED
DURING PURGE
The Ignition Position Limit switch on the air/fuel valve closed
during purge.
PRG SWTCH CLOSED
DURING IGNITION
The Purge Position Limit switch on the air/fuel valve closed
during ignition.
AIRFLOW FAULT
DURING IGN
The Blower Proof Switch opened during ignition.
AIRFLOW FAULT
DURING RUN
The Blower Proof Switch opened during run.
SSOV
SWITCH OPEN
The SSOV switch opened during standby.
SSOV FAULT
DURING PURGE
The SSOV switch opened during purge.
SSOV FAULT
DURING IGN
The SSOV switch closed or failed to open during ignition.
SSOV FAULT
DURING RUN
The SSOV switch closed for more than 15 seconds during
run.
SSOV RELAY
FAILURE
A failure has been detected in one of the relays that control
the SSOV.
FLAME LOSS
DURING IGN
The Flame signal was not seen during ignition or lost within 5
seconds after ignition.
FLAME LOSS
DURING RUN
The Flame signal was lost during run.
HIGH EXHAUST
TEMPERATURE
The High Exhaust Temperature Limit Switch is closed.
was restored is displayed.
FAULT MESSAGES
AIRFLOW FAULT
The Blower Proof Switch opened during purge.
LOSS OF POWER
A power loss had occurred. The time and date when power
APPENDIX B
FAULT MESSAGE
FAULT DESCRIPTION
FLAME
standby.
HEAT DEMAND
FAILURE
The Heat Demand Relays on the Ignition board failed to
activate when commanded.
IGN BOARD
COMM FAULT
A communication fault has occurred between the CPU board
and Ignition board.
DIRECT DRIVE
SIGNAL FAULT
The direct drive signal is not present or is out of range.
REMOTE SETPT
SIGNAL FAULT
The remote setpoint signal is not present or is out of range.
OUTDOOR TEMP
SENSOR FAULT
The temperature measured by the Outdoor Air Sensor is out
of range.
OUTLET TEMP
SENSOR FAULT
The temperature measured by the Outlet Sensor is out of
range.
FFWD TEMP
SENSOR FAULT
The temperature measured by the FFWD Sensor is out of
range.
HIGH WATER
TEMPERATURE
The temperature measured by the Outlet Sensor exceeded
the Temp Hi Limit setting.
LINE VOLTAGE
OUT OF PHASE
The High AC voltage is out of phase from the low AC voltage.
STEPPER MOTOR
FAILURE
The stepper motor failed to move the valve to the desired
position.
NETWORK COMM
FAULT
The RS-485 network information is not present or is
corrupted.
FAULT MESSAGES - Continued
RESIDUAL
The Flame signal was seen for more than 60 seconds during
Temperature Sensor Resistance Chart
(Balco)
APPENDIX C
APPENDIX D
WATER HEATER DEFAULT SETTINGS
MENU & OPTION FACTORY DEFAULT
Setup Menu
Password 0
Language English
Unit of Temp Fahrenheit
Comm Address 0
Baud Rate 9600
Configuration Menu
Internal Setpt 130°F
Unit Type Boiler
Unit Size 1.0 MBTU
Heater Mode Constant Setpoint
Remote Signal
(If Heater Mode = Remote Setpoint)
Outdoor Sensor Disabled
Setpt Lo Limit 60°F
Setpt Hi Limit 200°F
Temp Hi Limit 210°F
4 – 20 mA ,/ 1-5V
Max Fire Rate 100%
Aux Start On Dly 0 sec
Failsafe Mode Shutdown
mA Output Off
Lo Fire Timer 2 sec.
Setpt Limiting Disabled
Setpt Limit Band 5°F
D-1
APPENDIX D
WATER HEATER DEFAULT SETTINGS - Continued
MENU & OPTION FACTORY DEFAULT
Prop Band 8°F
Integral Gain 1.60
Derivative Time 0.10 min
Min Load Adj 0°F
Max Load Adj 0°F
FFWD Temp N/A
Outlet Feedback On
Feedback Gain 0.05
Breakpoint At 100% 77°F
Breakpoint At 90% 81°F
Tuning Menu
Breakpoint At 80% 85°F
Breakpoint At 70% 91°F
Breakpoint At 60% 95°F
Breakpoint At 50% 102°F
Breakpoint At 40% 110°F
Breakpoint At 30% 112°F
Breakpoint At 20% 114°F
Breakpoint At 10% 130°F
Breakpoint At 0% 135°F
Reset Defaults? No
D-2
APPENDIX E
E-1
APPENDIX E
18(45.7)
49 (124.5)
57 (144.8)
16-3/4
22-5/8
71-7/8
71-7/8
19 (48)
15-1/2 (39.4)
6 (15.2) I.D.
FLUE CONN.
3/4 (1.9) DIA.
(ENCLOSURE)
PRESS./TEMP.
RELIEF
2" NPT HOT
2" NPT COLD
3-1/8 (7.9)
(182.6)
5-3/4 (14.6)
REMOTE ALARM & CONTROL
CONNECTION - 3/4 CONDUIT
1-1/4 NPT GAS INLET
(182.6)
(57.5)
(42.5)
LIFTING LUG
VALVE
1"NPT
DRAIN
VALVE
5/8" I.D.
MALE HOSE
CONDENSATE
DRAIN
2"NPT
RECIRC
CONN.
1) ALL DIMENSIONS SHOWN ARE IN INCHES (CENTIMETERS)
AP-A-804
NOTES:
POTABLE WATER HEATER
INTERNATIONAL INC.
1:24
P.K./G.K.
DATE
DWN BY
SIZE
SCALE
APPD
CHKD
B
WATER OUTLET
WATER INLET
29
3 (8)
c.g.
INLET ADAPTER
COMB. AIR INTAKE
AERCO
NORTHVALE, NEW JERSEY 07647
MODEL KC1000 GAS FIRED
22-1/4 (57)
47 (119.4)
22 (56)
(FLOOR FLANGE)
2) DRAIN VALVE & RELIEF VALVE ARE INCLUDED SEPARATELY IN SHIPMENT
A
2-1-95
DIMENSIONAL DRAWING
AC SERVICE C0NN.
3/4 CONDUIT
120VAC SINGLE PHASE
20 AMP W/GRD
35 (89)
TYP.
4-PLCS
(
)
c.g.
78-1/2
(199.4)
13-9/16
(34.4)
3/4" NPT GAS VENT
CONN. FOR "IRI GAS
TRAIN OPTION" ONLY
(OPTIONAL O.A.
AVAIL. - 6" OD)
HEAT EXCHANGER DESIGN STANDARDS
MAXIMUM
TEMP. (°F)
ASME B & PV CODE SECTION IV STAMP HLW
SHELL SIDE
PRESS. (PSIG)
155
MAX. WORKINGTEST PRESS.
(PSIG)
210233
REV.
E-2
APPENDIX E
1/8" NPT x 3/8" O.D. TUBE AL. COMP. FTG.
3/8" NPT x 3/8" O.D. TUBE AL. COMP. FTG.
32
GP-122614
1
29
35
31
GM-20934
1
123581
GP-161146
1
1 BLOWER TO AIR VA. INLET HOSE
GAS INLET PIPE
30
34
GP-18894
1
GP-161147
1
GAS PRESS. CONTROL TUBE
VALVE TO BURNER AIR HOSE
33
201211
1
AIR/FUEL VALVE (NATURAL GAS)
36
GM-20874
1
BURNER ASSEMBLY (NATURAL GAS)
28
GP-122561
1 DAMPER TO BLOWER INLET HOSE
27
GP-122835
2 SPACER
26
GP-122669
1 AIR INLET SCREEN
25
GP-161152
1
23
124935
1
BLOWER AIR INLET SHUTTER
BLOWER (INCLUDES CAPACITOR 124936)
1/4" MNPT x 1/8" FNPT RED. BUSHING
44
45
GP-122403
123536
11LOW PRESSURE GAS SWITCH
EXH. MANIFOLD TO COMB. CHAMB. GASKET
18
GP-122537
1
EXH. MANIFOLD TO LOWER HEAD SEAL
17
GP-161151
1
15
16
1
GP-18899
GP-18900
1
COMBUSTION CHAMBER LINER
BURNER FLANGE GASKET
14
GP-122551
1 TEFLON RELEASE GASKET
21
20
19
GP-122608
GP-122573
1
1
GM-122828
1
1-1/2" NPT P&T RELIEF VALVE
1-1/2" NPT x 3" LG. NIPPLE
DRAIN VALVE ASSEMBLY
1/4"NPT x 3/8"O.D. TUBE 90° COMP. FTG.
4
GP-8-3-1
1
EXHAUST MANIFOLD
ITEM
QTYPART NO.DESCRIPTION
HOSE CLAMP 13/16" - 1-3/4"∅ RANGE
1
GM-123352
7
EXHAUST MANIFOLD DRAIN HOSE
8
GP-122540
1
5
6
GP-20885
GM-20844-2
11EXHAUST MANIFOLD INSULATION
EXHAUST MANIFOLD
46
GP-122822
1 TEMPERATURE SWITCH
43
61002-14
1
38
2
41
GM-20872
1
181198
GP-122464
1
1
BLOWER PROOF SWITCH
CONTROL BOX ASSEMBLY
BTU TRANSMITTER ASSEMBLY
IGNITION TRANSFORMER
BLOWER MOTOR CAPACITOR
24
124936
1
22
24
37
19
38
46
21
20
25
26
4544
48
47
49
123463
EXHAUST TEMPERATURE SWITCH1
47
123448
SHELL SENSOR1
48
122843
LOW WATER CUT-OFF1
GP-161145
HOT SUPPLY LINE1
3
161559
37
POWER BOX ASSEMBLY1
PART NO.
ITEM
QTY
LOAD-ALERT PARTS
DESCRIPTION
PART NO.
ITEM
QTY
OTHER ACCESSORIES
DESCRIPTION
PART NO.
ITEM
QTY
CONTROLS
DESCRIPTION
PART NO.
ITEM
QTY
BLOWER
DESCRIPTION
PART NO.
ITEM
QTY
BURNER AND AIR/FUEL VALVE
DESCRIPTION
ITEM
HEAT EXCHANGER
PART NO. QTYDESCRIPTION
HEAT EXCHANGER ASS'Y
1
GM-20881
1
UPPER HEAD LINER
SHELL GASKET
RELEASE GASKET
GP-123077
GP-18532
GP-18556
11
12
13
2
1
1
DESCRIPTION
PART NO.
ITEM
QTY
GASKETS
39
GP-122569
1 IGNITION CABLE ASSEMBLY
GAS TRAIN WIRING HARNESS1
161450
42
39
40
161560
1 INPUT/OUTPUT (I/O) BOX ASSEMBLY
CONDENSATE CUP ASSEMBLY
GP-123337
9
1
VENT MOUNTING FLANGE
GP-122849
10
2
23
*
GP-123050
1 EXTERNAL GAS SHUT-OFF VALVE
* - NOT SHOWN IN THE DRAWING
TEMPERATURE SWITCH THERMOWELL
123711
50
2
50
SHELL WIRING HARNESS
EXHAUST TEMP. SWITCH HARNESS
52
51
124334
161569
1
1
**
**
**
**
**
** - SEE DRAWING PL-A-136 FOR INSTALLATION DETAIL
51
KC1000 WATER HEATER
PARTS LIST
DATE
DATE
SCALE
APPD.
DWN.BY
CZ
(SH. 1 OF 2)
PL-A-137
041304
G
NORTHVALE, NJ 07647
INTERNATIONAL, INC.
AERCO
GAS TRAIN ASSEMBLY (IRI; NATURAL GAS)
GAS TRAIN ASSEMBLY (FM; NATURAL GAS)
GM-18997
PART NO.
22
ITEM
181182
1
QTY
DESCRIPTION
GAS TRAIN
BURNER ASSEMBLY (PROPANE)
GM-20933
201222
AIR/FUEL VALVE (PROPANE)
GAS TRAIN ASSEMBLY (FM; PROPANE)
GAS TRAIN ASSEMBLY (IRI; PROPANE)
181191
181123
E-3
APPENDIX E
14
36
35
16
34
7
15
18
17
1
6
10
33
29
32
31
30
40
2
41
3
4
2728
49
43
SEE DETAIL "A"
EXPLODED
DETAIL "A"
13
12
11
42
9
5
8
SEE DRAWING PL-A-134 FOR AVAILABLE PARTS
52
AERCO
KC1000 WATER HEATER
CZ
DWN.BY
APPD.
SCALE
041304
DATE
(SH. 2 OF 2)
PL-A-137
DATE
G
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
PARTS LIST
E-4
APPENDIX E
1 1/2" SAFETY SHUT-OFF VALVE
DIFFERENTIAL PRESSURE REGULATOR W/ BROWN SPRING
BURNER/GAS VA. ADAPTOR
2
3
4
5
1GM-
161095
GAS COCK
GP-
122415
GP-122409 1
1
1241501
53
4
2
1
1
1241381 SSOV ACTUATOR
FRONT VIEWRIGHT SIDE VIEWREAR VIEW
DESCRIPTIONITEM PART NO. REQ
PARTS LIST
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
KC1000 GAS TRAIN ASSEMBLY
(FACTORY MUTUAL)
APPD.
SCALE
DATE
CZ
DWN.BYDATE
043002
PL-A-135
B
REV.
6
7
GP-122548
6
1 SPRING (BROWN) FOR DIFFERENTIAL PRESSURE REGULATOR
- THE SECOND O-RING (NOT SHOWN IN THE DRAWING) GOES TO THE GAS OUTLET FLANGE OF THE AIR-FUEL VALVE.
*
GAS TRAIN O-RING
*
GP-122406 2
7
E-5
APPENDIX E
5
4
13
7
18
16
6
2
3
1/4"NPT x 3/8"OD TUBE 90° COMP. FTG.
PUMP OUTLET TUBE
1/4"NPT STREET ELBOW
1/4"NPT CLOSE NIPPLE
1/4"NPT BALL VALVE
CIRCULATING PUMP
2" COLD WATER INLET PIPE
1
GM-188591
GP-122756
GP-9-430
12820-1
GP-8-3-1
GP-122759
2
4
3
6
5
7
1
1
3
128232
3
1
2"NPT 90° COLD WATER INLET ELBOW
HYD. ZERO & CONT. ORIFICE TUBE ASS'Y
1/4"NPT x 3/8"OD TUBE STR. COMP. FTG.
1/4"NPT x 3/8"OD TUBE 45° COMP. FTG.
HOT WATER MIXING ORIFICE ASS'Y
COLD WATER MIXING ORIFICE ASS'Y
BTU TRANSMITTER SENSOR
ORIFICE DISC
ORIFICE RETAINING CLIP
TUBING ASS'Y
HYDRAULIC ZERO NEEDLE VALVE
122075
GP-122677-1
GP-122613-1
GM-122687
GM-122761
GP-122506
GM-122400
11
9
8
10
12
14
13
1
1
1
1
1
4
1
123449
GP-122552
GM-161212
GP-122512
16
15
17
18
1
1
1
1
ITEMQTY.PART NO.DESCRIPTION
NORTHVALE, NJ 07647
(SH. 1 OF 2)
PL-A-134
KC1000 WATER HEATER
BTU TRANSMITTER ASSEMBLY
(COMPLETE ASS’Y GM-20872)
INTERNATIONAL, INC.
SCALE
APPD.
DWN.BY
041304CZ
DATE
DATE
AERCO
B
E-6
APPENDIX E
17
14
J
15
1
5
9
8
4
5
11
10
4
13
12
NORTHVALE, NJ 07647
(SH. 2 OF 2)
PL-A-134
KC1000 WATER HEATER
BTU TRANSMITTER ASSEMBLY
(COMPLETE ASS’Y GM-20872)
INTERNATIONAL, INC.
SCALE
APPD.
DWN.BY
041304CZ
DATE
DATE
AERCO
B
E-7
APPENDIX E
DWN.BY
SCALE
APPD.
KC1000 WATER HEATER
IRI GAS TRAIN
SD-A-606
030801PDR
DATE
DATE
NTS
REV.
D
NORTHVALE, NJ 07647
INTERNATIONAL, INC.
AERCO
3/4" NORMALLY OPEN
VENT VALVE
P/N GP-122774
SSOV ACTUATOR
W/ P.O.C. SWITCH
P/N 124138
TO AIR-FUEL VALVE ASS'Y
1 1/4" NPT GAS REGULATOR
P/N GP-122415 (NAT. GAS)
123543 (PROPANE)
1 1/2" IRI SSOV
P/N 124137
VENT TO ATMOSPHERE
PER ANSI Z223.1 (NFPA54)
HEATER
BOUNDARY
SSOV ACTUATOR
W/O P.O.C. SWITCH
P/N 69038
LOW GAS PRESSURE SWITCH
P/N GP-122403
TOP VIEW
E-8
APPENDIX F
F-1
APPENDIX F
F-2
APPENDIX G
CLOSURE SWITCH
PROOF OF
GRN
WHT
60 Hz
120 VAC IN
20 A
NEU
GND
HOT
NC
C
GNH
GND
H
G
N
123456123456789
123456789101112131415
123456789101112
CONTROL BOX CONNECTORS
LOW GAS PRESS. SW.
BLOWER PROOF SW.
SAFETY SHUTOFF VALVE
OVER TEMPERATURE SWITCHES
BLOWER
IGNITOR
TRANSFORMER
WATER LEVEL PROBE
FLAME ROD
AC WIRING BOX
SHELL
TEMP.
SENSOR
GAS FIRED
SYSTEM SCHEMATIC
161613
16-PIN CONNECTOR
19-PIN CONNECTOR
9-PIN CONNECTOR7-PIN CONNECTOR
MANUAL RESET
HIGH GAS PRESS. SW.
BLK
STEPPING
MOTOR
PURGE
POSITION
IGNITION
POSITION
SWITCH
SWITCH
AIR/FUEL VALVE
BLK
YEL
WHT
53
5K
C
B
A
3
RED
GRN
BLU
2
10K
1
(KC 1000)
150
151153
152
153
152
151
150
7
133134
181917 16
14151613
154
AUTO RESET
IGNITION
265200
BLOWER
XFORMER
RELAY
24 VAC
194
193
192
191
190
195
201
206
209
208
210
203
202
204
FUSE
FUS
E
203
206
207
265
205
210
204
202
207
209
200
201
SENSOR
* FFWD
TEMP.
180
* BTU PUMP
183
183
184
182
191
141
184
194
193
137
155
136
154
135
192
138182
140
190
195
172
171
170
169
168
167
166
165
164
163
162
161
149
148
147
146
145
141
149
148
146145
147
181
136
137
209
208
* WATER HEATERS ONLY
6-PIN CONNECTOR
SHEET 1 OF 2
321
TO CONTROL BOX
320
321
322
TO BURNER
GND
AS FOLLOWS UNLESS OTHERWISE SPECIFIED
THIRD ANGLE PROJECTION
ALL DIMENSIONS ARE IN INCHES AND ALL TOLERANCES ARE
XX ±.015 XXX ± .005 FRACTIONS 1/32± ANGLES ±1°
PERPENDICULARITY/PARALLELISM/FLATNESS .003 TOTAL
DIAMETERS ON A COMMON AXIS
ALL DIMENSIONS ARE AFTER FINISH OR PLATING
RELEASED FOR PRODUCTION
THESE DRAWINGS AND/OR SPECIFICATIONS ARE THE PROPERTY OF AERCO INTERNATIONAL, INC. THEY ARE ISSUED IN STRICT CONFIDENCE AND
SHALL NOT BE REPRODUCED, COPIED, OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF APPARATUS WITHOUT PERMISSION OF THE OWNER.
FIM
A
REVISIONS
REV ECO
061302 MD
CK'D
DATE
BY
159 PARIS AVE, NORTHVALE, N.J.
061302MD
ORIGINAL
B
DRAWN BY:
DATE:
DATE:CHECKED BY:
DWG. SIZE
MAT'L SPEC.:
TITLE
.005 TOTAL
C
REVDWG. NO.:
B
FYP
ADDED GROUND WIRES 320, 321 & 322
100703 JM
031603
GENERAL CORRECTIONS TO SCHEMATIC
C
GKU
MC
173
1K
INTERNATIONAL INC.
G-1
APPENDIX G
CONTROL BOX CONNECTORS
GAS FIRED BOILER SYSTEM
WIRING SCHEMATIC
161613
1210 1113 14161517 18 19212022 23 24
24-PIN CONNECTOR
241
240242
243
244
245251
246250
247
252254
253
968 75 4 312
212
220
221
211
219
16-PIN CONNECTOR
8546 791 2 31116141513 1210
226
213
214
216
215
7
6
7
5
3
4
6
1
2
OUT
IN
OUT
IN
IN
OUT
FAULT
RELAY
NOT USED
DELAYED INTLK
EXHAUST TEMP
REMOTE INTLK
N.O.
C
4
3
5
1
2
NOT USED
N.C.
C
N.O.
N.C.
RELAY
AUX
12
13
14
11
SENSOR EXCIT. (12 VDC)
BMS (PWM) IN
ANALOG IN
OXYGEN SENSOR IN
FLOW SENSOR IN
CO SENSOR IN
+
-
-
+
-
+
-
+
AUX SENSOR IN
SENSOR COMMON IN
-
+
1
OUTDOOR AIR SENSOR IN
9
8
7
5
3
4
2
6
10
OUT
IN
LONWORKS
A
B
GND
4
1
2
1
-
+
2
2
1
3
3
ANALOG OUT
15
16
SHIELD
B
RS-485 IN
A
1 2437 8659 101211
87654321
87654321121110913 14 15
231
234232
233
238236
235237
239
INPUT/OUTPUT BOX
(KC 1000)
+
-
LS2
1
LS1
LS4
LS3
J3J2
J1
SHEET 2 OF 2
AS FOLLOWS UNLESS OTHERWISE SPECIFIED
THIRD ANGLE PROJECTION
ALL DIMENSIONS ARE IN INCHES AND ALL TOLERANCES ARE
XX ±.015 XXX ± .005 FRACTIONS 1/32± ANGLES ±1°
PERPENDICULARITY/PARALLELISM/FLATNESS .003 TOTAL
DIAMETERS ON A COMMON AXIS
ALL DIMENSIONS ARE AFTER FINISH OR PLATING
SEE SHEET ONE
THESE DRAWINGS AND/OR SPECIFICATIONS ARE THE PROPERTY OF AERCO INTERNATIONAL, INC. THEY ARE ISSUED IN STRICT CONFIDENCE AND
SHALL NOT BE REPRODUCED, COPIED, OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF APPARATUS WITHOUT PERMISSION OF THE OWNER.
REVISIONS
REV ECO
CK'D
DATEBY
159 PARIS AVE, NORTHVALE, N.J.
061302MD
ORIGINAL
B
DRAWN BY:DATE:
DATE:CHECKED BY:
DWG. SIZE
MAT'L SPEC.:
TITLE
.005 TOTAL
C
REVDWG. NO.:
16
INTERNATIONAL INC.
G-2
APPENDIX H
V.F.D. Display Module
P/N: 124527
Display Board
P/N: 124365
C.P.U. Board
P/N: 124364
Low Water Cutoff Board
P/N: 124363
Power Supply Board
P/N: 124362
Ignition/Stepper Board
P/N: 124361
Connector Board
P/N: 124366
KC1000 CONTROL PANEL EXPLODED VIEW
H-1
APPENDIX H
P1
P2
P3
P4
P5
P6
SHELL HARNESS
CONNECTOR
(19 PIN)
INTERLOCK HARNESS
CONNECTOR
(16 PIN)
EXT. SENSOR/COMM
HARNESS CONNECTOR
(24 PIN)
GAS TRAIN HARNESS
CONNECTOR
(9 PIN)
A/F VALVE
HARNESS
CONNECTOR
(16 PIN)
SENSOR
HARNESS
CONNECTOR
(7 PIN)
TO INPUT/OUTPUT (I/O) BOX
KC1000 CONTROL PANEL REAR VIEW
H-2
STANDARD WARRANTY:
INTERNATIONAL, INC.
Year
3
Discount From Then Prevailing List Price
100%
4
70%
5
40%
Gas-Fired Water Heater
PRESSURE VESSEL: 10 YEARS NON-PRORATED
The shell shall carry a non-prorated 10 year guarantee from shipment against leakage due to
thermal shock, water side corrosion, mechanical defects or workmanship.
HEAT EXCHANGER TUBES/COMBUSTION CHAMBER: 5 YEARS
The heat exchanger/combustion chamber shall carry a 5 year prorated, limited warranty from
shipment against any condensate corrosion, thermal stress failure, mechanical defects or
workmanship. Operation of the boiler using contaminated air will void the warranty. The heat
exchangers combustion chamber shall not be warranted from failure due to scaling, liming,
corrosion, or erosion due to water or installation conditions. AERCO will repair, rebuild or
exchange, at its option the heat exchanger/combustion chamber according to the following
schedule:
“C-MORE” CONTROL PANEL: 2 YEARS FROM SHIPMENT
AERCO labeled control panels are conditionally warranted against failure for (2) two years from
shipment.
OTHER COMPONENTS: 18 MONTHS FROM SHIPMENT
All other components, with the exception of the ignitor and flame detector, are conditionally
guaranteed against any failure for 18 months from shipment.
AERCO shall accept no responsibility if such item has been improperly installed, operated, or
maintained or if the buyer has permitted any unauthorized modification, adjustment, and/or
repairs to the item.
The warranty as set forth on the back page of the Operations & Maintenance Manual is in lieu
of and not in addition to any other express or implied warranties in any documents, or under
any law. No salesman or other representative of AERCO has any authority to expand
warranties beyond the face of the said warranty and purchaser shall not rely on any oral
statement except as stated in the said warranty. An Officer of AERCO must do any
modifications to this warranty in writing. AERCO MAKES NO WARRANTY OF
MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER
EXPRESS OR IMPLIED WARRANTIES. AERCO disclaims all responsibility for any special,
incidental or consequential damages. Any claim relating to the product must be filed with
AERCO not later than 14 days after the event-giving rise to such claim. Any claims relating to
this product shall be limited to the sale price of the product at the time of sale. The sale of the
product is specifically conditioned upon acceptance of these terms.
03/01/05 W-1 (D102.0)
STANDARD WARRANTY:
INTERNATIONAL, INC.
Gas-Fired Water Heater
CONDITIONS OF WARRANTY
Should an AERCO gas-fired (natural gas or propane only) water heater or hydronic boiler fail
for any of the above reasons within the specified time period from the date of original
shipment(s), AERCO shall at its option modify, repair or exchange the defective item. AERCO
shall have the option of having the item returned, FOB its factory, or to make field replacements
at the point of installation. In no event shall AERCO be held liable for replacement labor
charges or for freight or handling charges.
AERCO shall accept no responsibility if such item has been improperly installed, operated, or
maintained or if the buyer has permitted any unauthorized modification, adjustment, and/or
repairs to the item. The use of replacement parts not manufactured or sold by AERCO will void
any warranty, express or limited.
In order to process a warranty claim a formal purchase order number is required prior to
shipment of any warranty item. In addition, the returned item must include a Returned Goods
Authorization (RGA) label, attached to the shipping carton, which identifies the item's return
address, register number and factory authorized RGA number.
Warranty coverage for all components and equipment mentioned in said warranty are not valid
unless the water heater or hydronic boiler is started up by a factory certified SST (Service,
Start-Up and Troubleshooting) Technician and an AERCO start-up sheet is completed.
This warranty coverage is only applicable within the United States and Canada. All other
geographical areas carry a standard warranty of 18 months from date of shipment or 12 months
from startup, whichever comes first.
03/01/05 W-2 (D102.1)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.