AERCO GF-111 User Manual

Page 1
AERCO International, Inc. • 159 Paris Ave. • Northvale, New Jersey 07647 • Phone: 201-768-2400 FAX: 201-768-7789
KC Series Gas Fired Water Heater
GF-111
Applicable to Serial Numbers G-10-1232 and above
KC Series Gas Fired Water Heating System
Natural Gas or Propane Fired,
Condensing and Forced Draft Hot Water Heater
Patent No. 4,852,524
1,000,000 BTU/HR Input
Printed in U.S.A. REVISED 12/10
Page 2
AERCO International, Inc. • 159 Paris Ave. • Northvale, New Jersey 07647 • Phone: 201-768-2400 FAX: 201-768-7789
KC Series Gas Fired Water Heater
GF-111
Telephone Support
Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday)
(800) 526-0288
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
www.aerco.com
© AERCO International, Inc., 2010
The information contained in this operation and maintenance manual is subject to change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Printed in U.S.A. REVISED 12/10
Page 3
CONTENTS
Para.
Subject
Page
1.1
Warnings & Cautions
1-1
1.2
Emergency Shutdown
1-2
Para.
Subject
Page
1.3
Prolonged Shutdown
1-2
Para.
Subject
Page
2.1
Receiving the Unit
2-1
2.2
Unpacking
2-1
2.3
Installation
2-2
2.4
Gas Supply Piping
2-4
2.5
Electrical Supply
2-5
Para.
Subject
Page
2.6
Field Control W iring
2-6
2.7
Flue Gas Vent Installation
2-8
2.8
Combustion Air
2-8
Para.
Subject
Page
3.1
Introduction
3-1
3.2
Control Panel Description
3-1
3.3
Control Panel Menus
3-3
3.4
Operating Menu
3-4
3.5
Setup Menu
3-4
Para.
Subject
Page
3.6
Configuration Menu
3-6
3.7
Tuning Menu
3-7
3.8
Start Sequence
3-7
3.9
Start/Stop Levels
3-9
Para.
Subject
Page
4-1
Initial Startup Requirements
4-1
4-2
Tools and Instrumentation for Combustion Calibration
4-1
4-3
Natural Gas Combustion Calibration
4-2
Para.
Subject
Page
4-4
Propane Combustion Calibration
4-5
4.5
Unit Reassembly
4-5
4.6
Temperature Control Calibration
4-6
4.7
Over-Temperature Limit Switch Adjustments
4-7
Para.
Subject
Page
5.1
Testing of Safety Devices
5-1
5.2
Low Gas Pressure Fault Test
5-1
5.3
High Gas Pressure Test
5-1
5.4
Low Water Level Fault Test
5-2
5.5
Water Temperature Fault Test
5-2
5.6
Interlock Tests
5-3
5.7
Flame Fault Test
5-3
5.8
Air Flow Fault Test
5-4
Para.
Subject
Page
5.9
SSOV Proof of Closure Switch
5-4
5.10
Purge Switch Open During Purge
5-5
5.11
Ignition Switch Open During Ignition
5-5
GF-111 THE AERCO KC1000 GAS FIRED DOMESTIC WATER HEATER
Operating & Maintenance Instructions

FOREWARD A

Section 1 – SAFETY PRECAUTIONS 1-1

Section 2 – INSTALLATION PROCEDURES 2-1

Section 3 – CONTROL PANEL OPERATING PROCEDURES 3-1

Section 4 – INITIAL START-UP 4-1

Section 5 – SAFETY DEVICE TESTING PROCEDURES 5-1

5.12 Safety Pressure Relief Valve Test
5-6
i
Page 4
CONTENTS
Para.
Subject
Page
6.1
Maintenance Schedule
6-1
6.2
Spark Ignitor
6-1
6.3
Flame Detector
6-2
6.4
Combustion Calibration
6-2
6.5
Safety Device Testing
6-2
6.6
BTU Transmitter Pump Lubrication
6-2
Para.
Subject
Page
6.7
BTU Transmitter Assembly
6-3
6.8
Manifold and Exhaust Tubes
6-5
6.9
Heat Exchanger Inspection
6-8
6.10
Condensate Drain Assembly
6-9
Para.
Subject
Page
7.1
Introduction
7-1
Para.
Subject
Page
Para.
Subject
Page
8.1
Introduction
8-1
8.2
RS232 Communication Setup
8-1
Para.
Subject
Page
8.3
Menu Processing Utilizing RS232 Communication
8-1
8.4
Data Logging
8-2
App
Subject
Page
Descriptions
Messages
Chart
D
Water Heater Default Settings
D-1
App
Subject
Page
E
Dimensional and Parts Drawings
E-1
F
Piping Drawings
F-1
G
Wiring Schematics
G-1
H
KC1000 Control Panel Views
H-1
I
Recommended Spare Parts
I-1

Section 6 – MAINTENANCE 6-1

Section 7 – TROUBLESHOOTING 7-1

Section 8 – RS232 COMMUNICATION 8-1

APPENDICES

A Water Heater Menu Item
B
C
Startup, Status and Fault
Temperature Sensor Resistance
A-1
B-1
C-1

WARRANTIES W-1

ii
Page 5
FOREWORD
Foreword
The AERCO KC Water Heating System is a true industry advance that meets the needs of today's energy and environmental concerns. Designed for use in any domestic water heating system, it provides constant temperature water, regardless of flow rate. It’s small space requirements and venting capabilities allow maximum installation flexibility. The KC Heater’s load tracking controls modulate over a 20:1 turndown ratio for natural gas units and a 14:1 turndown ratio for propane units to match fluctuating system loads and yield high thermal efficiencies.
With it’s compact design and direct or chimney venting, the KC Water Heating System is adaptable to any installation. Efficiency, reliability and longevity make the KC Water Heating System a true step forward in Water Heating System design.
After prolonged shutdown, it is recommended that the startup procedures in Section 4 and test procedures in Section 5 of this manual be performed to verify system operating parameters. If there is an emergency, turn off the electrical power supply to the KC Heater or close the manual gas valve located before the unit. The installer is to identify the emergency shut-off device. FOR SERVICE OR PARTS, contact your local sales representative or AERCO INTERNATIONAL.
NAME:
ORGANIZATION:
ADDRESS:
TELEPHONE:
INSTALLATION DATE: ____________________________________________________
A
Page 6
Page 7
SAFETY PRECAUTIONS
SECTION 1 -- SAFETY PRECAUTIONS

1.1 WARNINGS & CAUTIONS

Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-
54) for gas-fired heaters and ANSI/NFPASB for LP gas-fired heaters. Where applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CGA B149, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
See pages 1-2 through 1-4 for important information regarding installation of units within the Commonwealth of Massachusetts.
IMPORTANT
This Instruction Manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
IMPORTANT
Read the following restrictions prior to installing the water heater:
1. The heater can only be used for applications where the chlorine concentra­tions Do Not Exceed 4 mg/L which is the Environmental Protection Agency limit for chlorine concentrations in drinking water.
2. Do Not use this heater for a pool heating application.
3. If this heater was ordered with the optional copper-lined, carbon steel shell, items 1 and 2 Do Not Apply. (Contact your local AERCO representative to verify heater shell material.
WARNINGS!
MUST BE OBSERVED TO PREVENT SERIOUS INJURY.
WARNING!
BEFORE ATTEMPTING TO PER­FORM ANY MAINTENANCE ON THE UNIT, SHUT OFF ALL GAS AND ELECTRICAL INPUTS TO THE UNIT.
WARNING
DO NOT USE MATCHES, CANDLES, FLAMES, OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.
WARNING!
THE EXHAUST VENT PIPE OF THE UNIT OPERATES UNDER A POSI­TIVE PRESSURE AND THERE­FORE MUST BE COMPLETELY SEALED TO PREVENT LEAKAGE OF COMBUSTION PRODUCTS INTO LIVING SPACES.
WARNING!
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR DAMAGE TO EQUIPMENT WHEN RELEASED. BE SURE TO SHUT OFF ALL INCOMING AND OUTGOING WATER SHUTOFF VALVES. CAREFULLY DECREASE ALL TRAPPED PRESSURES TO ZERO BEFORE PERFORMING MAINTENANCE.
WARNING!
ELECTRICAL VOLTAGES OF 120 VAC ARE USED IN THIS EQUIP­MENT. THEREFORE THE COVER ON THE UNIT’S POWER BOX (LOCATED ON THE FRONT RIGHT SIDE OF THE UNIT UNDER THE HOOD AND SHEET METAL SIDE PANEL) MUST BE INSTALLED AT ALL TIMES, EXCEPT DURING MAINTENANCE AND SERVICING.
1-1
Page 8
SAFETY PRECAUTIONS
MANUAL GAS SHUTOFF VALVE
VALVE OPEN
VALVE CLOSED
CAUTIONS!
Must be observed to prevent equipment damage or loss of operating effectiveness.
CAUTION!
Many soaps used for gas pipe leak testing
must
are corrosive to metals. The piping rinsed thoroughly with clean water after leak checks have been completed.
be
CAUTION!
DO NOT use this heater if any part has been under water. Call a qualified service technician to inspect and replace any part that has been under water.

1.2 EMERGENCY SHUTDOWN

If overheating occurs or the gas supply fails to shut off, close the manual gas shutoff valve (Figure 1-1) located external to the unit.
IMPORTANT
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.

1.3 PROLONGED SHUTDOWN

After prolonged shutdown, it is recommended that the startup procedures in Chapter 4 and the safety device test procedures in Chapter 5 of this manual be performed, to verify all system­operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO heater and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
Water heater Installations within the Commonwealth of Massachusetts must conform to the following requirements:
Heater must be installed by a plumber or a gas fitter who is licensed within the Commonwealth of
Prior to unit operation, the complete gas train and all connections must be leak tested using a
The vent termination must be located a minimum of 4 feet above grade level.
If side-wall venting is used, the installation must conform to the following requirements extracted
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
Figure 1-1
Manual Gas Shutoff Valve
IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS
Massachusetts.
non-corrosive soap.
from 248 CMR 5.08 (2):
1-2
Page 9
SAFETY PRECAUTIONS
INSTALLATION OF CARBON MONOXIDE DETECTORS
1. horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
. At the time of installation of the side wall
APPROVED CARBON MONOXIDE DETECTORS.
2. accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3.
SIGNAGE building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4.
INSPECTION equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b)
EXEMPTIONS
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED.
(c) the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
. A metal or plastic identification plate shall be permanently mounted to the exterior of the
. The state or local gas inspector of the side wall horizontally vented gas fueled
: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
Each carbon monoxide detector as required in
When
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
(d) When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
1-3
Page 10
SAFETY PRECAUTIONS
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
______________________________________ [End of Extracted Information From 248 CMR 5.08 (2)]
1-4
Page 11
SECTION 2 - INSTALLATION

2.1 RECEIVING THE UNIT

Each KC1000 Heater is shipped as a single crated unit. The shipping weight is approximately 1500 lb. and must be moved with the proper rig­ging equipment for safety and to avoid damage. The unit should be completely inspected at the time of receipt from the carrier before the bill of lading is signed. Each unit has Tip-N-Tell indicator on the outside of the crate. This indicates if the unit has been turned on its side.
If the Tip-N-Tell indicator is tripped, do not sign for the shipment. Note the information on the carrier’s paperwork and request a freight claim and inspection by a claims adjuster before proceeding. Any other visual damage to the packaging materials should also be made clear to the delivering carrier.

2.2 UNPACKING

Carefully unpack the unit. Take care not to damage the unit jacket when cutting away packaging materials. A close inspection of the unit should be made to determine if there has been any damage incurred during shipment that was not indicated by the Tip-N-Tell indicator.
INSTALLATION
The freight carrier should be notified immediately if any damage is detected. The following accessories come standard with each unit and are packed separately within the unit’s packing container
Spare Spark Ignitor
Spare Flame Detector
Manual 1-1/4" Gas Shutoff Valve
Drain Valve Assembly
ASME Pressure/Temperature
Relief Valve
Ignitor Removal Tool (One per Site)
2 Lifting Lugs
Stainless Steel Condensate Cup
Flue Clamps (2 Pieces)
Shell Cap
Wing Nut for Shell Cap
Optional accessories are also separately packed within the unit’s packing container. Standard and optional accessories shipped with the unit should be identified and put in a safe place until they are installed for use.
Figure 2.1 Heater Clearance
2-1
Page 12
INSTALLATION

2.3 INSTALLATION

The unit must be installed with the prescribed clearances for service as shown in Fig 2.1 These are the by AERCO. Local building codes may require more clearance and take precedence.
KEEP UNIT AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS AND FLAMMABLE VAPORS AND LIQUIDS.
MASSACHUSSETTS INSTALLATIONS
For water heater installations within the Commonwealth of Massachusetts, the heater must be installed by a plumber or a gas fitter who is licensed within the Commonwealth. In addition, the installation must comply with all requirements specified in Section 1 (Safety Precautions), pages 1-2 through 1-4.

2.3.1 SETTING THE UNIT

Locate the lifting lugs, shipped with the unit, and attach them to the 5/8” x 11 studs at the top of the unit. Remove the unit from the wooden skid and place in position using a block and tackle or hoist attached to the lifting lugs. (see Fig. 2.2). USE THE LIFTING LUGS TO MOVE THE UNIT.
The KC-1000 is U/L approved for installation on combustible flooring. A 4” to 6" high house­keeping concrete pad is recommended and allows for sufficient drainage of the condensate.
The unit must be secured using only the holes provided in the frame base. Do not use piping to secure the unit in place. See drawing AP-A-576 in Appendix E for the base frame dimensions.
In multiple unit installations, it is important to plan the position of each unit. Sufficient space for piping connections and maintenance require­ments must be given. All piping must include ample provision for expansion.
minimum clearance dimensions required
WARNING !

Figure 2.2

Lifting Lug Location
2.3.2 WATER INLET AND OUTLET PIPING
The locations of the 2" NPT cold water inlet and hot water outlet piping connections are shown in Figure 2.3. Flow rates through the unit are limited to 30 gpm continuous and 40 gpm intermittent.
The heater is shipped with a 2” NPT x 12” long stainless steel flex connector. It is important that this flex connector be installed at the hot water outlet as mentioned in the installation diagrams to ensure compliance with the AERCO warranty. If it is desired to install the flex connector elbowed towards the rear or top of the unit, two additional parts (not supplied with heater) are required. These parts are a 2”NPT x 6” long 304 or 316 stainless nipple and a 2” NPT 304 or 316 stainless elbow. Both of these parts must be capable of withstanding up to 155 psig @ 210°F. These parts may be added between the heater outlet connection and the flex connector. However, if this heater was ordered with the optional copper-lined carbon steel shell (contact your local AERCO Representative to verify), it is not shipped with, and does not require a flex connector.
2-2
Page 13
INSTALLATION
Shut-off valves and union conections must be installed in the inlet and outlet lines for main­tenance. The use of dielectric unions is recom­mended. Install the piping and accessories as per the following drawings, located in Appendix F of this manual.
SD-A-424 for single units
SD-A-425 for multiple units
SD-A-432 for single units with a stratified
tank
SD-A-434 for multiple units with a stratified storage tank
NOTE:
All piping must be arranged so that it does not interfere with removal of any cover, inhibit service or maintenance, or prevent access between the unit and walls, or another unit.

Figure 2.3

Inlet and Outlet Location
2.3.3 TEST HOSE BIB
A Test Hose Bib connection, upstream of the shut off valve on the hot water outlet, is required for startup and testing. It should be a minimum of 3/4". It cannot be omitted (See Fig. 2.4a)
Figure 2.4a
Hose Bib Location
NOTE:
The maximum working pressure for installations within the Province of Alberta is 87 psig. Therefore, a pressure & temperature relief valve with a setting of 75 psig/210°F is supplied with Alberta shipments. See Drawing AP-A-863 in Appendix E.
2.3.4 PRESSURE/TEMPERATURE RELIEF & DRAIN
An ASME rated Pressure/Temperature Relief Valve is supplied with each unit. With the exception of Alberta installations (see above Note), the valve setpoint is 150 psig/210°F. Install the relief valve as shown in Figure 2.5. A suitable pipe compound should be used on the threaded connections. Any excess should be wiped off to avoid getting any into the valve body. The relief valve should be pipied to within 12 inches of the floor to prevent injury in the event of a discharge. The relief piping must be full size, 1-1/2”, without reduction. No valves, restrictions, or other blockages are allowed in the discharge line. In multiple unit installations the discharge lines must together. Each must be individually run to a suitable discharge location.
A 1” drain valve assembly is furnished with each unit. The assembly should be installed as shown in Figure 2.4b. The drain should be hard piped to a suitable drain.
VALVE INSTALLATION
not be manifolded
2-3
Page 14
INSTALLATION
TEMPERATURE SENSOR
EXHAUST
MANIFOLD
CONDENSATE
DRAIN
BURNER
HOSE CLAMP
1-3/4" O.D. x 8-1 /2 “ LG.
SILICONE HOSE
5/8" O.D. TUBE CONN.
CONDENSATE CUP PLACED ON FLOOR
2.3.5 SYSTEM RECIRCULATION
The system recirculating line ties into the unit at the recirculating tee fitting provided in the drain valve assembly (see Fig. 2.4b). Shut off valves and union connections are recommended for maintenance. Recirculation flow rates must be kept to 8 gpm or less. In a multiple unit installation, each unit must be tied into the system recirculation system.
4. Replace the rear cover and side panel on the unit.

Figure 2.5

Condensate Drain Assembly Location

Figure 2.4b

Pressure/Temperature Relief and Drain
Valve Installation Location
2.3.6 CONDENSATE PIPING
The KC Heater is designed to condense. Therefore, the installation site must include suitable provisions for condensate drainage or collection. A stainless steel condensate cup is separately packed within unit’s shipping container. To install the condensate cup, proceed as follows:
1. Remove the left side panel and only the left half of the rear cover to provide access to the exhaust manifold and burner (Figure 2.5).
2. Insert the 1-3/4 inch manifold drain hose into the condensate cup. Allow the cup to rest on the floor directly beneath the manifold drain hole (Figure 2.5).
3. Attach a length of 3/4 inch I.D.polypropylene tubing to the condensate cup drain tube and route it to a floor drain. . If a floor drain is not available, a condensate pump can be used to remove the condensate to drain. The condensate drain line must be removable for routine maintenance.

2.4 GAS SUPPLY PIPING

AERCO Gas Fired Equipment Gas Components and Supply Design Guide (GF-1030) should be consulted before any gas piping is designed or started.
WARNING !
DO NOT USE MATCHES, CANDLES, FLAMES OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS
.
CAUTION !
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be rinsed thoroughly with clean water after leak checks have been completed
.
NOTE:
All gas piping must be arranged so that it does not interfere with removal of any cover, inhibit service or maintenance, or prevent access between the unit and walls, or another unit
The location of the 1-1/4" inlet gas connection on the right side of the unit is shown in Figure
2.6.
.
2-4
Page 15
INSTALLATION
gas trains at 1,000,000 BTU/H for natural gas and propane units.
The maximum static inlet pressure to the unit must be no more than 14” W.C.. Minimum gas pressure is 8.5” W.C. for FM gas trains and 8.9” W.C. IRI gas trains when the unit is firing at maximum input. Gas pressure should not exceed 10.5” W.C. at any time when the unit is firing. Proper sizing of the gas supply regulator in delivering the correct gas flow and outlet pressure is mandatory. The gas supply pressure regulator must maintain the gas pressure at a minimum of 8.5” W.C. (FM) or 8.9” W.C. (IRI) when the unit is at maximum BTU input (1,000,000 BTU/HR). The supply gas regulator must be able to supply sufficient capacity

Figure 2.6

Gas Supply Regulator and Manual Shut -
Off Valve Location
All pipe should be de-burred and internally cleared of any scale or iron chips prior to installation. No flexible connectors or non­approved gas fittings should be installed. Piping should be supported from floor or walls only and must not be secured to the unit.
A suitable piping compound approved for use with gas should be used sparingly. Any excess must be wiped off to prevent clogging of components. To avoid damage to the unit when pressure testing gas piping, isolate the unit from the gas supply piping. At no time should there be more than 1 psig maximum to the unit. Bubble test all external piping thoroughly for leaks using a soap and water solution or suitable equivalent. The gas piping must meet all applicable codes.
2.4.1 GAS SUPPLY PRESSURE
REGULATOR
A mandatory external, in line, supply gas regulator (supplied by others) should be positioned as shown in Figure 2.6. Union connections should be placed in the proper locations to allow maintenance of the regulator if required.
NOTE:
An individual gas pressure regulator must be installed upstream of each unit. The regulator must regulate gas pressure to 8.5” W.C. for FM gas train and 8.9” W.C. for IRI
volume, (1000 cfh), to the unit and should have no more than 1" droop from minimum to full fire. The supply gas regulator must also be rated to handle the maximum incoming gas pressure.
When the gas supply pressure will not exceed 14” W.C. a non-lock up, or flow through style regulator, may be used. When supply gas pressure will exceed 14” W.C., a lock up style regulator must be used. The gas supply regulator must be propery vented to outdoors. Consult the local gas utility for exact requirements concerning venting of supply gas regulators.
CAUTION
A lockup style regulator must be used when gas supply pressure exceeds 14” W.C.
2.4.2 MANUAL GAS SHUTOFF VALVE
A 1-1/4” manual gas shutoff valve is furnished with each unit and should be positioned as shown in Figure 2.6. The valve must be installed upstream of the gas supply regulator in a readily accessible location.
2.4.3 IRI GAS TRAIN KIT
The IRI gas train is an optional gas train required in some areas by code or for insurance pur­poses. The IRI gas train comes pre-assembled and wired from the factory. See Appendix E, Drawing SD-A-606.
The IRI gas train may be ordered pre-assembled or as separate components. If either IRI gas train option is ordered, a complete instructional package, detailing field installation will be included. To obtain a copy of an IRI instructional package prior to the equipment shipping contact your local representative or AERCO.
2-5
Page 16
INSTALLATION
POWER BOX
BLOWER
SSOV ACTUATOR
FRAME
USE COPPER CONDUCTORS ONLY FOR FIELD WIRING
60 HZ
DISCONNECT POWER BEFORE SERVICING
DANGER: HIGH VOLTAGE
20 AMP
120 VAC,
NEUTRAL
GROUND
LINE
POWER BOX
AERCO INTERNATIONAL INC.
INPUT POWER
GAS SHUT-OFF VALVE
I/O BOX
BLOWER

2.5 ELECTRICAL SUPPLY

The AERCO Gas Fired Equipment Electrical Power Wiring Guide, (GF-1060), must be consulted in addition to the following material before wiring to the unit is started. AC power connection to the unit are made at the Power Box.This box is located on the front right side of the unit as shown in Figure 2.7.
All electrical conduit and hardware should be installed so that it does not interfere with the removal of any cover, inhibit service or maintenance, or prevent access between the unit and walls or another unit.
2.5.1 ELECTRICAL REQUIREMENTS
Electrical requirements for each unit are 120 VAC, 1 Phase, 60 Hz, 20 Amps from a dedicated electrical circuit. No other devices should be on the same electrical circuit as a KC1000 unit.

Figure 2.7

AC Power Box Location

NOTE:
covers. A flexible electrical connection may be utilized to allow the covers to be easily removed.

Figure 2.8

AC Power Wiring Diagram

2.6 FIELD CONTROL WIRING

Each unit is fully wired from the factory with an internal operating control system. No field control wiring is required for normal operation. However, the KC1000 control system does allow for some control and monitoring features. W iring for these features can be accomplished in the I/O Box behind the left side panel (Figures 2.9 and 2.10). The I/O Box is common to both KC1000 water heaters and boilers. While some of the inputs and outputs are common to both water heaters and boilers, some are not applicable to both. These are noted in the following paragraphs.
CAUTION!
DO NOT make any connections to the I/O Box terminals labeled “NOT USED”. Attempting to do so may cause equipment damage.
A means for disconnecting AC power from the unit (such as a service switch) must be installed near the unit for normal operation and maintenance. All electrical connections should be made in accordance with the National Electrical Code and/or with any applicable local codes.
The electrical wiring diagram is shown in Figure
2.8. Conduit should be run from the knockouts in
the side of the box in such a manner that it does not interfere with the removal of any sheet metal
2-6

Figure 2.9

Input/Output (I/O) Box Location
Page 17
INSTALLATION
2.6.1 OUTDOOR AIR SENSOR IN
Not applicable to Water Heaters.
2.6.2 AUX SENSOR IN
The AUX SENSOR IN terminals can be used to add an additional temperature sensor for monitoring purposes. This input is always enabled and is a view only input that can be seen in the operating menu. The sensor must be wired to the AUX SENSOR IN and SENSOR COMMON and must be similar to AERCO BALCO wire sensor P/N 12449. A resistance chart for this sensor can be found in Appendix C.
2.6.3 ANALOG IN
The ANALOG IN + and – terminals are used when an external signal is used to change the setpoint of the water heater when operating in the Remote Setpoint Mode.
Either a 4 to 20 mA / 1 to 5 VDC or a 0 to 20 mA/ 0 to 5 VDC signal may be used to vary the setpoint or air/fuel valve position. The factory default setting is for 4 to 20 mA / 1 to 5 VDC, however this may be changed to 0 to 20 mA / 0 to 5 VDC using the Configuration Menu described in Section 3. If voltage rather than current is selected as the drive signal, a DIP switch must be set on the CPU Board located inside the Control Box. Contact the AERCO factory for information on setting DIP switches.
All supplied signals must be floating (ungrounded) signals. Connections between the source and the Heater’s I/O Box must be made using twisted shielded pair wire of 18 –22 AWG,,such as Belden 9841(see Fig. 2.10). Polarity must be maintained and the shield must be connected only at the source end. It must be left floating (not connected) at the Heater’s I/O Box.
Whether using voltage or current for the drive signal, they are linearly mapped to a 40°F to 240°F setpoint or a 0% to 100% valve position. No scaling for these signals is provided
2.6.4 B.M.S. (PWM) IN
Not applicable to Water Heaters.
2.6.5 SHIELD
The SHIELD terminals are used to terminate any shields used on sensor wires connected to the unit. Shields must only be connected to these terminals.
2.6.6 mA OUT
These terminals provide a 4 to 20 mA output that can be used to monitor setpoint ( to 220°F), outlet temperature ( to 245°F), or valve position (0% to 100%). This function is enabled in the Configuration Menu (Section 3, Table 3.4).
2.6.7 RS-485 COMM
These terminals are used for RS-485 MODBUS serial communication between the unit and an external “Master”, such as an Energy Manage­ment System.
2.6.8 EXHAUST SWITCH IN
These terminals permit an external exhaust switch to be connected to the exhaust manifold of the boiler. The exhaust sensor should be a normally open type switch (such as AERCO P/N
123463) that closes (trips) at 500°F.
2.6.9 INTERLOCKS
The unit offers two interlock circuits for interfacing with Energy Management Systems and auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called the Remote Interlock and Delayed Interlock (Fig. 2.10). The wiring terminals for these interlocks are located inside the I/O Box on the left side of the unit. The I/O Box cover contains a wiring diagram which shows the terminal strip locations for these interlocks labeled REMOTE INTL’K IN and DELAYED INTL’K IN. Both interlocks, described below, are factory wired in the closed position.
NOTE:
Both the Delayed Interlock and Remote Interlock must be in the closed position to allow the unit to fire.
2.6.9.1 REMOTE INTERLOCK IN
The remote interlock circuit (REMOTE INTL’K IN) is provided to remotely start (enable) and stop (disable) the unit if desired. The circuit is 24 VAC and comes factory pre-wired closed (jumped).
2.6.9.2 DELAYED INTERLOCK
The delayed interlock circuit (DELAYED INTL’K IN) is typically used in conjunction with the auxiliary relay described in paragraph 2.6.11. This interlock circuit is located in the purge section of the start string. It can be connected to the proving device (end switch, flow switch etc.) of an auxiliary piece of equipment started by the unit’s auxiliary relay. The delayed interlock must be closed for the heater to fire. If the delayed interlock is connected to a proving device that
2-7
Page 18
INSTALLATION
mA OUT
RS-485 COMM.
+
-
+
-
ANALOG IN
SENSOR COMMON
OUTDOOR SENSOR IN
REMOTE INTL'K IN
B.M.S. (PWM) IN
SHIELD
+
-
+
-
AUX SENSOR IN
NOT USED
EXHAUST SWITCH IN
DELAYED INTL'K IN
FAULT RELAY 120 VAC, 5A, RES
AUX RELAY 120 VAC, 5A, RES
G
RELAY CONTACTS: 120 VAC, 30 VDC 5 AMPS RESISTIVE
DANGER
120 VAC USED
IN THIS BOX
NOT USED
NOT USED
NC COM NO
NC COM NO
NOT USED
requires time to close (make), a time delay (Aux Start On Dly) that holds the start sequence of the unit long enough for a proving switch to make (close) can be programmed. Should the proving switch not prove within the programmed time frame, the unit will shut down. The Aux Start On Dly can be programmed from 0 to 120 seconds. This option is locate in the Configuration Menu (Section 3).
2.6.10 FAULT RELAY
The fault relay is a single pole double throw (SPDT) relay having a normally open and normally closed set of relay contacts that are rated for 5 amps at 120 VAC and 5 amps at 30 VDC. The relay energizes when any fault
condition occurs and remains energized until the fault is cleared and the CLEAR button is depressed. The fault relay connections are shown in Figure 2.10.
2.6.11 AUXILIARY RELAY CONTACTS
Each unit is equipped with a single pole double throw (SPDT) relay that is energized when there is a demand for heat and de-energized after the demand for heat is satisfied. The relay is provided for the control of auxiliary equipment, such as pumps and louvers, or can be used as a unit status indictor (firing or not firing). Its contacts are rated for 120 VAC @ 5 amps. Refer to Figure 2.10 to locate the AUX RELAY terminals for wiring connections.

2.7 FLUE GAS VENT INSTALLATION

AERCO Gas Fired Venting and Combustion Air Guide, GF-1050, must be consulted before any flue or combustion air venting is designed or installed. Suitable, U/L approved, positive pressure, watertight vent materials MUST be used for safety and UL certification. Because the unit is capable of discharging low temperature exhaust gases, the flue must be pitched back towards the unit a minimum of 1/4" per foot to avoid any condensate pooling and to allow for proper drainage.
2-8

Figure 2.10 I/O Box Wiring

While there is a positive flue pressure during operation, the combined pressure drop of vent and combustion air systems must not exceed 140 equivalent feet of 0.81” W.C. Fittings as well as pipe lengths must be calculated as part of the equivalent length. For a natural draft installation the draft must not exceed - 0.25” W.C. These factors must be planned into the vent installation. If the maximum allowable equivalent lengths of piping are exceeded, the unit will not operate properly or reliably.
Page 19
INSTALLATION
For Massachusetts installations, the Heatfab Division of the Selkirk Corporation provides vent systems which conform to all applicable requirements for installations within the Commonwealth of Massachusetts. Contact information for this supplier are as follows:
Selkirk Corporation Heatfab Division 130 Industrial Blvd. Turners Falls, MA 01376 Phone: 1-800-772-0739
.heat-fab.

2.8 COMBUSTION AIR

The AERCO Gas-Fired Heater Venting and Combustion Air Guide, GF-1050 MUST be consulted before any flue or inlet air venting is designed or installed. Air supply is a direct requirement of ANSI 223.1, NFPA-54, and local codes. These codes should be consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons or other chemicals that can become hazardous when used in gas­fired equipment. Common sources of these compounds are swimming pools, degreasing compounds, plastic processing, and refrigerants. Whenever the environment contains these types of chemicals, combustion air MUST be supplied from a clean area outdoors for the protection and longevity of the equipment and warranty validation. The more common methods of combustion air supply are outlined below. For combustion air supply from ducting, consult AERCO GF-1050, Gas Fired Venting and Combustion Air Guide.

2.8.1 COMBUSTION AIR FROM OUTSIDE THE BUILDING

Air supplied from outside the building must be provided through two permanent openings. For each unit these two openings must have a free area of not less than one square inch for each 4000 BTUs input of the equipment or 250 square inches of free area. The free area must take into account restrictions such as louvers and bird screens.

2.8.2 COMBUSTION AIR FROM INSIDE THE BUILDING

When combustion air is provided from within the building, it must be supplied through two perma­nent openings in an interior wall. Each opening must have a free area of not less than one square inch per 1000 BTUH of total input or 1000 square inches of free area. The free area must take into account any restrictions such as louvers.

2.8.3 SEALED COMBUSTION

The unit is UL approved for a 100% sealed combustion application when installed properly. When a sealed combustion air application is installed, the sealed combustion air piping must be deducted from the maximum allowable discharge piping amounts. Each unit must have a minimum 6" diameter connection made to the optional Inlet Air Adapter # GM-18917 available from AERCO. This Adapter bolts directly on to the air inlet of the unit blower. See installation instructions with Adapter. All inlet air ducts must be sealed air tight.
2-9
Loading...