AERCO GF-105 User Manual

Instruction No.
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
GF-105
& Maintenance Instructions
KC Series Gas Fired Water Heating System
Natural Gas or Propane Fired,
Condensing and Forced Draft Hot Water Heater
1,000,000 BTU/HR Input
Applicable to Serial Numbers G-01-026 and above
Patent No. 4,852,524
Printed in U.S.A. REVISED 12/30/04

Telephone Support

Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday) (800) 526-0288
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
© AERCO International, Inc., 2004
The information contained in this operation and maintenance manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
CONTENTS
GF-105 THE AERCO KC1000 GAS FIRED DOMESTIC WATER HEATER
Operating & Maintenance Instructions
FOREWORD
Section 1 SAFETY PRECAUTIONS--------------------------------1
Section 2 INSTALLATION PROCEDURES-----------------------2
2.1 Receiving the Unit
2.2 Unpacking
2.3 Installation
2.4 Gas Supply Piping
2.5 Electrical Supply
Section 3 CONTROL PANEL COMPONENTS
3.1 The Control Panel
3.2 The Temperature Contro ller
3.3 The Primary Menu
3.4 The Secondary Menu
3.5 The Annunciator Circuit
3.6 The Combustion Safeguard Controller
Section 4 INITIAL START-UP--------------------------------------17
4.1 Initial Start-Up req uir ements
4.2 Tools and Instrumentation f or Combustion Calibration
4.3 Combustion Calibration
4.4 Propane Combustion Calibration
2.6 Field Control Wiring
2.7 Flue Gas Vent Installation
2.8 Combustion Air
2.9 Unit Initial Fill
and OPERATING PROCEDURES------------9
3.7 Water Level T est and Reset Switches
3.8 On\Off Switch
3.9 Starting Sequence
3.10 After Flame
3.11 Flame Test Jacks
3.12 Start\Stop Levels
3.13 Auto Restarts
4.5 Unit Reassembly
4.6 Temperature Control Calibration
4.7 Over Temperature Limit Switch Adjustments
Section 5 SAFETY DEVICE TESTING
5.1 Testing of Safety Devices
5.2 Gas Pressure Fault Test
5.3 Low Water Level Fault Test
5.4 Water Temperature Fault Test
PROCEDURES-----------------------------------25
5.5 Flame Fault Test
5.6 Air Pressure Fault Test
5.7 Purge Interlocks Fault Test
5.8 Safety Pressure Relief Valve Test
i
CONTENTS
Section 6 MAINTENANCE REQUIREMENTS-------------------29
6.1 Maintenance Schedule
6.2 Spark Ignitor
6.3 Flame Detector
6.4 Combustion Calibration
6.5 Safety Device Testing
Section 7 TROUBLESHOOTING-----------------------------------39
7.1 Gas Pressure Fault
7.2 Exhaust Temperature Fault
7.3 Water Level Fault
7.4 Water Temperature Fault
A. Temperature Controller Menus B. Temperature Controller Quick
Programming Guide C. Shell Sensor Resistance Chart D. Mode of Operation Default
Settings
6.6 BTU Transmitter Pump Lubrication
6.7 BTU Transmitter Assembly
6.8 Manifold and Exhaust Tubes
6.9 Heat Exchanger Inspection
7.5 Flame Fault
7.6 Air Pressure Fault
7.7 System Fault
APPENDICES
E. Dimensional & Parts Drawings F. Piping Drawings G. Wiring Schem atics H. Control Panel Isometric Drawing
WARRA NTIES
2/27/99
ii
FOREWORD
Foreword
The AERCO KC Hot Water Heating System is a true industry advance that meets the needs of today’s energy and environmental concerns. Designed for use in any potable water heat ing system, it provides constant temperature water regardless of flow rate. It’s small space requirements and venting capabilities allows installations without norm al restrictions yet with maximum flexibility. The KC Heater’s load tracking controls modulate over a 14:1 turndown ratio to match the system demand and yield thermal efficiencies in excess of 93%.
Because of its compact design with direct or chimney venting, the KC Water Heating System is applicable to any installation with excellent results. Eff iciency, reliability and longevity make the KC Water Heat ing System a true step forward in Water Heating System design.
After prolonged shutdown, it is recom mended that the startup procedures in Section 4 and t est procedures in Section 5 of this manual be performed, to verify system operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO Heater or close the Manual Gas Valve located before the AERCO heater. T he I nstaller is to identify the emergency shut-off device. FOR SERVI CE OR PARTS, contact your local Sales Representative listed below or AERCO INTERNATIONAL.
NAME: ORGANIZATION: ADDRESS: TELEPHONE: INSTALLATION DATE: _____________________________________________
iii
SECTION 1 -- SAFETY PRECAUTIONS
Installing or operating per sonnel MUST, at all times, observe all safety regulations. The following warnings are general and must be given the same attention as specific precautions included in these instructions. In addition to the requirements included in this instruct ion manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANZI Z223.1 (National Fuel Gas Code, Publication No. NFPA-54) for gas-fired heaters and ANSI/NFPASB for LP gas-fired heaters. Where applicable, t he equipment shall be installed in accordance with CGA B149.
SAFETY PRECAUTIONS
WARNING!
DO NOT USE MATCHES, CANDLES,
FLAMES, OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS LEAKS.
WARNING!
THE EXHAUST VENT PIPE OPERATES
UNDER POSITIVE PRESSURE AND
MUST BE COMPLETELY SEALED TO
PREVENT LEAKAGE OF COMBUSTION
PRODUCTS INTO LIVING SPACES
.
WARNINGS!
MUST BE OBSERVED TO PREVENT
SERIOUS INJURY TO PERSONNEL
.
WARNING!
BEFORE PERFORMING ANY
MAINTENANCE ON THE UNIT,
SHUT OFF THE GAS SUPPLY AND THE
ELECTRICAL POWER SUPPLY TO THE
UNIT.
WARNING!
FLUIDS UNDER PRESSURE MAY
CAUSE INJURY TO PERSONNEL OR
DAMAGE TO EQUIPMENT WHEN
RELEASED.. BE SURE TO SHUT OFF
ALL INCOMING AND OUTGOING
WATER SHUTOFF VALVES AND
CAREFULLY DECREASE ALL TRAPPED
PRESSURES TO ZERO BEFORE
PERFORMING ANY MAINTENANCE.
CAUTIONS!
Must be observed to prevent equipment
damage or loss of operating
effectiveness.
CAUTION!
Many soaps used for gas pipe leak testing
are corrosive to metals. The piping m ust
be rinsed thoroughly with clean water after
leak checks have been completed.
CAUTION!
Do not use this unit if any part has been
under water. Call a qualified service
technician to inspect and replace any
part that has been under water.
NOTES:
Must be observed for effective operating
procedures & conditions
1
INSTALLATION PROCEDURES
SECTION 2 - INSTALLATION PROCEDURES
2.1 RECEIVING THE UNIT
Each KC unit is shipped as a single crated unit. The shipping weight is approximately 1500 lb. and must be moved with the proper rigging equipment for safety and to avoid damages. The unit should be completely inspected at the time of receipt from the carrier before the bill of lading is signed. Each unit has Tip-N-Tell indicator on the outside of the crate. This indicates if the unit has been turned on its side. If the Tip-N-Tell indicator is tripped, do not sign for the shipment. Note the information on the carrier’s paperwork and request a freight claim and inspection by a claims adjuster before proceeding. Any other visual damage to the packaging materials should also be made clear to the delivering carrier.
2.2 UNPACKING
Carefully unpack the unit by removing the packaging material. Take care not to damage the unit jacket when cutting away packaging materials. A close inspection of the unit should be made to determine if there has been any damage during shipment that was not indicated by the Tip-N-Tell.
The freight carrier should be notified immediately if any damage is detected. The following accessories come standard with each unit and are packed separately within the unit’s packing container
Spare Spark Ignitor
Spare Flame Detector
Manual 1-1/4" Gas Shutoff Valve
Drain Valve Assembly
ASME Pressure/Temperature
Relief Valve
Ignitor Removal Tool (O ne per Site)
Regulator Adjustment Tool (One
per Site)
2 Lifting Lugs
Stainless Steel Condensate Cup
Flue Clamps (2 Pieces)
Optional accessories are also separately packed within the unit’s packing container. Standard and optional accessories shipped with the unit should be identified and put in a safe place until installation/use.

Figure 2.1

Heater Clearances
2
INSTALLATION PROCEDURES
2.3 INSTALLATION
The unit must be installed with the prescribed clearances for service as shown in Fig 2.1 These are the minimum clearance dimensions required by AERCO. Local building codes may require more clearance and take precedence.
WARNING !
KEEP UNIT AREA CLEAR AND FREE
FROM COMBUSTIBLE MATERIALS AND
FLAMMABLE VAPORS AND LIQUIDS.
2.3.1 SETTING THE UNIT
Locate the lifting lugs, shipped with the unit, and attach them to the 5/8” x 11 studs at the top of the unit. Remove the unit from the wooden skid and place in position using a block and tackle or hoist attached to the lifting lugs. (see Fig. 2.2). USE THE LIFTING LUGS TO MOVE THE UNIT.
2.3.2 WATER INLET AND O UTLET PIPING
The locations of the 2" NPT cold water inlet and hot water outlet piping connections are shown in Figure 2.4. Flow rates through the unit are limited to 30 gpm continuous and 40 gpm intermittent.
Shut-off valves and union conections must be installed in the inlet and outlet lines for maintenance. The use of dielectric unions is recommended. Install the piping and accessories as per the following drawings, located in Appendix F of this manual.
SD-B-424 for single units
SD-B-425 for multiple units
SD-B-432 for single units with a stratified
tank
SD-B-434 for multiple units with a stratified storage tank
NOTE:
All piping must be arranged so that it does
not interfere with removal of any cover,
inhibit service or maintenance, or prevent
access between the unit and walls, or
another unit.

Figure 2.2

Lifting Lug Location

The KC-1000 is U/L approved for installation on combustible flooring. A 4” to 6" high housekeeping concrete pad is recommended and allows for sufficient drainage of the condensate.
The unit must be secured using only the holes provided in the frame base. Do not use piping to secure the unit in place. See drawing AP-A-576 in Appendix E for the base frame dimensions. In multiple unit installations it is important to plan the position of each unit. Sufficient space for piping connections and maintenance requirements must be given. All piping must include ample provision for expansion.

Figure 2.3

Inlet and Outlet Location

2.3.3 TEST HOSE BIB
A Test Hose Bib connection, upstream of the shut off valve on the hot water outlet, is required
3
INSTALLATION PROCEDURES
for startup and testing. It should be a minimum of 3/4". It cannot be omitted (See Fig. 2.4a)
maintenance. Recirculation flow rates must be kept to 8 gpm or less. In a multiple unit installation, each unit must be tied into the system recirculation system.

Figure 2.4a

Hose Bibb Location

2.3.4 PRESSURE/TEMPERATURE RELIEF AND DRAIN
VALVE
INSTALLATION
An ASME rated Pressure/Temperature Relief Valve is supplied with each unit. The valve setpoint is 150 psig/210 valve as shown in Fig. 2.4. A suitable pipe compound should be used on the threaded connections. Any excess should be wiped off to avoid getting any into the valve body. The relief valve should be pipied to within 12 inches of the floor to prevent injury in the event of a discharge. The relief piping must be full size, 1­1/2”, without reduction. No valves, restrictions, or other blockages are allowed in the discharge line. In multiple unit installations the discharge lines must not be manifolded together. Each must be individually run to a suitable discharge location.
A 1” drain valve assembly is furnished with each unit. The assembly should be installed as shown in Figure 2.4. The drain should be hard piped to a suitable drain.
0
F. Install the relief

Figure 2.4b

Pressure/Temperature Relief and Drain
Valve Installation Location
2.3.6 CONDENSATE PIPING
The KC Heater is designed to condense and the installation must have provisions for suitable drainage. A 1 inch ID silicone hose, supplied with the unit, directs condensate from the exhaust manifold to a stainless steel condensate cup. The condensate cup is shipped loose and should be installed inside the unit directly under the manifold’s condensate drainage hole. The condensate drain fitting is attached to the cup and should be located at the rear of the unit as shown in Figure 2.5. A 5/8-inch ID flexible polypropylene tubing (or suitable equivalent) should be used to carry the condensate by gravity to a nearby floor drain. If a floor drain is not available, a condensate pump can be used to remove the condensate to a convenient drain. The maximum condensate flow rate is 5 GPH. The condensate cup and line must be removable for routine maintenance. Do not hard pipe.
2.3.5 SYSTEM RECIRCULATION
The system recirculating line ties into the unit at the recirculating tee fitting provided in the drain valve assembly (see Fig. 2.4b). Shut off valves and union connections are recommended for
4

Figure 2.5

Condensate Drain Assembly Location

2.4 GAS SUPPLY PIPING
AERCO Gas Fired Equipment Gas Components and Supply Design Guide (GF-1030) should be consulted before any gas piping is designed or started.
INSTALLATION PROCEDURES
A suitable piping compound approved for use with gas should be used sparingly. Any excess must be wiped off to prevent clogging of components.
To avoid damage to the unit when pressure testing gas piping, isolate the unit from the gas supply piping. At no time should there be more than 1 psig maximum to the unit. Bubble test all external piping thoroughly for leaks using a soap and water solution or suitable equivalent. The gas piping must meet all applicable codes.
WARNING !
DO NOT USE MATCHES, CANDLES,
FLAMES OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS LEAKS
.
CAUTION !
Many soaps used for gas pipe leak testing
are corrosive to metals. The piping m ust be
rinsed thoroughly with clean water after
leak checks have been completed.
NOTE:
All gas piping must be arranged so that it
does not interfere with removal of any
cover, inhibit service or maintenance, or
prevent access between the unit and walls,
or another unit
The location of the 1-1/4" inlet gas connection on the right side of the unit is shown in Figure
2.6. All pipe should be de-burred and internally
cleared of any scale or iron chips before installation. No flexible connectors or non­approved gas fittings should be installed. Piping should be supported from floor or walls only and must not be secured to the unit.
.

Figure 2.6

Gas Supply Regulator and Manual Shut -
Off Valve Location
2.4.1 GAS SUPPLY PRESSURE REGULATOR
A mandatory external, in line, supply gas regulator (supplied by others) should be positioned as shown in Figure 2.6. Union connections should be placed in the proper locations to allow maintenance of the regulator if required.
NOTE:
An individual gas pressure regulator must
be installed upstream of each unit. The
regulator must regulate gas pressure to
8.5” W . C. for FM gas train and 8.9” W.C. for IRI gas trains at 1,000,000 BTU/H for
natural gas and propane units.
The maximum static inlet pressure to the unit must be no more than 14” water column. Minimum gas pressure is 8.5” W.C. for FM gas trains and 8.9” W.C. IRI gas trains when the unit is firing at maximum input. Gas pressure should
5
INSTALLATION PROCEDURES
not exceed 10.5” W.C. at any time when the unit is firing. Proper sizing of the gas supply regulator in delivering the correct gas flow and outlet pressure is mandatory. The gas supply pressure regulator must maintain the gas pressure at a minimum of 8.5” W.C. (FM) or 8.9” W.C. (IRI) when the unit is at maximum BTU input (1,000,000 BTU/HR). The supply gas regulator must be able to supply sufficient capacity volume, (1000 cfh), to the unit and should have no more than 1" droop from minimum to full fire. The supply gas regulator must also be rated to handle the maximum incoming gas pressure. When the gas supply pressure will not exceed 14” W.C. a non-lock up, or flow through style regulator, may be used. When supply gas pressure will exceed 14” W.C., a lock up style regulator must be used. The gas supply regulator must be propery vented to outdoors. Consult the local gas utility for exact requirements concerning venting of supply gas regulators.
CAUTION!
A lockup style regulator must be used when
gas supply pressure exceeds 14” W. C.
ELECTRICAL WIRING BOX
FRAME
SSOV ACTUATOR
BLOWER

Figure 2.7

AC Wiring Box Location

2.4.2 MANUAL GAS SHUTOFF VALVE
A 1-1/4” manual gas shutoff valve is furnished with each unit and should be positioned as shown in Figure 2.6. The valve must be installed upstream of the gas supply regulator in a readily accessible location.
2.4.3 IRI GAS TRAIN KIT
The IRI gas train is an optional gas train required in some areas by code or for insurance purposes. The IRI gas train may be ordered pre­assembled or as separate components. If either IRI gas train option is ordered a complete instructional package, detailing field installation will be included. To obtain a copy of an IRI instructional package prior to the equipment shipping contact your local representative or AERCO.
2.5 ELECTRIC SUPPLY
AERCO Gas Fired Equipment Electrical Power Wiring Guide (GF-1060) must be consulted in addition to the following material before wiring to the unit is started. The location of the electrical wiring box is on the front right side of the unit as shown in Figure 2.7.
NOTE:
All electrical conduit and hardware should
be installed so that it does interfere with the
removal of any cover, inhibit service or
maintenance, or prevent access between
the unit and walls or another unit.
2.5.1 ELECTRICAL REQUIREMENTS
Electrical requirements for each unit are 120 VAC, 1 Phase, 60 Hz, 20 Amps from a dedicated electrical circuit. No other devices should be on the same electrical circuit as a KC unit. A disconnecting means such as a service switch must be installed near the unit for normal operation and maintenance. All electrical connections should be made in accordance with the National Electrical Code and/or with any applicable local codes.
The electrical wiring diagram is shown in Figure
2.8. Conduit should be run from the knockouts
provided in the side of the electrical box in such a manner that it does not interfere with the removal of any sheet metal covers. A flexible electrical connection may be utilized to allow the covers to be removed easily.
6

Figure 2.8

Electrical W ir ing Diagram

2.6 FIELD CONTROL WIRING
Each unit is fully wired from the factory with an internal operating control system. No field control wiring is required for normal operation. However a fault relay, for remote fault indication, and enable/disable interlock circuits are provided. Wiring for these circuits can be accomplished in the Field Control Wiring Box behind the left side panel (see Fig. 2.9).
INSTALLATION PROCEDURES
This interlock must be closed,(jumped), to allow the unit to fire. When the interlock is open, the control panel Annunciator will display 'INTERLOCK DISABLED' and the unit will not fire. The unit comes factory wired with the interlock closed.
2.6.2 THE FAULT RELAY
The fault relay is a single pole single throw relay, that is energized upon any fault condition. The relay will remain energized until the fault is cleared and the CLEAR button is pushed The normally open field connections are shown in Figure 2.10. The relay contacts are rated for 5 amps at 250 VDC and 5 amps at 30 VDC.
AERCO INTERNATIONAL INC.
BLOWER
FIELD WIRING
816
OUTDOOR
START
INDICATION
FAULT
-
BMS
+
SHIELD
AIR SENSOR
7
15
6
14
4-20 mA
5
13
+
4
12
3
11
2
10
EXH. TEMP. SWITCH
1
9
FIELD
CONTROL
WIRING BOX
GAS SHUT-OFF VALVE

Figure 2.9

Field Control W ir ing Box Location

2.6.1 ENABLE/DISABLE INTERLOCK
Each unit has an enable/disable interlock circuit located in the field wiring box (see Figure 2.10).

Figure 2.10

Field Control Box Wir ing

2.7 FLUE GAS VENT INSTALLATION
AERCO Gas Fired Venting and Combustion Air Guide, GF-1050, must be consulted before any flue or combustion air venting is designed or installed. Suitable, U/L approved, positive pressure, watertight vent materials MUST be used for safety and UL certification. Because the unit is capable of discharging low temperature exhaust gases, the flue must be pitched back towards the unit a minimum of 1/4" per foot to avoid any condensate pooling and to allow for proper drainage.
While there is a positive flue pressure during operation, the combined pressure drop of vent and combustion air systems must not exceed 140 equivalent feet of 0.81” W.C. Fittings as well as pipe lengths must be calculated as part
7
INSTALLATION PROCEDURES
of the equivalent length. For a natural draft installation the draft must not exceed - 0.25” W.C. These factors must be planned into the vent installation. If the maximum allowable equivalent lengths of piping are exceeded, the unit will not operate properly or reliably.
2.8 COMBUSTION AIR
The AERCO Gas-Fired Heater Venting and Combustion Air Guide, GF-1050 MUST be consulted before any flue or inlet air venting is designed or installed. Air supply is a direct requirement of ANSI 223.1, NFPA-54, and local codes. These codes should be consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons or other chemicals that can become hazardous when used in gas­fired equipment. Common sources of these compounds are swimming pools, degreasing compounds, plastic processing, and refrigerants. Whenever the environment contains these types of chemicals, combustion air MUST be supplied from a clean area outdoors for the protection and longevity of the equipment and warranty validation.
The more common methods of combustion air supply are outlined below. For combustion air supply from ducting, consult the AERCO GF­1050, Gas Fired Venting and Combustion Air Guide.
2.8.1 COMBUSTION AIR FROM OUTSIDE THE BUILDING
Air supplied from outside the building must be provided through two permanent openings. For each unit these two openings must have a free area of not less than one square inch for each 4000 BTUs input of the equipment or 250 square inches of free area. The free area must take into account restrictions such as louvers and bird screens.
be deducted from the maximum allowable discharge piping amounts. Each unit must have a minimum 6" diameter connection made to the optional Inlet Air Adapter # GM-18917 available from AERCO. This Adapter bolts directly on to the air inlet of the unit blower. See installation instructions with Adapter. All inlet air ducts must be sealed air tight.
2.9 UNIT INITIAL FILL
Before filling the shell for the first time, blow out all the connecting water and gas piping and check thoroughly for leaks. Rinse all soap suds from the gas piping with clean water. Do not allow water to get on the Control Panel or electrical connections. Check that all installation procedures have been completed.
The following steps should be followed to fill the unit:
1. Close the unit’s drain valve.
2. Open the shut-off valves at the water inlet
and outlet.
3. Open the temperature/pressure relief valve
to allow air to escape from the shell. The shell is full when water flows out of relief valve discharge piping.
4. Close the temperature/pressure relief valve
and open fixtures in building to free the system of air.
2.8.2 COMBUSTION AIR FROM INSIDE THE BUILDING
When combustion air is provided from within the building, it must be supplied through two permanent openings in an interior wall. Each opening must have a free area of not less than one square inch per 1000 BTUH of total input or 1000 square inches of free area. The free area must take into account any restrictions such as louvers.
2.8.3 SEALED COMBUSTION
The unit is UL approved for a 100% sealed combustion application when installed properly. When a sealed combustion air application is installed, the sealed combustion air piping must
8
CONTROL PANEL OPERATING PROCEDURES
SECTION 3- CONTROL PANEL OPERATING PROCEDURES
The following is a guide to the operation of the unit’s control panel. Initial startup of this unit must be performed by factory trained startup personnel. Operation prior to initial startup by factory trained personnel will void the warranty.
CAUTION:
All initial installation procedures must be
satisfied before attem pt ing to start the unit
WARNING:
DO NOT ATTEMPT TO DRY FIRE THE KC
1000. STARTING THE UNIT WITHO UT A FULL WATER LEVEL CAN SERIOUSLY
DAMAGE THE UNIT AND MAY RESULT IN
PERSONNEL INJURY OR PROPERTY
DAMAGE. THIS SITUATION WILL VOID
ANY WARRANTY.
3.1 THE CONTROL PANEL
The KC 1000 Control Panel has been designed to provide the operator with all the necessary information required for operation and troubleshooting the unit. There are six separate accessible controls or displays, available to the operator (see Figure 3.1). These are:
1. The Temperature Controller
2. The Annunciator & Function Switches
3. The Combustion Safeguard Controller
4. Water Level Test and Reset Switches
5. On/Off Switch
6. Fault Indicator Light The following sections will describe the above
components in more detail.
WARNING
CONTROL BOX INTERNALS MUST NOT
BE SERVICED OR ACCESSED BY OTHER
THAN FACTORY CERTIFIED SERVICE
TECHNICIANS. ALL CONTROL BOX
INTERNALS HAVE THE CAPABILITY OF
HOLDING AN ELECTRICAL VOLTAGE OF
120 VOLTS AC.
3.2 THE TEMPERATURE CONTROLLER
The temperature controller is a PID programmable controller that utilizes feed forward and feedback information to accurately maintain a desired set point. It is the primary source for programming and viewing operating parameter settings. It also plays a part in the start sequence and includes other features such as:
2- eight segment LED displays
5 indicator status lights
3 menu levels
RS-485 communications capability,
.

FIGURE 3.1

Front Panel Controls Location

3.2.1 LED DISPLAYS
The upper and lower displays each consist of four 8 segment LED’s’ (see figure 3.2). When an operating parameter is chosen to be changed or looked at, the lower led display indicates the parameter being looked at in the form of a code. The upper display indicates the parameter’s value. For a complete listing of the operating parameters see Appendix A of this manual.
3.2.2 INDICATOR STATUS LIGHTS
The first LED indicator light, “MAN”) indicates whether the controller is in auto or manual mode, (see Fig. 3.2). When lit the controller is in manual mode and the operator is responsible for operation of the unit. When the LED is not lit the controller is in auto mode. In auto mode the controller is operating the unit from signals generated by sensors located on the unit.
The second LED, “REM”, designates whether the controller is being controlled locally or remotely. (see Fig. 3.1). When lit the controller is in remote mode and can accept commands from an external source via the RS-485 interface. When this LED is not lit the controller is in local mode and will respond to whatever the current internal settings are. All external commands are ignored.
9
CONTROL PANEL OPERATING PROCEDURES
The third LED, “ON”, indicates the status of the start relay, (Fig. 3.2). The start relay is internal to the controller and is part of the start string for the unit. When this LED is lit there is a demand for heat and the start relay is closed.
o
The last two LED’s, whether the temperature displayed is °F or °C.
F” and “oC”, indicate
NOTE:
When the t em per ature controller is
displaying in oC only the temperature being
displayed is affected. All other set t ings
remain in oF.

Figure 3.2

Temperature Controller Operating Status
Lights
menu parameter are listed within this section. For more data concerning the minimum and maximum range, and factory defaults of menu parameters, see the Appendix D of this manual.
3.3 PRIMARY MENU
The primary menu is the default menu. When in another menu level and there is no activity for five minutes the temperature controller will default back to the primary menu. The Primary menu allows the operator access to the controller parameters listed below.
Code Meaning
tout Actual unit outlet water temperature.
pct Current firing rate of the unit in
percent.
Setp The desired set-point of outlet water
temperature.
Auto Automatic controlling mode ON or
OFF.
3.3.1 OUTLET TEMPERATURE (TOUT)
Outlet temperature is the actual outlet water temperature of the unit. To access outlet temperature, press the INDEX button until (tout) is displayed in the lower LED. The variable under this feature may not be manually changed. Fig 3.3, below, shows an outlet temperature of 120º F
3.2.3 MENU LEVELS
The temperature controller has two menu levels that are operator accessible for programming the unit functions and parameters. These are the Primary and Secondary menus.
To change from the primary menu to the secondary menu simultaneously depress the
arrow key and ENTER button. To change from the secondary to the primary menu simultaneously press the arrow key and the INDEX button.
To scroll through a menu, depress the INDEX button. To change a parameter scroll through the menu until the desired parameter is indicated on the controller’s lower LED display. Then use the
!
and " arrow keys to change the parameters value. Once the desired parameters value has been changed the ENTER key must be pushed for the change to be recognized by the controller. Leaving the desired parameter without entering the new value will result in that parameter value defaulting back to the previous value. Detailed descriptions and instructions for accessing each
!

Figure 3.3

Outlet Temperature Display

3.3.2 PERCENTAGE OF FIRING RATE (Pct)
Percentage of firing rate is a number, in percent, that is related to the input BTU’s of the unit. For instance a 50% signal equals approximately 500,000 BTU gas input while a 75 % signal equals approximately 750,000 BTU gas input.
CAUTION:
Do not leave the unit unattended while in the
manual mode of operation.
10
CONTROL PANEL OPERATING PROCEDURES
To access the percent of firing rate press the INDEX button while in the primary menu until
(Pct) is displayed in the lower LED. Use the arrow key to increase or decrease the percentage of firing rate. Press the ENTER button to accept the desired change. Figure 3.4 shows the temperature controller displaying a 100% firing rate.
!, "

Figure 3.4

Percent of Firing Rate Display

WARNING:
WHEN SWITCHING FROM AUTO TO
MANUAL MODE, THE FIRING RATE DOES NOT CHANGE. THE UNIT WILL CONTINUE TO OPERATE AT THE SAME FIRING RATE
PERCENTAGE AS WHEN THE UNIT WAS
IN AUTO MODE.
3.3.3 SETPOINT (SETP)
Setpoint is the desired outlet water temperature that is to be maintained by the unit when in automatic mode. Fig 3.5 shows the controller with a setpoint of 120º F.
NOTE:
Changing the setpoint will only be
recognized when the unit is in the automatic
mode.
3.3.4 AUTOMATIC\MANUAL (AUTO)
When set to automatic mode the controller is receiving and processing inputs from temperature sensor(s) located externally or on the unit. The controller uses these inputs to automatically decrease or increase the firing rate to match the load.
In manual mode the controller no longer automatically controls the firing rate of the unit. It is up to the operator to control the outlet temperature and firing rate. Manual mode is commonly used for service and troubleshooting the unit. All safety limits remain functional whether the controller is in automatic or manual mode.
To place the controller in automatic mode press the INDEX button until (Auto) is displayed in the lower LED.
!
Now press the displayed in the upper LED, (see Fig. 3.6). Press the enter button to accept the change. The MAN LED should not be lit.
To place the KC 1000 in manual mode, press the
! "
arrow keys until OFF is displayed in the upper LED (See Fig. 3.7). Press the enter button to accept the change. The MAN LED should now be lit.
" arrow keys until ON is
To access the unit’s setpoint press the INDEX button until (Setp) is displayed in the lower LED. To increase or decrease the unit’s setpoint press
! "
the accept the change.
arrow keys. Press the ENTER button to

Figure 3.5

Setpoint Display

Figure 3.6

Auto/Manual Display with Auto On
11
CONTROL PANEL OPERATING PROCEDURES

Figure 3.7

Auto/Manual Display with Manual ON

3.4 SECONDARY MENU
The secondary menu is primarily related to temperature control. It is necessary to access this menu when temperature calibrating the unit.
To access the secondary menu, press the arrow key and ENTER simultaneously. To scroll through the menu press the INDEX button. The secondary menu allows access to the following temperature control features:
!
For a complete explanation of the secondary menu parameters see the Appendix A of this manual.
3.5 THE ANNUNCIATOR CIRCUIT
The annunciator consists of the annunciator circuit board, the front panel LCD display, and 4 function switches (see Fig. 3.8). The annunciator circuit board is the interface between the LCD display and the combustion safeguard system. It monitors the unit during every phase of operation and prompts the LCD display with start sequence and fault messages. The function switches are used to reset the annunciator and gain access to the annunciator’s three function displays.
Func
tout
FFt Pct
SetP
SEnS
OFSt
LLt HLt
Pb1 Proportional Band
Int Integral Rate
Drt Derivative Time
Fdb Feedback on or off
Addr
LOre
Unit’s mode of
operation Outlet water temperature
Water temperature
at the BTU
transmitter sensor
Firing rate of the unit
in percent
The desired set point
of outlet water temp
High flow temperature
adjustment
Low flow
temperature
adjustment
Low temperature
alarm
High temperature
alarm
Controller address
for external
communication
Local/ remote status
of the control

Figure 3.8

Annunciator Function Switches and LCD
Display
The annunciator circuit board and LCD display are not an integral part of the start sequence or combustion safeguard system. If either should fail the unit will still operate with no adverse effects.
The annunciator start sequence messages, fault messages, function switches and function displays are explained below.
3.5.1 ANNUNCIATOR FUNCTION DISPLAYS AND SWITCHES
The annunciator has three function displays that are available to the operator. These are the MAIN, the CYCLES, and the SET DATE displays. These displays are accessed using the four membrane switches located directly under the
12
CONTROL PANEL OPERATING PROCEDURES
LCD display on the front of the control panel.
!, "
They are labeled CLEAR, The MAIN display is used during normal operation
of the unit. In the MAIN display, start sequence and fault messages can be viewed. To return to the MAIN display from any other display,
simultaneously press CLEAR and the key. To reset the MAIN display after a fault has occurred press the CLEAR button.
The CYCLES display indicates the date and time, and the number of cycles the unit has started. When in the CYCLES display only the number of cycles can be reset. To reset the number of cycles
to zero, simultaneously press the keys and hold them for approximately four seconds.
In the SET DATE display, both the time and date are displayed and can be changed. To access the SET DATE display, press the CLEAR button while in the CYCLES display. Continue pressing the CLEAR button to move
through the SET DATE display fields. Use the
"
arrow keys to set the date and time.
The following table shows the messages displayed after accessing the CYCLES and SET DATE DISPLAYS.
The number of times
# CYCLES =
“DATE” “TIME”
SET DATE:
“DATE” “TIME”
completed it’s start cycle, and the time
Displays and allows
setting of the date
, and AUX.
!
arrow
! "
arrow
the controller has
and date
and time
!
3.5.2 ANNUNCIATOR FAULT MESSAGES
The following table lists the Annunciator fault messages and their meanings.
LOW WATER
LEVEL
REMOTE
DISABLED
PURGE INTLK
OPEN
LOW AIR FLOW
SYSTEM FAULT
PURGE
INTERLOCKS
SYSTEM FAULT
LOW AIR
PRESSURE
FLAME FAULT
DURING
IGNITION TRIAL
LOCKOUT RUN
AIR FLOW
LOCKOUT RUN
FLAME
LOCKOUT RUN
HI EXHAUST
TEMP
The unit water level is below the probe level.
The interlock terminals, in the relay box, are not closed. The proof of closure switch or the purge switch did not prove closed during the start sequence. The air flow switch did not proved closed during the start sequence.
The proof of closure
switch or purge switch did not proved closed 45 seconds after the unit attempted to start.
The air pressure switch
did not prove closed 45 seconds after the unit attempted to start.
Flame did not prove at
the end of the trial for ignition period.
The air pressure switch
opened after flame was proven.
Flame signal was lost
after flame was proven.
The combustion
safeguard is locked out.
The exhaust gas
temperature has exceeded 500º F
3.5.3 ANNUNCIATOR START SEQUENCE MESSAGES
The following table lists the annunciator start sequence messages.
MESSAGE MEANING
AC power has been
RESET MAIN
POWER
HIGH WATER
TEMP
LOW GAS
PRESSURE
interrupted. Power must be shut off for 20 seconds to reset the display. Outlet water temperature has exceeded the high temperature limit setting. The unit has tripped due to low gas pressure.
13
MESSAGE MEANING
The unit is in standby
STANDBY
PURGING The unit is in the 7 sec
IGNITION TRIAL
FLAME PROVEN
mode waiting for a call
for heat
purge.
The unit is in ignition
position attempting to
light the burner
The unit has
established flame and
is running normally.
CONTROL PANEL OPERATING PROCEDURES
3.6 THE COMBUSTION SAFEGUARD CONTROLLER
The Combustion Safeguard is responsible for monitoring the safety components during the start sequence, and after flame is established. It is also responsible for timing of the purge and ignition cycles during the start sequence.
The combustion safeguard is located on the left side of the control panel as shown in Figure 3.9. There are five status LEDs that indicate the status of operation. Along with the annunciator, these are useful as a double check for proper system operation and troubleshooting. The table below defines the function of each light. The reset button located under the LEDs is to reset the combustion safeguard on lockout.
DESCRIPTION FUNCTION
POWER
PILOT
FLAME
MAIN
ALARM
Lights upon power up of
the unit.
Lights when there is a call
for heat.
Lights once flame has
been detected.
Lights after flame has
been detected and
stabilized
This lights when the
controller is in a LOCKOUT
condition.
3.7 WATER LEVEL TEST and RESET SWITCHES
The water level switches are located on the left side of the panel (see Fig. 3.10). When depressed the TEST switch simulates a low water level condition by breaking the connection between the water level probe and the sensing circuitry. To test the water level circuitry, depress the test switch for 3 seconds. The unit should fault resulting in the red fault light blinking and the LED display indicating LOW WATER LEVEL.

Figure 3.10

Water Level Test and Reset Switch Locations

Figure 3.9

Combustion Safeguard Status Indicator LED
Location
Note:
Only water level circuitry is tested during the
above test. To determine if the probe is
functioning properly, the water level must be
reduced below the level of the probe.
To reset the unit, depress the water level reset switch, the annunciator clear button, and if necessary, the reset button on the combustion safeguard.
3.8 ON/OFF SWITCH
The ON/OFF switch is located on the right side of the control box above the temperature controller (see Figure 3.1). It is part of the start string and must be in the ON position to enable the unit to fire. When the switch is in the ON position and illuminated, it is indicating that the start limit string, consisting of water temperature, gas pressure, water level, and the interlock is satisfied. The unit, at this point, is in standby mode and ready to run.
14
CONTROL PANEL OPERATING PROCEDURES
3.9 START SEQUENCE
When the unit is in the standby mode, and there is a demand for hot water, the following will occur:
1. Upon demand the temperature controller’s ON status indicator will light.
2. The combustion safeguard’s PILOT LED lights, and the blower contactor energizes, starting the blower.
3. The system next checks for proof of closure from the safety shut-off valve, (see Fig. 3.11), and the air fuel valve rotates open engaging the air /fuel valve open switch (see Fig. 3.12).
4. The LCD display shows PURGE INTLK OPEN until the above conditions are met. Once met the LCD display will show LOW AIR FLOW.
5. The blower proof switch closes, (See Fig.
3.13), and the LCD display will show PURGING.
6. Closure of the blower proof switch signals the combustion safeguard to begin its 7-second purge cycle.
145
146
147
149
148
FROM CONNECTOR 9A

Figure 3.12

Air/Fuel Valve Open and Engaging the
Air/Fuel Valve Open Microswitch
7. At the end of the purge cycle the combustion safeguard initiates a 10 second trial for ignition and the following simultaneously occurs:
The LCD displays the message IGNITION TRIAL.
The ignition transformer energizes.
The air/fuel valve rotates to its low fire
position. This engages the air-fuel valve closed switch, energizing the safety shut-off valve, (see Fig. 3.14).
PROOF OF CLOSURE SWITCH
SAFETY SHUT-OFF VALVE

Figure 3.11

Proof of Closure Switch Location

Figure 3.13

Blower Proof Switch Location

8. Once the combustion safeguard detects flame, its flame LED lights. Power is removed
15
CONTROL PANEL OPERATING PROCEDURES
from the ignition transformer and the MAIN LED lights of the combustion safeguard.
At this point, the annunciator will display FLAME PROVEN. The unit, in the automatic mode, is released to modulate through the PID controls.
3.10 AFTER FLAME
Once the control signal has gone below the stop level (see section 3.12 for Stop Level explanation), the temperature controller’s green ON light extinguishes, indicating there is no longer a call for heat. This signals the combustion safeguard to shut down the burner. The POWER LED of the combustion safeguard remains illuminated and the annunciator displays the message STANDBY.
3.11 FLAME TEST JACKS
The front of the combustion safeguard has two test jacks marked + and - for flame monitoring, (see Fig. 3.15). To access the test jacks remove the combustion safeguard cover by turning the center screw counterclockwise. A standard voltmeter is required to monitor the flame signal strength. A flame signal of 1.5 to 5VDC is typical during proper operation of the unit.

Figure 3.15

Flame Test Jack Location

3.12 START STOP LEVELS
The start and stop levels are the firing rate percentages that represent a call for heat and an indication that the call for heat has been satisfied. The start level is preset to 20% and the stop level is preset to 16%. These are factory preset and should not require adjustment.

Figure 3.14

Air/Fuel Valve in Ignition Position, Engaging
the Ignition Microswitch
16
SECTION 4 - INITIAL START UP
INITIAL START-UP
4.1 INITIAL START- UP REQUIREMENTS
The Initial Start-Up of the KC-1000 Boiler is comprised of the following steps:
installation completed 100%
combustion calibration
proper setting of controls and limits
temperature calibration
safety device testing (see Section 5)
Installation procedures should be completed 100% before performing initial start-up and the start-up must be complete prior to putting the unit into service. Starting a unit without the proper piping, venting, or electrical systems can be dangerous and void the product’s warranty. These start-up instructions should be precisely followed in order for the unit to operate safely, at a high thermal efficiency, and with low flue gas emissions.
Initial unit start-up is to be performed ONLY by AERCO factory trained start-up and service personnel. After following the steps in this section, it will be necessary to perform the mode of operation settings in section 5, and the safety control test procedures in section 6 to complete the initial unit start-up.
An AERCO Gas Fired Startup Sheet included with each KC-1000 must be completed for each unit for warranty validation and a copy must be returned promptly to AERCO at:
AERCO International, Inc. 159 Paris Ave. Northvale, NJ 07647
WARNING
!
DO NOT ATTEMPT TO FIRE THE UNIT
WITHOUT FULL WATER LEVEL. THI S
CAN SERIOUSLY DAMAGE THE UNIT
AND MAY RESULT IN PERSONAL
INJURY OR PROPERTY DAMAGE. THIS
IS NOT COVERED BY WARRANTY.
CAUTION!
All installation procedures in Section 2 must
be completed before attempting to start the
unit.
4.2 TOOLS AND INSTRUMENTATION
FOR COMBUSTION CALIBRATION
To properly perform combustion calibration, the proper instruments and tools must be used and correctly installed on the unit. The following sections outline the necessary tools and instrumentation as well as their installation.
4.2.1 REQUIRED TOOLS AND
INSTRUMENTATION
The following tools and instrumentation are necessary to perform combustion calibration of the unit:
1. A digital combustion analyzer with oxygen accuracy to 0.4%, and carbon monoxide in PPM
2. ** A 16" W.C. manometer and plastic tubing
3. Three, 1/8" NPT to barbed fittings for use with manometers
4. Aerco differential gas pressure regulator adjustment tool P/N GM-122643 (one supplied per installation)
5. Small and large flat blade screwdrivers
6. 7/16" open end wrench and small adjustable wrenches
7. Tube of silicone adhesive
8. * Digital multimeter with 10 amp and volt capability
*Although not necessary for actual start-up procedures, recommended for troubleshooting.
**For propane fired units: an additional 8" W.C. manometer and 1/2" NPT to barbed fitting is needed.
4.2.1 INSTALLING THE SUPPLY GAS
MANOMETER
1. Close the manual gas supply valve upstream of the unit.
2. Remove the 1/8" NPT pipe plug from the gas train assembly. This pipe plug is located below the low gas pressure switch before the safety shut off valve (see Fig. 4.1).
3. Install a barbed fitting into the pipe plug tapping.
4. Attach one end of a length of plastic tubing to the barbed fitting and one end to the 16" W.C. manometer.
17
1/4" NPT PLUG
(INSTALL MANOMETER
HERE)
SSOV

Figure 4.1

1/8” Gas Plug Location

4.2.2 PREPARING THE FLUE VENT PROBE HOLE
1. If the unit has been installed using the recommended AL29-4C vent, there will be a 3/8” hole, 18” to 24” above the exhaust manifold. The outer vent section, that covers vent section connections must be loosened and slid down to uncover the hole (see Fig. 4.2).
2. If equipped with one, adjust the stop on the combustion analyzer probe so that it extends into the flue gas flow without hitting the opposite wall of the flue. Do not insert the probe at this time.
INITIAL START-UP

Figure 4.3

Differential Reg ulator Adjustment Tool
Installation
4.2.3 INSTALLING THE DIFFERENTIAL REGULATOR ADJUSTMENT TOOL
1. Remove the cap from the differential pressure regulator (see Fig. 4.3).
2. Place the gasket from the regulator cap onto the regulator adjustment tool.
3. Prior to Installing the tools on the regulator pull up the tool's screwdriver blade. Then thread the tool into the regulator.
4. Engage the tool’s screwdriver blade into the regulator’s adjustment screw slot.
4.3 COMBUSTION CALIBRATION
The KC-1000 ships combustion calibrated from the factory. Recalibration as part of a start-up is necessary due to altitude, gas BTU content, gas supply piping and supply regulators. Factory test data sheets are shipped with each unit as a reference.

Figure 4.2

Analyzer Probe Hole Location

The following combustion calibration procedure closely follows the factory procedure. By following this procedure readjustment of combustion will be kept to a minimum.
NOTE:
If the instructions in section 4. 2 have not yet
been performed, go back and do so before
continuing.
1. Open the supply and return valves to the unit and ensure that the system pumps are running.
2. Open the gas supply valve(s) to the unit.
18
INITIAL START-UP
3. Using the 16” manometer installed as per Section 4.2.1, adjust the gas supply regulator until a reading of 12” W.C. static pressure is obtained.
4. Place the green ON/OFF switch in the OFF position. Turn on AC power to the unit. The temperature controller and annunciator displays should light.
5. Put the temperature controller in manual mode
NOTE:
For a review of control panel operating
procedures, see Section 3.
6. Change the firing rate (Pct) to 0.0%.
7. Place the green ON/OFF switch in the ON position.
8. Change the firing rate (Pct) to 25%. This will put the unit into the starting sequence.
NOTE:
On initial start-up or return to service from a
fault condition, a warm-up timer of 2
minutes is activated by the controller. This
prevents the BTU input from exceeding
400,000 BTUs/HR even though the control
signal may indicate a greater input.
9. Observing the 2 minute warm-up period increase the firing rate in 10 % increments while monitoring the gas pressure after every increase. If gas pressure dips below
8.5” W.C. for FM gas trains and 8.9” W.C. for IRI gas trains at any input percentage, stop and raise the pressure. Once 100% is reached adjust the gas pressure for 8.5” W.C. for FM and 8.9” W.C. for IRI.
NOTE:
If 8.5” W.C. (FM) or 8.9” (IRI ) gas pressure
cannot be obtained at the 100% firing rate,
it will be necessary to stop calibration and
contact the local AERCO representative in
your area. Running the unit on insufficient
gas pressure will void the warranty
10. Once 8.5” W.C. is set at the 100% level, change the firing rate (Pct) to 30%. Insert the combustion analyzer probe into the stack.
NOTE:
Always go to a percentage of firing rate from the same direction, ( i. e. , 100% to 30% or 30% to 20%). Whenever going to a firing
rate from below (i.e., 20% to 30%), first go above then back down to the desired firing
rate. This is necessary due to hysteresis in
the air/fuel stepper mot or. Hysteresis
causes the air/fuel valve to stop in a slightly
different position if the firing rat e
percentage is approached from below or
above. This results in a difference in
oxygen readings for the same f iring rate
percentage causing unnecessary
recalibration.
11. Allow enough time for the combustion analyzer to settle. Compare the measured oxygen level to the oxygen range for intake air temperature in Table 1.
Table 1
Inlet Air
Temp Oxygen
20oF 5.7% <50ppm 40oF 5.5% <50ppm 60oF 5.2% <50ppm 80oF 5.0% <50ppm
100oF 4.9% <50ppm
Combustion Oxygen Levels for a 30%
Firing Rate
12. If the measured oxygen level is within the range, at the current intake air temperature in Table 1, no adjustment is necessary. Proceed to step 17.
13. If the measured oxygen level is below the range in Table 1, rotate the differential regulator adjustment tool counter clockwise 1/4-1/2 revolution to decrease gas flow.
14. Wait for the combustion analyzer to settle, then compare the new oxygen reading to Table 1. Repeat adjustment until oxygen is within the specified range.
15. If the measured oxygen level is above the oxygen range in Table 1, rotate the differential regulator adjustment tool
Carbon
Monoxide
19
INITIAL START-UP
clockwise, 1/4-1/2 turns, to increase gas flow.
16. Wait for the analyzer reading to settle, then compare the new reading to Table 1. Repeat adjustment until oxygen is within the specified range.
NOTE:
Adjust only the different ial regulator at 30%
control signal, do not adjust the air shutter
17. Once the oxygen level is within the specified range at 30%, change the firing rate to 20%.
18. Oxygen levels at the 16% firing rate should be 10% or less as shown in Table 2. If the measured oxygen level is less then 10%, no adjustment is necessary. If the measured oxygen levels are greater than 10%, rotate the regulator adjustment tool clockwise 1/4 to 1/2 revolution to add gas.
19. Wait for the analyzer to settle. Repeat adjustment until the measured oxygen reading is 10% or less.
20. If the oxygen level cannot be brought to 10% or less, check the oxygen level in 1% increments above the 16% firing rate until an oxygen level of 10%, or less, is measured. Reset the unit’ stop level at that firing rate. Go back and recheck the oxygen level at 30% before continuing.
Table 2
Inlet Air
Temp
20oF 10% or less <25ppm 40oF 10% or less <25ppm 60oF 10% or less <25ppm 80oF 10% or less <25ppm
100oF 10% or less <25ppm
Combustion Oxygen Levels for a 20%
21. Change the firing rate to 100%. After the combustion analyzer has settled, compare the measured oxygen level with the levels in Table 3.
22. If the measured oxygen reading is below the oxygen range in Table 3, loosen the two bolts that secure the inlet air shutter to the unit using a 7/16” wrench (see Fig. 4.4).
Oxygen Carbon
Monoxide
Firing Rate
Open the shutter 1/4” to 1/2”, to increase the oxygen level then tighten the nuts.
23. Wait for the analyzer to settle, then compare the new oxygen reading to Table 3. Repeat the inlet air shutter adjustment until the oxygen is within the specified range. Firmly tighten the inlet air shutter locking nuts when finished.
Table 3
Inlet Air
Temp
Oxygen Carbon
Monoxide
20oF 5.4% <150ppm 40oF 5.4% <150ppm 60oF 5.2% <150ppm 80oF 4.9% <150ppm
100oF 4.7% <150ppm
Combustion Oxygen Levels for a 100%
Firing Rate
REMINDER:
At 30% firing rate adjust only the differential
pressure regulator. At 100% firing rate,
adjust only the inlet air shutter.
BLOWER INLET

Figure 4.4

Air Shutter Locking Nut Locat ion

24. If the measured oxygen reading is above the oxygen range in Table 3, loosen the two 7/16" locking nuts securing the inlet air shutter. Close the air shutter 1/4” to 1/2” to decrease the oxygen level and tighten the two nuts.
25. Allow the analyzer to settle, then compare the new oxygen reading to Table 3.
SCREEN
SHUTTER
SHUTTER LOCKING
NUTS
BLOWER OUTLET
20
INITIAL START-UP
26. Allow the analyzer to settle. Repeat the adjustment until the oxygen is within the specified range. Firmly tighten the inlet air shutter locking nuts when finished.
NOTE:
Adjust the inlet air shutter only at 100%
firing rate. Do not adj ust the differential
pressure regulator.
27. Change the firing rate to 30%. Allow time for the combustion analyzer to settle. Check the measured oxygen reading to insure that it is still within the range as per Table 1.
28. Continue this procedure until all oxygen levels are within the ranges specified in Tables 1,2, and 3.
29. Record all readings on the AERCO start-up sheet provided with each unit. Proceed to Section 4.5.
4.4 PROPANE COMBUSTION
CALIBRATION
For propane units it will be necessary to install an additional 8” W.C. manometer as described below. This is used to measure the pressure drop across the air/propane mixing orifice.
1. Referring to Fig. 4.5 remove the 1/8” NPT plug from the gas inlet pipe ahead of the burner and install an 1/8” NPT barbed fitting.
2. Remove the 1/2” NPT plug from the tee located after the air pressure regulator and install a 1/2” barbed fitting (see fig. 4.5).
3. Attach the 8” W.C. manometer to the barbed fittings installed in steps 1, and 2.
4. While following the combustion calibration procedure in Section 4.3 measure the pressure drop across the air/propane mixing orifice using the 0-8” W.C. manometer.
5. This reading should remain a constant 3.8” to 4” W.C. throughout the operating range.
6. If the pressure drop is not within this range, remove the cap from the air pressure regulator.
7. Using a flat blade screwdriver adjust the regulator until 3.8”-4.0” W.C. is obtained. Clockwise will increase the reading and counter-clockwise will decrease the reading.
8. If adjustments are made to this regulator it will be necessary to recheck oxygen settings at 16%, 30%, and 100% firing rates
NOTE:
After an adjustment is m ade to the air
regulator, the cap must be put back on
securely to obtain an accurate reading

Figure 4.5

Propane Air Different ial Pressure Taps

4.5 UNIT REASSEMBLY
Once combustion calibration is set properly, the unit can be re-assembled for permanent operation.
1. Put the green ON/OFF switch in the off position. Disconnect the AC power supply to the unit.
2. Shut off the gas supply to the unit.
3. Remove the regulator adjustment tool by first pulling up the screwdriver blade to disengage it from the regulator adjusting screw, and then turning the tool out of the top of the regulator.
4. Remove the gasket from the tool and place it back onto the regulator cap.
5. Apply a drop of silicone to the regulator adjusting screw to lock its setting.
6. Reinstall the cap and gasket back on the regulator. Tighten the cap using a screwdriver or wrench.
7. Remove all of the manometers and barbed fittings and reinstall the pipe plugs using a suitable thread compound.
21
Loading...
+ 58 hidden pages