AEM 30-2340-N 4-Channel Wideband UEGO AFR Controller User Manual

AEM 4-CH WIDEBAND UEGO CONTROLLER WITH
Part Number 30-2340-N
NASCAR SPEC ECU CAN CONFIGURATION
FIGURE 1. WIRING DIAGRAM
AEM Performance Electronics
th
2205 126
Phone: (310) 484-2322 Fax: (310) 484-0152
http://www.aemelectronics.com
Instruction Part Number: 10-2340-N
© 2012 AEM Performance Electronics
AEM 4 CH UEGO Controller Parts
1 x 35-2340 4 CH UEGO Module 1 x 35-2908 Wiring Harness 4 x 1-2059 6-32 Stainless Steel Hex Nut 4 x 1-2047 6-32 x 1 ¼ screw 1 x 10-2340-N Installation Instructions
INSTALLATION
PROCEDURE OVERVIEW
1. Disconnect the negative battery cable.
2. Find a suitable mounting location for the 4 CH UEGO controller, away from any direct heat or water sources and shielded from the elements.
3. Connect the flying lead analog output wires as shown in Figure 1.
4. Mount the UEGO sensors as shown in figure 2.
5. Plug the UEGO sensor connector on the harness into the mating connector on each UEGO sensor.
6. Install the 30-2064 EBP sensor kit* and connect it as shown in Figure 1. * Sold Separately
WIRING INSTRUCTIONS
Power
RED - Connect to a switched, fused (20A) 12-volt power source, that is on only when
the engine is running.
BLACK – Connect to a clean power ground.
Outputs
WHITE - Connect to Lambda + Input. BLACK - Connect to sensor ground. Connect to power ground if sensor ground is not available.
Page 2
MOUNTING INSTRUCTIONS
UEGO Sensor Mounting
A high flow stainless steel weld-in sensor bung is needed for sensor installation (additional sensors & bungs are available 30-2063). The bung is specifically designed so the sensor can provide accurate AFR readings with minimal flow intrusion and survive extreme exhaust gas temperatures. Pick a mounting location(s) that allows for easy access to the sensor(s). The sensor tip must be exposed to exhaust gas in order to give accurate AFR readings. For thin wall tubing, drill a 15/16” hole and weld in the bung. For thick wall tubing/ castings, drill a 1 1/16” hole and weld in the bung. The sensor must be mounted at an angle of at least 10 degrees from horizontal in order to prevent liquids from collecting in the sensor housing. See Figure 2 below. NOTE:
THE OPTIONAL AEM EBP (EXHAUST BACK PRESSURE) KIT (PART # 30-2064) MUST BE USED IF SENSORS ARE MOUNTED PRE-TURBO.
FIGURE 2. Sensor Bung and Sensor Mounting
Controller Mounting
Mount the controller using the supplied 6-32 x 1 ¼ stainless steel screws and nuts. See Figure 3 and Figure 4 for mounting holes and footprint size.
Page 3
Mounting Screws
FIGURE 3. Mounting holes
FIGURE 4. Dimensions
OPERATING INSTRUCTIONS
INDICATOR LIGHTS
The AEM 4 CH UEGO controller has eight indicator LEDs, one Status and one Ready LED for each channel (Figure 5). Both Ready and Status LEDs flash during sensor
Page 4
warm up. Once the UEGO sensor reaches operating temperature, usually within 30 seconds, the Status LED will turn off and the Ready LED will remain on solid. If a UEGO sensor error is detected, analog output will switch to approximately +5V and both LEDs will flash. The Status LED will flash on and off a number of times, followed by a short pause, signifying an error code. The error codes are listed below in Table 1.
# of Flashes Fault Corrective Action
1 UEGO sensor heater open 2 Virtual Ground (VM) Error 3 Nernst Cell (UN) Error 4 Pump current (IP) Error
Check sensor cable for
broken wires/shorts
5 UEGO sensor heater time out 6 UEGO sensor heater short 7 System voltage below 10 volts dc Check electrical system
for good connections
and proper function
TABLE 1. Error Codes
When there is no UEGO sensor connected to a particular channel, the Status LED of that channel will remain on solid and the Ready LED will turn off after a few minutes. The remaining channels with UEGO sensors connected will function properly.
When the exhaust back pressure kit (30-2064) is used, the 4 CH UEGO controller will monitor exhaust back pressure. (NOTE: The 4 CH UEGO controller is designed to
work with a specific AEM pressure sensor. Do not use any sensor other than the one included in the Exhaust Back Pressure Kit.) If a pressure sensor error is
detected, the 4 CH UEGO controller turns off all Ready LEDs and flashes Status LEDs, starting with CH1 and ending with CH4. The analog output voltage level for all 4 channels switches to approximately +5V to signify an error.
Status Indicator LED
FIGURE 5. Indicator Lights
Ready Indicator LED
Page 5
BACK PRESSURE COMPENSATION (OPTIONAL)
UEGO sensors are extremely sensitive to pressure. Without an EBP kit (30-2064), UEGO sensors mounted before the turbocharger will give inaccurate AFR readings due to back pressure. When the EBP kit is installed correctly, the 4 CH UEGO controller will output accurate AFR readings. UNDER NO CIRCUMSTANCES SHOULD UEGO SENSORS BE MOUNTED PRE-TURBO WITHOUT USING THE EBP KIT.
When using multiple 4 Channel UEGO controllers on twin turbo or dual bank engines, it is recommended that an EBP kit is used for each controller as back pressure levels can vary per bank. When using multiple 4 Channel UEGO controllers on single turbo engines, such as an inline 6, it is possible to share a single EBP source. To share a single EBP source between multiple controllers, the green and black EBP wires for each controller must be tied together as shown in Figures 6 and 7. Use extreme caution when modifying the harness as improper connections may result in inaccurate AFR readings. Be sure to cover all connections with moisture resistant heat shrink or equivalent covering.
Figure 6. EBP sensor connector Figure 7. Cut & Spliced wires
UEGO ANALOG OUTPUT
The analog output from the 4 CH UEGO controller is a linear dc voltage signal that varies from 0.5 Vdc at 8.5:1 AFR Gasoline (0.58 Lambda) to 4.5Vdc at 18.0:1 AFR Gasoline (1.22 Lambda). The signal is used for sending information to a data logger or an engine management system such as the AEM EMS or F/IC. The transfer function for the output is listed below.
AFR Gasoline = 2.375(V) + 7.3125
For example, if the output is 2.0 Vdc, the AFR is 12.06:1
2.375 * 2.0 + 7.3125 = 12.06
Page 6
A table showing the analog output voltage and corresponding Air/Fuel ratios for some of the common fuels is shown below in Table 2.
AFR
VOLTS LAMBDA AFR GAS
0.50 0.58 8.5 3.7 5.6 5.2
0.71 0.61 9.0 3.9 5.9 5.5
0.92 0.65 9.5 4.1 6.3 5.8
1.13 0.68 10.0 4.4 6.6 6.1
1.34 0.71 10.5 4.6 6.9 6.4
1.55 0.75 11.0 4.8 7.3 6.7
1.76 0.78 11.5 5.0 7.6 7.0
1.97 0.82 12.0 5.2 7.9 7.3
2.18 0.85 12.5 5.4 8.2 7.7
2.39 0.88 13.0 5.7 8.6 8.0
2.61 0.92 13.5 5.9 8.9 8.3
2.82 0.95 14.0 6.1 9.2 8.6
3.03 0.99 14.5 6.3 9.6 8.9
3.11 1.00 14.7 6.4 9.7 9.0
3.24 1.02 15.0 6.5 9.9 9.2
3.45 1.05 15.5 6.7 10.2 9.5
3.66 1.09 16.0 7.0 10.6 9.8
3.87 1.12 16.5 7.2 10.9 10.1
4.08 1.16 17.0 7.4 11.2 10.4
4.29 1.19 17.5 7.6 11.5 10.7
4.50 1.22 18.0 7.8 11.9 11.0
METHANOL AFR E85
AFR
ETHANOL
TABLE 2. AFR Values
AEMNet NETWORK
The AEMNet is designed to provide easy installation & communication between compatible AEM devices. The 4 CH UEGO controller outputs Lambda values of all four channels and other useful information via the network. If using a non-AEM device to communicate with the 4 CH UEGO controller, refer to the section " Connecting To the AEMNet Network Using a non-AEM Device” below.
4 CH UEGO controller information:
Lambda values (all 4 channels)
Error messages (all 4 channels)
o UEGO sensor Error o System low power Error o EBP sensor error
Cylinder Configuration Mode (1 – 7), refer to Table 3.
Exhaust Back Pressure sensor value in PSIg
Exhaust Back Pressure sensor status
Page 7
There are 7 different cylinder numbering combinations available on the AEM network. The different combinations allow for easy installation and data analysis, and allow users to connect up to three 4 Channel UEGO modules on the AEM network. See Table 3 and the figures below for recommended connections on some of the more common engine configurations.
MODE 4
MODE 3
MODE 1
CHEVROLET/ DODGE/ TOYOTA FORD
MODE 6
MODE 3
HONDA / ACURA NISSAN / TOYOTA
MODE 2
MODE 4MODE 7
MODE 2
MODE 5
MODE 4
MODE 1
MODE 3
VIPER V12
Page 8
MODE 5
MODE 6
MODE 7
MODE 1
4 CYLINDER 6 CYLINDER
FIGURE 8. 4 CH UEGO controller configuration mode
MODE 1 MODE 2 MODE 3 MODE 4 MODE 5 MODE 6 MODE 7 UEGO 1 Cylinder1 Cylinder 5 Cylinder 1 Cylinder 2 Cylinder 9 Cylinder 1 Cylinder 4 UEGO 2 Cylinder 2 Cylinder 6 Cylinder 3 Cylinder 4 Cylinder 10 Cylinder 2 Cylinder 5 UEGO 3 Cylinder 3 Cylinder 7 Cylinder 5 Cylinder 6 Cylinder 11 Cylinder 3 Cylinder 6 UEGO 4 Cylinder 4 Cylinder 8 Cylinder 7 Cylinder 8 Cylinder 12 --- ---
TABLE 3. UEGO sensor connection
For example, Chevrolet big block engines require two 4 CH UEGO controllers. The first unit connects to cylinders 2, 4, 6 and 8 using MODE 4 (see Table 3). UEGO 1 connects to cylinder 2, UEGO 2 to cylinder 4, UEGO 3 to cylinder 6, and UEGO 4 to cylinder 8. The second unit connects to cylinders 1, 3, 5 and 7 using MODE 3. UEGO 1 connects to cylinder 1, UEGO 2 to cylinder 3, and so on.
Honda / Acura V6 engines also require two 4 CH UEGO controllers. As shown in Figure 8, Mode 6 and 7 from Table 3 are used. UEGO 1, 2, 3 of the first 4 CH UEGO controller connect to cylinders 1, 2 and 3. UEGO 1, 2, 3 of the second unit go to cylinder 4, 5 and 6. Unused channels can be left unconnected.
Cylinder Mode Configuration
NOTE: Only applicable when using AEMnet. Configuration mode is selected during the power up sequence. By factory default the 4
CH UEGO controller is in MODE 1. There are three wires, CONFIG 1 (pink), CONFIG 2 (purple) and GROUND (yellow) under the sleeve on the wiring harness (Figure 9). To change the mode, first make sure the 4 CH UEGO controller is powered off. Connect CONFIG 1 to GROUND and power the 4 CH UEGO controller on. Tap CONFIG 2 to the GROUND wire. The 4 Channel UEGO controller will jump to the next mode every time the CONFIG 2 wire is tapped to the GROUND wire. The LEDs will illuminate to
Page 9
show the selected mode. The number of Status/Error LED’s illuminated corresponds to the mode selected. When a desired mode is selected, disconnect both CONFIG wires from the GROUND wire. The mode will be saved in the controller and the LEDs of the corresponding mode will blink three times. When more than one 4 CH UEGO
controller is connected to the net, the controllers must be in different modes.
Upon powering up, the number of LEDs corresponding to the mode will blink three times to indicate the mode. For example, if in mode 7, 7 LED’s will blink 3 times.
FIGURE 9. Mode Configuration Wires
Connecting to the AEMnet Network
Each 4 CH UEGO controller wiring harness has 2 connectors for accessing the AEMnet (Refer to figure 10), one for accessing the network and the other for an expansion to other devices.
FIGURE 10. AEMnet Connector
Page 10
To join the AEM network, connect the Deutsch male connector to the female connecter of other AEM devices in the network (Figure 11).
FIGURE 11. AEMnet cable connection
Connecting To The AEMnet Network Using a non-AEM Device with CAN
Each AEMnet connector has 4 pins, CAN+ (PIN1, White), CAN- (PIN2, Green) and two pins for power carry-over (PIN3 and PIN4, Red and Black). NOTE: Pin numbers are located at the back of the connector. Non-AEM devices can connect to the AEMnet by connecting their CAN +/- wires to the CAN+/- wires on the AEM network. The parts for mating connectors are listed below and shown in Figure 12.
Deutsch DTM04-4P (Receptacle connector)
Deutsch 1060-20-0122 (Pins)
Deutsch DTM06-4S (Plug connector)
Deutsch 1062-20-0122 (Pins)
Figure 12. Connector Assembly
Page 11
NOTE: the 4 CH UEGO controller has one terminating resistor. If an additional terminating resistor is needed, one must be installed on the other device.
Network Message Structure
The 4 CH UEGO controller transmits two messages through the CAN network. The first message contains Lambda values of all four channels and is transmitted every 10 ms. The second message, transmitted every 40 ms, includes error flags, cylinder configuration mode, EBP sensor readings and status. Messages are transmitted at 1Mbps and use standard format message ID (11 bits). Appendix A shows entire message protocols, including message IDs, number of bytes, data field, etc.
Lambda values are scaled up by 10,000 to retain decimal points. For example, if a value of 9,876 is received as a lambda value from a 4 CH UEGO controller, the actual lambda value is 0.9876. Use the following equation to derive the actual lambda value:
Actual Lambda value = Lambda from a message / 10,000
The back pressure value is scaled up by 100. Use the following equation to derive the actual back pressure value.
Actual back pressure value (PSIg) = pressure from a message / 100
USING THE 4 CH UEGO CONTROLLER WITH AN AEM SERIES 2 EMS (Including EMS - 4)
AEMnet Network
Tuner Setup (Must use 01v22 firmware or newer)
In the AEMTuner EMS software go to Wizards -> Setup Wizard. Under Wizard types, click on Setup: CAN Receive. Choose a configuration and click Apply. There are currently 4 configuration types available: MODE 1 + EBP Sensor, MODE 1 + MODE 2, MODE 4 + MODE 5, and MODE 6 + MODE 7. Once this configuration is completed correctly, the word “Matched” will appear next to the configuration chosen, as shown in Figure 13. Read the notes under Configuration Notes and close the window.
Page 12
FIGURE 13. Series 2 EMS / EMS – 4 Setup Wizard
Viewing Live Data
Right-click in a blank space in the AEMTuner software and choose Add Channel Display. From the list of available channels, select all the ones associated with the selected configuration mode, as listed in Table 4. Figure 14 shows the Channel display for “Mode 1 + EBP Sensor.”
Configuration Mode Channels To Be Added
Mode 1 + EBP Sensor
UEGO M1 Cyl 1 UEGO M1 Cyl 2
UEGO M1 Cyl 3 UEGO M1 Cyl 4
UEGO M1 EBP Sensor
Mode 1 + Mode 2
UEGO M1 Cyl 1 UEGO M2 Cyl 1 UEGO M1 Cyl 2 UEGO M2 Cyl 2 UEGO M1 Cyl 3 UEGO M2 Cyl 3 UEGO M1 Cyl 4 UEGO M2 Cyl 4
Mode 4 + Mode 5
UEGO M4 Cyl 1 UEGO M5 Cyl 1 UEGO M4 Cyl 2 UEGO M5 Cyl 2 UEGO M4 Cyl 3 UEGO M5 Cyl 3 UEGO M4 Cyl 4 UEGO M5 Cyl 4
Mode 6 + Mode 7
UEGO M6 Cyl 1 UEGO M7 Cyl 1 UEGO M6 Cyl 2 UEGO M7 Cyl 2 UEGO M6 Cyl 3 UEGO M7 Cyl 3 UEGO M6 Cyl 4 UEGO M7 Cyl 4
TABLE 4. Channel Selection
Page 13
FIGURE 14. Mode 1 + EBP Sensor
Analog Outputs (Refer to EMS Instructions for more information)
Hardware Setup
Connect two WHITE AFR output + wires to O2 #1 and O2 #2 EMS analog input pins. Connect the BLACK Analog Output – wire to the EMS sensor ground.
NOTE: The current version of EMS has only two input pins dedicated to O2 analog inputs. To view the analog outputs from all four channels use spare analog inputs, i.e., EGT1 ~ 4.
Tuner Setup (Must use 01v22 firmware or newer)
With an EMS calibration open in the AEMTuner software, go to Wizards -> Setup Wizard and choose Sensor: 02 #1 (AFR) and Sensor 02 #2 (AFR). Under Configuration Name, choose AEM (4-Channel UEGO PN 30-2340) and click Apply. When the configuration is set, as shown in figure 15, close the wizard.
Page 14
FIGURE 15. Series 2 EMS / EMS – 4 Setup Wizard
Viewing Live Data
Open a new Channels Display in AEMTuner and add O2 #1 and O2 #2 channels. The Channel Display, as shown in figure 16, will show the values in air-to-fuel ratio.
FIGURE 16. O2 #1 and O2 #2
When using spare analog inputs, the values will show in Volts. Use the following equation to convert to air-to fuel ratio.
AFR Gasoline = 2.375 x voltage + 7.3125
Page 15
CONNECTOR PIN-OUTS
The pin-out for the UEGO sensor connector is shown below in Figure 17.
FIGRE 17. UEGO Connector Pin-out
SPECIFICATIONS
4 CH UEGO Controller
Supply Current (nominal, peak) 3.2A, 10.5A peak Differential Analog Outputs 4 Measuring Range: UEGO 8.5:1 to 18:1 AFR Gasoline, 0.58-1.22 Lambda UEGO Sensor Accuracy 0.1 AFR Operating Voltage (nominal) 8.5-15 volts dc Harness & Connector Temp Limit:105C
NOTES
If further tuning help is needed be sure to visit the video gallery or performance electronics forum at www.aemelectronics.com for comprehensive instructional videos and information.
The UEGO sensor contains a ceramic module and should not be subject to mechanical or thermal shock or it may be damaged. The sensor is not designed for operation on leaded fuels; doing so will dramatically shorten sensor life. Long term running in the rich region (Lambda < 0.95) will shorten sensor life. High exhaust temperatures (over 850C) will shorten sensor life. Engine oil consumption at a rate greater than 1 quart per 1,000 miles will shorten sensor life. With the UEGO Sensor installed, do not run the engine without power applied to 4 CH UEGO controller.
REPLACEMENT/OPTIONAL UEGO CONTROLLER COMPONENTS
30-2001 UEGO Sensor 35-4008 Stainless Steel UEGO Sensor Bung 30-2063 Sensor Kit with Stainless Bung 30-2064 Exhaust Back Pressure (EBP) Kit
Page 16
APPENDIX A
CAN MESSAGE PROTOCOL
CAN 2.0b, 11 bit address, 1 Mbit/sec 8 data bytes/message
All multi-byte data packed big endian unless specified (most significant byte transmitted first) All bits numbered with the LSB = bit0, MSB = bit7
Message ID: 0x0000001F
Source: AEM 4 Channel UEGO set on MODE 1
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1 2 3 4 5 6 7
Lambda 1 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 2 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 3 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 4 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Message ID: 0x00000020
Source: AEM 4 Channel UEGO set on MODE 2
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1 2 3 4 5 6 7
Message ID: 0x00000021
Source: AEM 4 Channel UEGO set on MODE 3
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1 2 3 4 5 6 7
Lambda 5 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 6 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 7 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 8 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 1 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 3 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 5 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 7 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Page 17
Message ID: 0x00000022
Source: AEM 4 Channel UEGO set on MODE 4
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1 2 3 4 5 6 7
Message ID: 0x00000023
Source: AEM 4 Channel UEGO set on MODE 5
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1 2 3 4 5 6 7
Lambda 2 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 4 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 6 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 8 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 9 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 10 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 11 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 12 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Message ID: 0x00000024
Source: AEM 4 Channel UEGO set on MODE 6
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1 2 3 4 5 6 --- --- --- --- --­7 --- --- --- --- ---
Message ID: 0x00000025
Source: AEM 4 Channel UEGO set on MODE 7
Rate: 10ms continuous
Byte Label Data Type Scaling Offset Range
0 1
Lambda 1 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 2 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 3 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 4 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Page 18
2 3 4 5 6 --- --- --- --- --­7 --- --- --- --- ---
Message ID: 0x000001AF
Source: AEM 4 Channel UEGO set on MODE 1
Rate: 40ms continuous
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7) 1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0) 2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7) 3 (bit0) 3 (bit1) 3 (bit2) 3 (bit3) 3 (bit4) 3 (bit5) 3 (bit6) 3 (bit7) 4 (bit0) 4 (bit1) 4 (bit2)
AFR 1 Heater Time-Out Error
AFR 2 Heater Time-Out Error
AFR 3 Heater Time-Out Error
AFR 4 Heater Time-Out Error
Lambda 5 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
Lambda 6 16 bit unsigned .0001 Lambda/bit 0 0 to 6.5535 Lambda
AFR 1 Ready
AFR 1 Heater Open Error
AFR 1 VM Error AFR 1 UN Error
AFR 1 IP Error
AFR 1 Heater Short Error
AFR 1 Overtemp Error
AFR 2 Ready
AFR 2 Heater Open Error
AFR 2 VM Error AFR 2 UN Error
AFR 2 IP Error
AFR 2 Heater Short Error
AFR 2 Overtemp Error
AFR 3 Ready
AFR 3 Heater Open Error
AFR 3 VM Error AFR 3 UN Error
AFR 3 IP Error
AFR 3 Heater Short Error
AFR 3 Overtemp Error
AFR 4 Ready
AFR 4 Heater Open Error
AFR 4 VM Error AFR 4 UN Error
AFR 4 IP Error
AFR 4 Heater Short Error
AFR 4 Overtemp Error
UEGO Low Voltage Error
EBP sensor ready
EBP sensor Error Low Volt
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 19
4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) 5 (bit1) 5 (bit2) 5 (bit3) 5 (bit4) 5 (bit5) 5 (bit6) 5 (bit7)
6 7
Message ID: 0x000001B0
Source: AEM 4 Channel UEGO set on MODE 2
Rate: 40ms continuous
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7) 1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0) 2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7) 3 (bit0) 3 (bit1)
EBP sensor detected
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Reserved Reserved Reserved
Reserved Sensor 4 Heating up Sensor 3 Heating up Sensor 2 Heating up Sensor 1 Heating up
Exhaust Pressure 1 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
AFR 5 Ready
AFR 5 Heater Open Error
AFR 5 VM Error AFR 5 UN Error
AFR 5 IP Error
AFR 5 Heater Time-Out Error
AFR 5 Heater Short Error
AFR 5 Overtemp Error
AFR 6 Ready
AFR 6 Heater Open Error
AFR 6 VM Error AFR 6 UN Error
AFR 6 IP Error
AFR 6 Heater Time-Out Error
AFR 6 Heater Short Error
AFR 6 Overtemp Error
AFR 7 Ready
AFR 7 Heater Open Error
AFR 7 VM Error AFR 7 UN Error
AFR 7 IP Error
AFR 7 Heater Time-Out Error
AFR 7 Heater Short Error
AFR 7 Overtemp Error
AFR 8 Ready
AFR 8 Heater Open Error
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 20
3 (bit2) 3 (bit3) 3 (bit4) 3 (bit5) 3 (bit6) 3 (bit7) 4 (bit0) 4 (bit1) 4 (bit2) 4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) 5 (bit1) 5 (bit2) 5 (bit3) 5 (bit4) 5 (bit5) 5 (bit6) 5 (bit7)
6 7
AFR 8 VM Error AFR 8 UN Error
AFR 8 IP Error
AFR 8 Heater Time-Out Error
AFR 8 Heater Short Error
AFR 8 Overtemp Error
UEGO Low Voltage Error
EBP sensor ready
EBP sensor Error Low Volt
EBP sensor detected
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Reserved
Reserved
Reserved
Reserved Sensor 8 Heating up Sensor 7 Heating up Sensor 6 Heating up Sensor 5 Heating up
Exhaust Pressure 2 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Message ID: 0x000001B1
Source: AEM 4 Channel UEGO set on MODE 3
Rate: 40ms continuous
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7) 1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0)
AFR 1 Ready
AFR 1 Heater Open Error
AFR 1 VM Error AFR 1 UN Error
AFR 1 IP Error
AFR 1 Heater Time-Out Error
AFR 1 Heater Short Error
AFR 1 Overtemp Error
AFR 3 Ready
AFR 3 Heater Open Error
AFR 3 VM Error AFR 3 UN Error
AFR 3 IP Error
AFR 3 Heater Time-Out Error
AFR 3 Heater Short Error
AFR 3 Overtemp Error
AFR 5 Ready
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 21
2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7) 3 (bit0) 3 (bit1) 3 (bit2) 3 (bit3) 3 (bit4) 3 (bit5) 3 (bit6) 3 (bit7) 4 (bit0) 4 (bit1) 4 (bit2) 4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) 5 (bit1) 5 (bit2) 5 (bit3) 5 (bit4) 5 (bit5) 5 (bit6) 5 (bit7)
6 7
AFR 5 Heater Open Error
AFR 5 VM Error AFR 5 UN Error
AFR 5 IP Error
AFR 5 Heater Time-Out Error
AFR 5 Heater Short Error
AFR 5 Overtemp Error
AFR 7 Ready
AFR 7 Heater Open Error
AFR 7 VM Error AFR 7 UN Error
AFR 7 IP Error
AFR 7 Heater Time-Out Error
AFR 7 Heater Short Error
AFR 7 Overtemp Error
UEGO Low Voltage Error
EBP sensor ready
EBP sensor Error Low Volt
EBP sensor detected
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Reserved
Reserved
Reserved
Reserved Sensor 7 Heating up Sensor 5 Heating up Sensor 3 Heating up Sensor 1 Heating up
Exhaust Pressure 1 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Message ID: 0x000001B2
Source: AEM 4 Channel UEGO set on MODE 4
Rate: 40ms continuous
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7)
AFR 2 Ready
AFR 2 Heater Open Error
AFR 2 VM Error AFR 2 UN Error
AFR 2 IP Error
AFR 2 Heater Time-Out Error
AFR 2 Heater Short Error
AFR 2 Overtemp Error
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 22
1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0) 2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7) 3 (bit0) 3 (bit1) 3 (bit2) 3 (bit3) 3 (bit4) 3 (bit5) 3 (bit6) 3 (bit7) 4 (bit0) 4 (bit1) 4 (bit2) 4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) --- --- --- --- --­5 (bit1) --- --- --- --- --­5 (bit2) --- --- --- --- --­5 (bit3) --- --- --- --- --­5 (bit4) 5 (bit5) 5 (bit6) 5 (bit7)
6 7
AFR 4 Ready
AFR 4 Heater Open Error
AFR 4 VM Error AFR 4 UN Error
AFR 4 IP Error
AFR 4 Heater Time-Out Error
AFR 4 Heater Short Error
AFR 4 Overtemp Error
AFR 6 Ready
AFR 6 Heater Open Error
AFR 6 VM Error AFR 6 UN Error
AFR 6 IP Error
AFR 6 Heater Time-Out Error
AFR 6 Heater Short Error
AFR 6 Overtemp Error
AFR 8 Ready
AFR 8 Heater Open Error
AFR 8 VM Error AFR 8 UN Error
AFR 8 IP Error
AFR 8 Heater Time-Out Error
AFR 8 Heater Short Error
AFR 8 Overtemp Error
UEGO Low Voltage Error
EBP sensor ready
EBP sensor Error Low Volt
EBP sensor detected
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Sensor 8 Heating up Sensor 6 Heating up Sensor 4 Heating up Sensor 2 Heating up
Exhaust Pressure 2 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Message ID: 0x000001B3
Source: AEM 4 Channel UEGO set on MODE 5
Rate: 40ms continuous
Page 23
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7) 1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0) 2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7) 3 (bit0) 3 (bit1) 3 (bit2) 3 (bit3) 3 (bit4) 3 (bit5) 3 (bit6) 3 (bit7) 4 (bit0) 4 (bit1) 4 (bit2) 4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) --- --- --- --- --­5 (bit1) --- --- --- --- --­5 (bit2) --- --- --- --- --­5 (bit3) --- --- --- --- --­5 (bit4)
AFR 10 Heater Time-Out Error
AFR 11 Heater Time-Out Error
AFR 12 Heater Time-Out Error
AFR 9 Ready
AFR 9 Heater Open Error
AFR 9 VM Error AFR 9 UN Error
AFR 9 IP Error
AFR 9 Heater Time-Out Error
AFR 9 Heater Short Error
AFR 9 Overtemp Error
AFR 10 Ready
AFR 10 Heater Open Error
AFR 10 VM Error AFR 10 UN Error
AFR 10 IP Error
AFR 10 Heater Short Error
AFR 10 Overtemp Error
AFR 11 Ready
AFR 11 Heater Open Error
AFR 11 VM Error AFR 11 UN Error
AFR 11 IP Error
AFR 11 Heater Short Error
AFR 11 Overtemp Error
AFR 12 Ready
AFR 12 Heater Open Error
AFR 12 VM Error AFR 12 UN Error
AFR 12 IP Error
AFR 12 Heater Short Error
AFR 12 Overtemp Error
UEGO Low Voltage Error
EBP sensor ready
EBP sensor Error Low Volt
EBP sensor detected
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Sensor 12 Heating up
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Boolean 0 = false, 1 = true 0 0/1
Page 24
5 (bit5) 5 (bit6) 5 (bit7)
6 7
Message ID: 0x000001B4
Source: AEM 4 Channel UEGO set on MODE 6
Rate: 40ms continuous
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7) 1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0) 2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7)
3 --- --- --- --- --­4 (bit0) 4 (bit1) 4 (bit2) 4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) --- --- --- --- --­5 (bit1) --- --- --- --- --­5 (bit2) --- --- --- --- ---
Sensor 11 Heating up Sensor 10 Heating up
Sensor 9 Heating up
Exhaust Pressure 2 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
AFR 1 Ready
AFR 1 Heater Open Error
AFR 1 VM Error AFR 1 UN Error
AFR 1 IP Error
AFR 1 Heater Time-Out Error
AFR 1 Heater Short Error
AFR 1 Overtemp Error
AFR 2 Ready
AFR 2 Heater Open Error
AFR 2 VM Error AFR 2 UN Error
AFR 2 IP Error
AFR 2 Heater Time-Out Error
AFR 2 Heater Short Error
AFR 2 Overtemp Error
AFR 3 Ready
AFR 3 Heater Open Error
AFR 3 VM Error AFR 3 UN Error
AFR 3 IP Error
AFR 3 Heater Time-Out Error
AFR 3 Heater Short Error
AFR 3 Overtemp Error
UEGO Low Voltage Error
EBP sensor ready
EBP sensor Error Low Volt
EBP sensor detected
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 25
5 (bit3) 5 (bit4) --- --- --- --- --­5 (bit5) 5 (bit6) 5 (bit7)
6
7
Message ID: 0x000001B5
Source: AEM 4 Channel UEGO set on MODE 7
Rate: 40ms continuous
Byte Label Data Type Scaling Offset Range
0 (bit0) 0 (bit1) 0 (bit2) 0 (bit3) 0 (bit4) 0 (bit5) 0 (bit6) 0 (bit7) 1 (bit0) 1 (bit1) 1 (bit2) 1 (bit3) 1 (bit4) 1 (bit5) 1 (bit6) 1 (bit7) 2 (bit0) 2 (bit1) 2 (bit2) 2 (bit3) 2 (bit4) 2 (bit5) 2 (bit6) 2 (bit7)
3 --- --- --- --- --­4 (bit0) 4 (bit1) 4 (bit2) 4 (bit3) 4 (bit4) 4 (bit5) 4 (bit6) 4 (bit7) 5 (bit0) --- --- --- --- ---
Sensor 3 Heating up Sensor 2 Heating up Sensor 1 Heating up
Exhaust Pressure 1 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
AFR 4 Heater Open Error
AFR 4 Heater Time-Out Error
AFR 4 Heater Short Error
AFR 4 Overtemp Error
AFR 5 Heater Open Error
AFR 5 Heater Time-Out Error
AFR 5 Heater Short Error
AFR 5 Overtemp Error
AFR 6 Heater Open Error
AFR 6 Heater Time-Out Error
AFR 6 Heater Short Error
AFR 6 Overtemp Error
UEGO Low Voltage Error
EBP sensor Error Low Volt
EBP sensor detected
--- --- --- --- ---
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
AFR 4 Ready
AFR 4 VM Error AFR 4 UN Error
AFR 4 IP Error
AFR 5 Ready
AFR 5 VM Error AFR 5 UN Error
AFR 5 IP Error
AFR 6 Ready
AFR 6 VM Error AFR 6 UN Error
AFR 6 IP Error
EBP sensor ready
CAN Config Mode CAN Config Mode CAN Config Mode CAN Config Mode
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 26
5 (bit1) 5 (bit2) --- --- --- --- --­5 (bit3) --- --- --- --- --­5 (bit4) --- --- --- --- --­5 (bit5) 5 (bit6) 5 (bit7)
6
7
Sensor 6 Heating up Sensor 5 Heating up Sensor 4 Heating up
Exhaust Pressure 2 16 bit unsigned .001 psig/bit 0 0 to 655.35 psig
--- --- --- --- ---
Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1 Boolean 0 = false, 1 = true 0 0/1
Page 27
12 MONTH LIMITED WARRANTY
Advanced Engine Management Inc. warrants to the consumer that all AEM High Performance products will be free from defects in material and workmanship for a period of twelve (12) months from date of the original purchase. Products that fail within this 12­month warranty period will be repaired or replaced at AEM’s option, when determined by AEM that th e product failed due to defects in material or workmanship. This warranty is limited to the repair or replacement of the AEM part. In no event shall this warranty exceed the original purchase price of the AEM part nor shall AEM be responsible for special, incidental or consequential damages or cost incurred due to the failure of this product. The Bosch LSU 4.2 UEGO sensor has a limited life and is not warranted. Warranty claims to AEM must be transportation prepaid and accompanied with dated proof of purchase. This warranty applies only to the original purchaser of product and is non-transferable. All implied warranties shall be limited in duration to the said 12 month warranty period. Improper use or installation, accident, abuse, unauthorized repairs or alterations voids this warranty. AEM disclaims any liability for consequential damages due to breach of any written or implied warranty on all products manufactured by AEM. Warranty returns will only be accepted by AEM when accompanied by a valid Return Goods Authorization (RGA) number. Product must be received by AEM within 30 days of the date the RGA is issued.
Please note that before AEM can issue an RGA for any product, it is first necessary for the installer or end user to contact the AEM Performance Electronics tech line at 1-800-423-0046 to discuss the problem. Most issues can be resolved over the phone. Under no circumstances should a system be returned or a RGA requested before the above process transpires.
Need additional help? Contact the AEM Performance Electronics tech department at 1-800-423-0046 or tech@aempower.com, or visit the AEM Performance Electronics forum at http://forum.aempower.com/forum/
Loading...