These instructions relate to the technical specifications of the
equipment at the time of publication. These instructions are a
component part of the system.
Legal claims arising from this contractual relationship shall only be
recognised by AEG Power Solutions GmbH subject to the terms
agreed under the warranty obligation in the main contract.
1.2 Appropriate Use
The compact station TKS-CS is designed for use in solar power
stations with one or two Protect PV inverters, in accordance with
IEC 62271-202. The compact station is intended for outdoor
installation.
An output-related transformer for electrical isolation and outputdependent medium-voltage switchgear for feeding into the local
medium-voltage mains are installed in the compact station.
The equipment may only be used for this purpose. Any other use
constitutes misuse and can endanger personal safety.
1.3 List of Abbreviations
Abbreviation Meaning
CS Compact Station
MH Metal Housing
Further information can be found in the Protect PV Inverter Operating
Instructions (BAL).
Page 6 of 39 8000043213 BAL
Compact Station TKS-CS - Operating Instructions
2 Safety
The qualified skilled personnel are responsible for safety.
The member of personnel who is responsible for the equipment
must ensure that only suitably qualified persons are allowed
access to the equipment.
To ensure safety in the electrical operating areas, these areas
should be lockable; i.e. suitable locking systems should be
installed by the owner on all exterior doors of the compact station.
2.1 Installation Location
The equipment is intended for use outdoors as an enclosed
electrical unit.
• Environmental conditions: ( technical data) in accordance
with DIN EN 60721-3-4.
• Freely accessible air vents for heat dissipation.
• Ground pressure: min. 250 kN/m
Refer to the technical data for additional criteria.
When selecting the installation location, regional regulations
governing noise emissions must be taken into account.
Do not install the equipment in areas subject to flooding or those
with a high groundwater level.
2
( excavation plan)
2.2 Lightning Protection
The connection to the potential equalisation system of the
foundation provides the equipment with effective protection against
lightning strikes.
The manufacturer’s specifications must be implemented effectively
in order to provide the photovoltaic system with suitable lightning
protection measures.
Further safety information can be found in the Protect PV Inverter Operating
Instructions (BAL).
8000043213 BAL Page 7 of 39
Compact Station TKS-CS - Operating Instructions
3 Scope of Delivery
Check that the following components have been delivered with the
equipment:
• 1x compact station TKS-CS inc.:
• Technical documents comprising:
Available to order
AEG Service can also provide the following documents:
• Spare parts list
• Service book
To place an order, please contact:
AEG Power Solutions GmbH
Emil-Siepmann-Strasse 32
59581 Warstein
Germany
+49 2902 763 100
Fax: +49 2902 763 645
E-mail:
Internet: http://www.aegps.com
− Transformer corresponding to nominal output
− Medium-voltage system corresponding to nominal output
− Low-voltage box
− Power supply and auxiliary power supply
− Technical data
− Installation and operating instructions
− Drawings/circuit diagrams
service.aegpss@aeg.com
Page 8 of 39 8000043213 BAL
Compact Station TKS-CS - Operating Instructions
4 Equipment Specifications
4.1 Structure
The compact station TKS-CS consists of a metal housing with a
detachable roof structure and a concrete base.
The concrete base comprises a warp-resistant foundation with an
oil and water-tight trough in the transformer compartment.
1 2 3
4 5 6 7 8 9
Figure 1 - Compact station TKS-CS
1 Transformer compartment
2 Roof structure
3 ISO small distribution box,
PV.LoG
4 MV branch - feed
5 MV switchgear
6 Wall structure
7 Concrete base
8 AC feed from MH
9 Low-voltage box
The wall and door structures are designed with double walls and
forced ventilation. An additional axial ventilator is installed in the
door of the transformer compartment for ventilation purposes.
8000043213 BAL Page 9 of 39
4.2 Dimensions
Compact Station TKS-CS - Operating Instructions
Figure 2 - Compact station side views
Dimension [mm]
Height of metal housing with roof 1686.5
4.3 Low-Voltage Box
Height of concrete base 780
MH depth (roof) 1750 (1804)
MH width (roof) 2900 (2954)
Table 1 - Dimensions
1 2 3 4 5 6 7
Figure 3 - Low-voltage box (example)
1 Central earthing system
2 Communications cabinet PV.LoG-MH
3 Load interrupter s witch, 3 -pin
4 LV connections with protective cover
Page 10 of 39 8000043213 BAL
5 ISO small distribution
box
6 Battery cabinet
7 Socket outlet with
earthing contact
4.3.1 AC Connections
Compact Station TKS-CS - Operating Instructions
The low-voltage box must remain closed during operation.
1 2 3 4 5 5 3
Figure 4 - Low-voltage boxes (example)
1 LV box for an MH
2 AC connection - 1Q0 with steel
sheet protective cover
3 Load interrupter switch
4 LV box for two MH
5 AC connection -1Q0/ 2Q 0 with
Makrolon protective cover
8000043213 BAL Page 11 of 39
Compact Station TKS-CS - Operating Instructions
4.3.2 ISO Small Distribution Box
1 2 3 4
5 6 5 7 8
Figure 5 - ISO small distribution box (example)
1 Cable duct (internal)
2 -F20 - FI switch 25 A
3 F21 - 27 miniature circuit
breakers
4 -4Q0 - motor protection switch
6 -F0 - fuse max. 20 A
Sub-distribution
7 -F1 - fuses max. 25 A
Auxiliary transformer
8 -F10 - overvoltage protection
Fan
5 -3Q0 - motor protection switch
Auxiliary transf or mer
Fuse
F21
F22
F23
F24
F25
F26
F27
-F0
16 A Socket outlet with earthing contac t
16 A Door contacts and lighting
6 A Medium-voltage tripping
16 A Power supply PV.LoG-MH
6 A Axial fan
16 A optional
16 A optional
20 A Sub-distribution supply
-F1
-F10
Table 2 - Fuses
25 A Auxiliary transformer
Overvoltage protection
Page 12 of 39 8000043213 BAL
Loading...
+ 27 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.