Advantech ADAM CPU 821 NET, ADAM CPU 821 DP, ADAM CPU 821 DPM, ADAM CPU 8214, ADAM CPU 8215 Series Manual

...
CPU ADAM 821x Chapter 1 Principles
Chapter 1 Principles
Outline
Contents
This introduction contains references on the handling and information about application areas and usage of the CPU modules.
It also provides certain suggestions on the approach when programming the module and the CPU specifications that are important in this respect.
Safety information for users
Construction and operation of the CPU 821x
Programming principles
Topic Page
Chapter 1 Principles ............................................................................... 1-1
Safety information for users................................................................... 1-2
Hints for the deployment of the MPI interface........................................ 1-3
Hints for the deployment of the Green Cable ........................................ 1-4
Overview System 82xx .......................................................................... 1-5
General description of the System 82xx................................................ 1-6
Overview CPU 821x .............................................................................. 1-7
Hints for project engineering.................................................................. 1-8
Application fields.................................................................................. 1-11
Features .............................................................................................. 1-12
Operating modes of a CPU.................................................................. 1-13
CPU 821x programs ............................................................................ 1-14
CPU 821x operands ............................................................................ 1-14
ADAM 8000 Manual CPU 821x – Rev 1.1 1-1
Chapter 1 Principles CPU ADAM 821x
Safety information for users
Handling of electrostatically sensitive modules
Shipping of modules
ADAM modules make use of highly integrated components in MOS­technology. These components are extremely sensitive to over-voltages that may occur during electrostatic discharges.
The following symbol is attached to modules that can be destroyed by electrostatic discharges:
The symbol is located on the module, the module rack or on packing material and it indicates the presence of electrostatically sensitive equipment.
It is possible that electrostatically sensitive equipment is destroyed by energies and voltages that are far less than the human threshold of perception. These voltages may occur where persons do not discharge themselves before handling electrostatically sensitive modules and they may damage components thereby causing the module to become inoperable or unusable. Modules that have been damaged by electrostatic discharge are usually not detected immediately. The respective failure may become apparent after a period of operation.
Components damaged by electrostatic discharges can fail after a temperature change, mechanical shock or changes in the electrical load.
Only the consistent implementation of protective devices and meticulous attention to the applicable rules and regulations for handling the respective equipment is able to prevent failures of electrostatically sensitive modules.
Please ship the modules exclusively in the original packing material.
Measurements and alterations on electrostatically sensitive modules
1-2 ADAM 8000 Manual CPU 821x – Rev 1.1
When you are conducting measurements on electrostatically sensitive modules you should take the following precautions:
Floating instruments must be discharged before use.
Instruments must be grounded.
You should only use soldering irons with grounded tips when you are making modifications on electrostatically sensitive modules.
Attention!
Personnel and instruments should be grounded when working on electrostatically sensitive modules.
CPU ADAM 821x Chapter 1 Principles
Hints for the deployment of the MPI interface
2
What is MP
I?
Deployment as MP interface
The MP
2
I jack combines 2 interfaces in 1:
MP interface
RS232 interface
Please regard that the RS232 functionality is only available by using the Green Cable from Advantech.
The MP interface provides the data transfer between CPUs and PCs. In a bus communication you may transfer programs and data between the CPUs interconnected via MPI.
Connecting a common MPI cable, the MPI jack supports the full MPI functionality.
Important notes for the deployment of MPI cables!
Deploying MPI cables at the ADAM CPUs from Advantech, you have to make sure that Pin 1 is not connected. This may cause transfer problems and in some cases damage the CPU!
Especially Profibus cables from Siemens, like e.g. the 6XV1 830-1CH30, must not be deployed at MP
2
I jack.
For damages caused by nonobservance of these notes and at improper deployment, ADAM does not take liability!
Deployment as RS232 interface only via "Green Cable"
For the serial data transfer from your PC, you normally need a MPI transducer. Fortunately you may also use the "Green Cable" from Advantech You can order this under the order no. ADAM-8950-0KB00.
The "Green Cable" supports a serial point-to-point connection for data transfer via the MP
2
I jack exclusively for ADAM 8xxx CPUs.
Please regard the hints for the deployment of the "Green Cable" on the following page.
ADAM 8000 Manual CPU 821x – Rev 1.1 1-3
Chapter 1 Principles CPU ADAM 821x
Hints for the deployment of the Green Cable
What is the Green Cable?
The Green Cable is a green connection cable, manufactured exclusively for the deployment at ADAM System components.
The Green Cable is a programming and download cable for ADM CPUs 8xxx and ADAM fieldbus masters. The Green Cable from Advantech is available under the order no. ADAM-8950-0KB00.
The Green Cable allows you to:
transfer projects serial Avoiding high hardware needs (MPI transducer, etc.) you may realize a serial point-to-point connection via the Green Cable and the MP This allows you to connect components to your ADAM CPU that are able to communicate serial via an MPI adapter like e.g. a visualization system.
execute firmware updates of the CPUs and fieldbus masters Via the Green Cable and an upload application you may update the firmware of all recent CPUs 8xxx and certain fieldbus masters (see Note).
Important notes for the deployment of the Green Cable
Nonobservance of the following notes may cause damages on system components.
For damages caused by nonobservance of the following notes and at improper deployment, Advantech does not take liability!
2
I jack.
Note to the application area
The Green Cable may exclusively deployed directly
1-4 ADAM 8000 Manual CPU 821x – Rev 1.1
of the ADAM components (in between plugs are not permitted). At this time, the following components support the Green Cable: CPUs 8xxx and the fieldbus masters ADAM 8208-1xx01 from Advantech.
Note to the lengthening
The lengthening of the Green Cable with another Green Cable res. The combination with further MPI cables is not permitted and causes damages of the connected components!
The Green Cable may only be lengthened with a 1:1 cable (all 9 Pins are connected 1:1).
at the concerning jacks
CPU ADAM 821x Chapter 1 Principles
Overview System 82xx
The System 82xx
The System 82xx is a modular automation system for low and middle range of performance that you may use either centralized or decentralized. The single modules are directly clipped to a 35mm DIN rail and are connected together with the help of special bus clips.
The following picture shows the range of performance of the System82xx:
System 8000
decentral
DP 8xxx
Profibus DeviceNet CAN Interbus PC-CPU PLC-CPU
on demand
on demand
PC 8xxx
central
PLC 8xxx
for STEP®7 of Siemens
Overview Manuals
peripheral
Dig. IN / Dig. OUT / Anal. IN / Anal. OUT / FM / CP
The current manual describes the PLC-CPU family CPU 821x compatible to
STEP
The peripheral modules, PCs and decentralized peripheral equipment are to find in the manual HB97 "System82xx". This manual also contains hints for installation and commissioning of the System82xx.
7 by Siemens.
ADAM 8000 Manual CPU 821x – Rev 1.1 1-5