Advanced Protection XRL User Manual [en, es]

ENGLISH
TEXA, TEXB, TEXR, TEXW
Series
Surge Protective Device (SPD)
Installation, Operation
& Maintenance Manual
WARNING – IMPORTANT – PLEASE READ – WARNING
Safety First – Hazardous Voltage & Shock Hazard
• Only qualied licensed electricians should install or service SPDs
• Hazardous voltages exist within SPDs
• SPDs should never be installed or serviced when energized
• Use appropriate safety precautions including Personal Protection Equipment
• Failure to follow these instructions can result in death, serious injury, and/or equipment damage
• This manual shall be read in its entirety prior to installing
V
Bonding and Grounding Hazard
Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electric Code (NEC®) and all applicable codes.
Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC® and all applicable codes.
During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, inspected and tested. All conductors must be connected and functional including the neutral (if required).
The voltage rating of the SPD and system must be veried
before energizing the SPD.
Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if
the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC®.
Do Not Hi-Pot Test SPDs
Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-potential testing and then reconnected after test completion.
Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void the warranty.
14550 58th Street North
(800) 237-4567·(727) 535-6339 · Fax (727) 539-8955
UL is a registered trademark of Underwriters Laboratories, NEC® and National Electrical Code are registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002, C62.45-2002, C62.72-2007 are registered trademarks of IEEE.
www.aptsurge.com · info@apttvss.com
Clearwater, Florida 33760
·
European Authorized Representative
Obelis s.a.
Boulevard Général Wahis 53
1030 Brussels, BELGIUM
Tel: +(32) 2. 732.59.54 Fax: +(32) 2. 732.60.03 E-Mail: mail@obelis.net
01.24.13.lh #8169
INTRODUCTION
Thank you for choosing an APT Surge Protective Device (SPD). This is a high quality, high energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages.
Proper installation is important to maximize performance. Please follow steps outlined herein.
This entire Operation & Maintenance Manual should be read prior to beginning installation. These instructions are not intended to replace national or local codes. Follow all applicable electrical codes to ensure compliance. Installation of this SPD should only be performed by
qualied electrical personnel.
APT SPDs are extensively tested in accordance with industry standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62, C62.72, UL 1449, UL 1283, IEC 61643, etc.
This SPD is a single-port parallel-connected device intended for service entrance, panelboard or downstream installation for IEEE Category C, B or A applications.
Major Industry Nomenclature Changes Effective 2008-2009
Be aware that UL 1449 Third Edition and 2008 NEC® Article 285 generated substantial changes.
The term TVSS changed to SPD Types 1, 2, 3 & 4 SPDs are created UL 1449 clamping voltage performance testing
changed from 500A to 3,000A
UL 1449 added new I nominal testing (I
consists of more rigorous duty-cycle testing
Figure 1
(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B & A)
This SPD complies with the latest regulatory actions and is UL Listed as such.
For further information, please review latest editions of NEC® Article 285, UL 1449 or contact APT Tech Support at (800) 237-4567.
GENERAL INFORMATION
Product Family Outline
XA – Single Module in enclosure XB – Two Modules in enclosure XR – Single small module for integration by OEM XW – Single large module for integration by OEM
2
NEC® Article 285 & UL 1449-3
SPD Types: Types 1, 2, 3, & 4
Based on Location within electrical distribution system
), which
n
Each is available with an ‘S’ or ‘L’ sufx, which designate
Standard modes (most common) or discrete 10-modes
(specic application) respectively. For example, XAS is SPD
in enclosure with Standard modes of protection; XRL is SPD without enclosure to go inside host gear having discrete ten mode protection.
XR & XW versions without enclosures are available for internal mounting within electrical gear. The XR version is rated 100-300kA. The XW version is rated 300-500kA. Both are available with S or L designations.
The XA & XB families are intended for use as a Type 1 external mount SPD. XR and XW families are Type 4 SPDs intended for Type 1 applications. See Model Number Decoder in Table 1.
Type 1 SPD
Type 1 SPDs include internal overcurrent protection and have been evaluated by UL to more stringent requirements. Type 1 SPDs are suitable for installation on the line side or load side of the service disconnect overcurrent device. Type 1 SPDs may be used in Type 2 applications.
Internal Protection
This device features internal overcurrent and overtemperature protection that will disconnect effected surge suppression components at the end of their useful life, but will maintain power to the load – now unprotected. If this situation is undesirable for the application, follow these instructions for servicing or replacing the device.
Service Guidelines
Service of this unit consists of replacing the internal module(s), disconnect switch (if equipped) and/or display assembly.
There are no user-serviceable parts inside the replaceable module. Do not attempt to disassemble the module as it stores charge.
Simplied Explanation of Operation
SPDs sense overvoltage and create a momentary short circuit to redirect harmful surge energy. SPDs reset automatically and wait for the next surge. This is similar to the pressure relief valve on a water heater: pressure goes up, valve opens to relieve pressure and then resets. In an electrical system, an SPD senses overvoltage, shorts temporarily, which equalizes damaging voltages and then resets. SPDs are capable of repeating this function thousands of times.
Parallel Connection
This is a Parallel connected SPD – not series connected. As outlined above, an SPD ‘drains off’ excessive voltage from an electrical system. Because of parallel connection, installation of the SPD anywhere near the equipment to be
protected is satisfactory. This effect is similar to ushing
any toilet in a house; pressure in the shower goes down. In an electrical system, a parallel connected SPD will remove excessive voltage off the entire system (assuming reasonable proximity).
Tip: It is very important that wiring leads be congured as short
& straight as possible. Avoid long leads. Avoid sharp bends. Route SPD conductors in the same conduit. Leads do not have to be sized for the entire load – this SPD is parallel connected,
not series connected. As a generalization, 6 AWG works ne.
Do not create model numbers from this chart as all features are not available on all models
TABLE 1: MODEL NUMBER DECODER
Transient Eliminator
Voltage Code for Electrical System Model Family Options
Common North American Systems: 01 = 240/120V Split Phase - 1Ø, 3W+Grnd, (Fig 1) 02 = 208Y/120V Wye - 3Ø 4W+Grnd, (Fig 2) 03 = 240/120V High Leg Delta (B High), (Fig 3) 04 = 480Y/277V Wye - 3Ø 4W+Grnd, (Fig 2) 05 = 480V Delta - 3Ø 3W+Grnd, (Fig4) & HRG Wye 08 = 600Y/347V Wye - 3Ø 4W+Grnd, (Fig2)
Other Available Systems - Conrmation encouraged:
15 = 254/127V Split Phase - 1Ø 3W+Grnd, (Fig 1) 18 = 480/240V Split Phase, or Two legs of Wye, (Call) 21 = 220Y/127V Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300V Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240V Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230V Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250V Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 06 = 240V Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 07 = 380Y/220V Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600V Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye
(Available: 100kA, 150kA, 200kA, 250kA)
91 = 600V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
(Available: 100kA, 150kA, 200kA, 250kA) 11 = 120V Single Phase (Fig 5) 12 = 240V Single Phase (Fig 5) - Not split phase 13 = 127V Single Phase (Fig 5) 14 = 300V Single Phase (Fig 5) 16 = 277V Single Phase (Fig 5) 17 = 480V Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5)
TE 02 XAS 20 E1 XD
XAS = External Mount SPD
Standard Modes
XAL = External Mount SPD
10 Mode
XBS = External Mount SPD
Two Modules Standard mode
XBL = External Mount SPD
Two Modules
10 Mode For Internal Mount (No Enclosures):
XRS = Component SPD,
UL Recognized
Standard Modes XRL = Component SPD,
UL Recognized
10 Modes XWS = Component SPD,
UL Recognized
Standard Modes
XWL = Component SPD,
UL Recognized
10 Modes
Surge Current Rating
10 = 100kA/Phase 15 = 150kA/Phase 20 = 200kA/Phase 25 = 250kA/Phase 30 = 300kA/Phase 31 = 300kA/Phase 40 = 400kA/Phase 45 = 450kA/Phase 50 = 500kA/Phase 60 = 600kA/Phase 80 = 800kA/Phase 90 = 900kA/Phase 1K = 1000kA/Phase
X = Surge Counter, six-digit LCD counter
includes maintenance-free Eprom memory backup
Z = Surge Counter, plus External Surge
Counter Signal
E = Remote Locatable Display on 6 ft Cable
custom cable lengths available M = Mount Display on SPD instead of cable F = Noise Filtering - Extended Range &
Attenuation D = Rotary Disconnect Switch
Bussman, UL98 T = Thru-door Rotary Disconnect Switch
Bussman, UL 98, NEMA 1/12/3R only K = Rotary Disconnect Switch
Katco, UL 508 S = Thru-door Rotary Disconnect Switch
Katco, UL 508, NEMA 1/12/4 only
Delete Options L = Delete L-N Protection (reduces kA rating) G = Delete L-G Protection (reduces kA rating) N = Delete N-G Protection (reduces kA rating) J = Delete Noise Filter
Enclosure Rating
E1 = NEMA 1/12/3R/4 4X = NEMA 4X Non-Metallic 4S = NEMA 4X Stainless Steel FM = NEMA 1 Flush Mount P1 = NEMA 1 pullbox ‘indoor'
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6
Phase A (BLK)
Phase B (BLK)
B
A
Neutral (WHT)
N
V
}
Phase C (BLK)
C
Ground (GRN)
WYE 3 Hots, 1 Neu, 1 Grnd
TYPICAL PARALLEL
ELECTRICAL PANEL
BC
Advanced Protection Technologies
Phase A
Surge Counter
Phase B
Phase C
Service
GN
Silence
TestCountReset
Figure 2
To Protected Loads
Hot (BLK)
V
}
Neutral (WHT)
}
V
Hot (BLK)
Ground (GRN)
SPLIT 2 Hots, 1 Neu, 1 Grnd
CONNECTED SPD ON
A
BREAKER
Phase A (BLK)
Phase B (ORNG)
V
}
Phase C (BLK)
Neutral (WHT) Ground (GRN)
HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd
Phase A (BLK)
V
}
Phase B (BLK)
Phase C (BLK)
Ground (GRN)
DELTA & HRG WYE 3 Hots, 1 Grnd
V
}
SINGLE POLE 1 Hot, 1 Neu, 1 Grnd
Precautionary Statement Regarding SPDs on Ungrounded Systems
Caution – Ungrounded systems are inherently unstable and can produce excessively high line-to-ground voltages during certain fault conditions. During these fault conditions, any electrical equipment including an SPD, may be subjected to voltages which exceed their designed ratings. This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system.
Cascade Surge Protection
For optimum surge protection, cascade or staged surge suppression should be implemented at the service entrance and downstream locations as appropriate. Known or expected surge sources, as well as sensitive loads, should also have localized surge suppression. For interconnected electronic loads (data cabling), SPDs should also be utilized to protect the devices on either end of the interconnecting data cables.
Hot (BLK)
Neutral (WHT)
Ground (GRN)
Phase A (BLK)
V
}
Phase C (BLK)
Ground (GRN)
CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd
3
Unpacking & Preliminary Inspection
Inspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect the unit for any obvious shipping damages.
If any damage was found and is a result of shipping
or handling, immediately le a claim with the shipping
company and forward a copy to APT.
Storage Environment
This SPD should be stored in a clean, dry environment. Storage temperature range is -40°C (-40°F) to +60°C (+140°F). Avoid exposure to high condensation.
PRE-INSTALLATION & INSTALLATION PLANNING
Operating Environment
The standard unit uses a Type 1/12/3R/4 enclosure. Non-metallic polycarbonate 4X, stainless steel and Type
1 ush-mount or pull box enclosures are available as
options. Before installing, ensure that your enclosure type and application are appropriate per NEMA 250 with regard
to moisture, dirt, excessive dust, ammable materials or
atmospheres, corrosive vapors, etc. Please consult factory if enclosure needs to be changed.
This SPD is designed in an ambient temperature range of -40°C (-40°F) to +60°C (+140°F) with a relative humidity of 0% to 95% (non-condensing). Excessive temperature may inadvertently operate internal thermal overtemperature protectors.
On rare occasions in high temperature climates, SPDs inside clear cover polycabonate enclosures have experienced internal temperatures exceeding 200°F (94°C). We recommend positioning the unit so that the clear front avoids direct summer sunlight by shading or not facing west.
Line Side versus Load Side Installation
The XA & XB family SPDs are tested and qualied as
Type 1 SPDs per UL 1449 Third Edition and 2008 NEC®. This SPD can be installed on the Line Side of the service overcurrent device per 2008 NEC® Article 285. Type 1 SPDs may also be installed in Type 2 applications. As a generalization, it is more practical to install as Type 2 on load side of main overcurrent device for maintenance reasons. Such installations would be similar to traditional TVSS installations. (Note: cUL models are Type 2 due to different cUL criteria.)
XR and XW SPD modules are Type 4 components that have been evaluated by UL for use in Type 1 applications. (XR’s and XW’s are essentially XA’s without enclosures for installation within host electrical equipment.)
There may be circumstances where Line Side installation is desirable. Follow all applicable Code requirements for Line Side installation. We generally recommend that the SPD be installed with a disconnecting mechanism for servicing purposes.
Tip: APT offers an optional Disconnect Switch that has been UL evaluated as part of the SPD. This includes SCCR and Line Side suitability. If you do not use the APT Disconnect option, select a disconnect switch rated for line side (UL
98) having appropriate SCCR rating including any required
overcurrent protection. This may be more time consuming and expensive than anticipated. The optional Disconnect Switch is fully engineered and almost certainly easier, smaller and less expensive. Please contact APT Technical Support as appropriate.
Audible Noise
SPD background noise is negligible or non-existent, and does not restrict the location of installation.
Mounting, Dimensions, and Weight
The XA & XB series include enclosures and are intended for wall mounting. The XR & XW series are component SPDs intended for installation within other electrical gear already having enclosures. See Table 2. Mechanical drawings are included in back of this manual (page 12).
TABLE 2: DIMENSIONS & WEIGHTS
XA H/W/D (in. / mm.) Weight
Standard (and w/ Opt. Disc. Switch
& <300kA)
With Opt. Disc.
Switch & >300kA
4X Non-Metallic
(std.)
(>300kA w/disc.)
4X Stainless
(>300kA w/disc.)
Pullbox & Flush
mount
(>300kA w/disc.)
12"x12"x6.5"
(305x305x165)
16"x14"x6.5"
(406x356x165)
14"x12"x7" (356x305x178) 16"x14"x7" (406x356x178)
12"x12"x7.5"
(305x305x191)
16"x14"x7.5"
(406x356x191)
12"x12"x6" (305x305x152) 16"x14"x6" (406x356x152)
23 lbs
(10.4 kg)
32 lbs
(14.5 kg)
14 lbs (6.4) 21 lbs (9.5)
24 lbs (10.9)
33 lbs (15)
21 lbs (9.5)
29 lbs (13.2)
XB H/W/D (in. / mm.) Weight
Standard
(includes Disc.
Switch)
4X Non-Metallic
4X Stainless
Pullbox & Flush
mount
20" x 20" x 7.5"
(508 x 508 x 191)
24" x 24" x 8"
(610 x 610 x 203)
20" x 20" x 7.5"
(508 x 508 x 191)
20" x 20" x 6"
(508 x 508 x 152)
52 lbs
(23.6 kg)
52 lbs
(23.6 kg)
53 lbs
(24 kg)
43 lbs
(19.5 kg)
XR H/W/D (in. / mm.) Weight
Standard
With Opt. Disc.
Switch on alum.
backplane
6.5" x 11" x 4.5"
(165 x 279 x 114)
10.75" x 10.88" 4.5" (273 x 276 x 114)
5 lbs
(2.3 kg)
9 lbs
(4.1 kg)
XW H/W/D (in. / mm.) Weight
Standard
With Opt. Disc.
Switch on alum.
backplane
9" X 11" X 4.5"
(229 x 279 x 114)
14.75" X 12.9" X 5.25" (375 x 328 x 133)
Service Clearance
Service clearance is needed at the front of the unit; 36 inches minimum is the required distance for clearance pursuant to the NEC®.
Lead Lengths & Maximizing SPD Performance SPDs must be located as close to the circuit as possible to minimize parasitic losses. Surges are high current, high frequency events that cause substantial voltage drops across conductors. This hurts SPD performance. Use the shortest & straightest possible leads. Pre-Plan installations
7 lbs
(3.2 kg)
11 lbs (5 kg)
4
and ensure that nearest breaker positions are used. If new construction, adjust breaker locations as appropriate.
Tip: Voltage drops for normal 120V or 277V lines might be 2-3V per hundred feet. In surge applications, voltage drops might be 100-150V per foot. These voltage drops add to clamping voltage, thus hurting performance. Make every effort to keep leads short and straight.
As distribution gear becomes larger, shorter leads are more
difcult to accomplish. When longer leads are unavoidable,
gently twist leads together (one to two twists per foot), or tie-wrap leads together.
Tip: surges create magnetic elds per the ‘right-hand rule’. When current goes in direction of thumb, magnetic eld is in direction of curl of ngers. As surge current goes to SPD, elds are created in one direction. When the SPD sends those
currents to neutral and/or ground, current goes in the opposite direction. If ‘coming & going’ are on the same axis, the magnetic
elds can be cancelled, thus avoiding performance decrease.
Gentle twists, bundling & tie-wraps accomplish this.
Shortest Leads Possible
Leads must be as short and straight as possible -
See NEC® Art. 285.12
Pretend wire is $1000 per foot coming out of your pocket. No long leads No sharp bends No wire nuts How short is short enough? As short as you can make it. How long is too long? If anyone else can make it shorter.
Overcurrent Protection
SPDs draw very little current under normal conditions and conduct for a brief duration upon encountering a transient surge current. This SPD contains internal overcurrent and overtemperature protection to protect against abnormal voltage conditions.
Supplemental overcurrent protection is not required to protect this SPD. However, connecting conductors require protection in Type 2 or 4 applications. Follow applicable codes.
Voltage Rating
Before installing SPD, verify that it has the same voltage rating as the power distribution system. Compare the SPDs nameplate voltage or model number and ensure that SPD
conguration matches the intended power source. See Table 1.
The specier or the user of the device should be familiar with the conguration and arrangement of the power distribution
system in which any SPD is to be installed. The system
conguration of any power distribution system is based strictly
on how the secondary windings of the transformer supplying
the service entrance main or load are congured. This includes
whether or not the transformer windings are referenced to
earth via a grounding conductor. The system conguration is not based on how any specic load or equipment is connected
to a particular power distribution system.
480V System Example: SPDs should be installed per the electrical system, not per a load or motor’s wiring connection. For example, a 480V three phase motor might appear to be connected as a 480V Delta. In actuality, the serving distribution system might be a 480Y/277V grounded Wye, with or without a neutral pulled to the motor or MCC. The system is still a 480Y/277V Wye, even though the load
is connected as a Delta. A grounded Wye has a dened
reference to ground (i.e., neutral is bonded to ground).
Some Delta systems are ungrounded, which have no reference to ground and are known to become unstable in certain situations. Such instability can cause line to ground
voltage uctuations that may prematurely fail SPDs. For this
reason, the NEC® Article 285 has placed SPD restrictions on ungrounded systems. As generalizations, SPDs for ungrounded systems can be installed on grounded systems with a clamping performance penalty. However, SPDs for grounded systems installed on ungrounded systems are almost certainly destined for premature failure. Call APT Tech Support at (800) 237-4567 for further information.
Circuit Breaker and Disconnect Switch
The XA & XB family SPDs are tested and qualied as a Type
1 SPD per UL 1449 Third Edition and 2008 NEC®. This SPD can be installed on the line side of the service overcurrent device per 2008 NEC® Article 285. As a generalization, it is more practical to install on load side of main overcurrent device for maintenance reasons.
When connected on load side of main disconnect, we suggest connecting via a 60A circuit breaker. The circuit breaker is the intended disconnect switch and provides short circuit protection to the connecting conductors. These SPDs have internal overload protection elements within the product. A breaker or disconnect is not required for the SPDs overcurrent protection. These SPDs have demonstrated 200kA Short Circuit Current Ratings (SCCRs). 120V & 120/240V models have demonstrated 100kA SCCRs. Refer to label on unit.
Terminals
Terminals will accept 14 - 2 AWG conductor and are provided for line (phase), neutral (if used), and equipment safety ground connections. 8 AWG is the minimum recommended wire size because UL testing and evaluation was performed using 8 AWG.
Wire Size and Installation Torque
This is a parallel-connected SPD; it is not series-connected. The size of the SPD wiring is independent of the ampere rating of the protected circuit. Recommended wire is 6 AWG for phase, neutral and ground connections. Torque connections to 18 inch-pounds. Conductor length should be as short as possible.
If other wire sizes are used, we recommend that all conductors be the same gauge. Note that larger conductor
might appear to be benecial. However, large conductor
tends to have the same inductance as smaller conductor, thus netting limited improvement in exchange for being more
difcult to work with. Terminals accept 14 - 2 AWG conductor
with 6 AWG being preferred. Coordinate conductor size and overcurrent protection per applicable codes.
If equipped, Disconnect Switch will accept 6 AWG to 1/0 AWG, with 6 AWG preferred. Torque connections to 18 inch-pounds. Do Not overtorque connections on Disconnect Switch as it Will Break the Disconnect Switch and will not be covered by warranty.
System Grounding
An equipment grounding conductor must be used on all electrical circuits connected to the SPD.
For the best performance, use a single point ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes, building steel, metal water pipes, driven rods, etc. (for reference see: IEEE Std 142-2007).
5
For sensitive electronics and computer systems, we recommend that the ground impedance measurement be as low as possible. When metallic raceway is used as an additional grounding conductor, an insulated grounding conductor should be run inside the raceway and sized per the NEC®. Adequate electrical continuity must be maintained at all raceway connections. Do not use isolating bushings to interrupt a metallic raceway run.
A separate isolated ground for the SPD is NOT recommended. Proper equipment connections to grounding system and
ground grid continuity should be veried via inspections and
testing on a regular basis as part of a comprehensive electrical maintenance program.
On 4-Wire Power Systems, neutral to ground bonding (Main Bonding Jumper) must be installed per the NEC®. Failure to do so WILL damage SPDs.
Internal Mounting of XR and XW Component SPD
XR’s and XW’s are essentially XA’s without enclosures. XR’s and XW’s are intended for installation within host electrical equipment having suitable enclosures.
The experienced integrator will appreciate the simplicity of XR/XW. XR/XW’s are Type 4 SPDs and have been evaluated by UL for use as Type 1 (or Type 2) SPDs when installed in appropriate enclosures. All UL required safety testing is complete without needing additional
safety apparatus. Contact factory for UL le Engineering
Considerations. Mount SPD in appropriate enclosure, mount Diagnostic Display in appropriate location and follow appropriate instructions, including short leads. UL evaluation within your completed product should be easy and trouble free. Do not Hi-Pot test with SPD in circuit.
In many instances, a disconnecting means is appropriate for future service. A breaker serves this function, as well as provides overcurrent protection to the connecting conductors. If a breaker or optional Disconnect Switch are not used, consider a disconnect or safety switch having appropriate SCCR rating including any required overcurrent protection. Line side is likely to require a UL 98 switch where load side is likely to require a UL 508 (or UL 98) switch. This may be more time consuming, more expensive and physically larger than anticipated. APT offers an optional Disconnect Switch that has been UL evaluated as part of the SPD. The optional Disconnect Switch is fully engineered and almost certainly easier, smaller and less expensive. Please contact APT Technical Support as appropriate.
Mounting Diagnostic Display: Mount the Display in a user-friendly location, with consideration to weather and vandalism. Dimensions are in Figure 4 (page 7). A Display with a 6’ connector cable is typically included. Longer lengths are available. The Display is also mountable directly on the XR/XW module (shorter cables required). The standard Display includes mounting thru-holes and is not weather resistant. Contact factory for weather resistant NEMA 4 rated Display (with mounting studs instead of thru-holes and label
material including UL 746C(f1) & UL 94-5VA ame rating).
UL 1283 required language concerning the installation of EMI Filters a) An insulated grounding conductor that is identical in size
and insulation material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green with or without one or more yellow stripes, is to be installed
as part of the circuit that supplies the lter. Reference should
be made to Table 250-122 of the National Electrical Code regarding the appropriate size of the grounding conductor.
b) The grounding conductor mentioned in item a is to be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure.
c) Any attachment-plug receptacles in the vicinity of the
lter are to be of a grounding type, and the grounding
conductors serving these receptacles are to be connected to earth ground at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure.
d) Pressure terminal or pressure splicing connectors and
soldering lugs used in the installation of the lter shall be identied as being suitable for the material of the conductors.
Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs
between dissimilar conductors unless the device is identied
for the purpose and conditions of use.
Optional Flush Mount Installation Considerations
The XA & XB are approximately 6” deep. The unit will not
mount ush unless there is at least 6” of depth clearance. The XA & XB are not designed to mount ush on a typical
2 x 4 stud wall.
Back Flange Mounting: Mount as close as possible to protected panel. Create a wall opening slightly larger than
SPD. See Figure 4. Congure a robust backing plate inside
Figure 3
6
FLUSH MOUNT INSTALLATION
STEP 1:
Prepare Wall
- Must support 25-55lbs
Cutout slightly larger than SPD base
Mounting Plate 6 1/16” from outside of front wall
STEP 2:
Mount SPD
STEP 3:
Install Flush Mount Plate & Cover
the wall cavity 6 1/16” from the wall face such that the SPD
0.000
0.000
1.384
1.699
2.014
2.329
3.437
0.951
4.618
0.559
0.250
4.875
0.250
3.690
0.180 THRU 4 PL.
R0.375 4 PL.
Count Reset
3.963
1.798
2.861
CLEAR WINDOW TYP.
Phase C
Service
Phase B
Phase A
Test
Silence
Surge Counter
0.497
0.654
1.324
1.994
Ø.50 BLACK BORDER TYP.
1.660
BLACK LETTERS (SURGE COUNTER) BACKGROUND TO BE PANTONE 441C
RED LETTERS (ALARM SILENCE ONLY) PANTONE 185C
BACKGROUND TO BE PANTONE 445C
PANTONE 441C 4 PLACES
R0.062 4 PL.
BLACK BORDER
2.999
2.077
2.737
2.545
2.269
0.125 TRANSLUCENT WINDOW 5 PL.
is supported from its back. Note the mounting holes on the
back ange. Also note that the SPD weighs 22-52 lbs. Be
careful not to drop the SPD into the wall.
Disconnect Switch (Opt. on XA, Std. on XB)
The disconnect switch provides manual disconnection means for phase conductors and the neutral conductor. Ground is not switched.
Special care should be taken while pre-planning installation to ensure that leads are as short as possible. Most XA’s & XB’s in ‘square’ enclosures have backplanes that can be removed and repositioned to reduce leads. See Figure 8. (Models with rectangular enclosures may be repositioned by inverting only.) (Excludes thru-door handle options.)
There is limited working space around the Disconnect Switch. This is a consequence of reducing internal size and lead lengths. Please be patient.
Disconnect switch will accept 6 AWG to 1/0 AWG, with 6 AWG preferred. Torque connections to 18 inch-pounds. OVER-TORQUING connections WILL BREAK the Disconnect Switch and will not be covered by warranty.
The disconnect switch is mounted on DIN-rail. It may be removed by gently pulling out the mounting tab at the bottom of the switch assembly.
APT is one of few SPD manufacturers that make Disconnect
Switches available as a fully UL qualied option. The Disconnect Switch was included during UL certication
and testing. The Short Circuit Current Rating posted on the UL label of the SPD includes the Disconnect Switch and supersedes any rating on the individual Disconnect Switch. When used in a Type 1 line-side application, the SPD including its Disconnect Switch has been UL tested and approved. Further evaluation is not required by UL, nor is a separate UL 98 rated switch required.
Module Rotation Feature
Installation lead wire length must be minimized because longer leads hurt performance. Lead length may be reduced by rotating the module inside the enclosure. SPD ships with terminals pointing down. If installation lends itself toward other orientation, the module’s aluminum backplane can be unscrewed and reoriented. For example, if leads enter from top, rotate module assembly such that leads are shortest. Be careful with ribbon cable connector and take care to retighten screws & secure ribbon cable. Mounting screws are in four corners. Rectangular enclosures may be rotated up or down only. See Figure 5.
Figure 5
ROTATING MODULE
DESIGN ALLOWS FOR
SHORTER LEADS
Diagnostic Cable Connector
Mounting Screws in Corners
Figure 4
INTERNAL MOUNT
DISPLAY DIMENSIONS
7
INSTALLATION
Pre-Plan your installation. You will need to accomplish the following:
Meet all National and Local codes. (NEC
®
Article 285 addresses SPDs)
Mount SPD as close to panel or equipment as possible to keep leads short. Ensure leads are as short and straight as possible, including neutral and ground.
Consider a breaker position that is closest to the SPD and the panel’s neutral & ground.
Suggested breaker & conductor size is 60A-30A with 6 AWG. Make sure system is grounded per NEC
®
and clear of faults before energizing SPD.
Certain options or implementations require extra consideration. See appropriate sections
within this manual:
Line Side Installation (page 4) Internal or Integral Mount Installation inside electrical gear (page 7) Disconnect Switch Option (page 7) Flush Mount Option (page 6) Retro-t where no breaker positions are available (page 11) UL/NEMA 3R Drain Holes (page 10)
1. Use a voltmeter to check all voltages to ensure correct SPD.
2. If SPD has Dry Contact, Remote Monitoring or Remote Display, pre-plan their installation.
3. Remove power for panel. Conrm panel is deenergized.
4. Identify connection/breaker location and SPD location.
5. Make sure leads are short. Reducing inches matters. Pretend that connector leads cost you $1000/foot to make leads short!
Installation Tips: SPD module is mounted on backplane within its enclosure. In many cases, the backplane assembly can be unbolted and rotated in two or four directions to yield shortest leads. See Fig 8. Carefully disconnect ribbon
cable(s) and unbolt backplane assembly. Various congurations have limited work space. Please be patient. Installation
may be easier if disconnect switch is temporarily removed from DIN-rail, or module/backplane is temporarily removed.
6. Remove an appropriately sized knockout from panel. Create an appropriately sized and lo­cated hole in the SPD enclosure.
7. Mount SPD. Connect to equipment using an approved wiring method, including seals appropriate for the enclosure rating. Carefully reinstall backplane or disconnect switch as appropriate.
8. Connect conductors as appropriate – short and straight as possible (Note that Hi-Legs are Phase B).
9. Label or mark conductors as appropriate (neutral: white, ground: green, energized: black, hi-leg: orange).
10. Make sure system is bonded per NEC® and is clear of hazards or faults before energizing (N-G bonding not per NEC® will fail SPDs: #1 cause of SPD failures).
11. Energize and conrm proper operation of indicators and/or options. If Red LED ashes & Audible Alarm cycles, deenergize immediately and call for help.
Figure 6
To Protected Loads
8
TYPICAL PANEL INSTALLATION
BC
A
BREAKER
Advanced Protection Technologies
Phase A
Surge Counter
Phase B
Phase C
Service
GN
Silence
Test CountReset
Use closest breaker to SPD Locate SPD close to intended breaker
Keep Leads Short as Possible Avoid Sharp Bends
Outdoor installation requires appropri-
ate weather sealing at nipple (o-ring, sealing condulet, etc.)
}
}
Figure 7
C
Advanced Protection Technologies, Inc.
Clearwater, Florida
Listed
56E3
TVSS
U
R
L
N
CAUTION
G
A
TWO POLE
2
1
3
46
5
7
8
Advanced Protection Technologies, Inc.
Clearwater, Florida
Listed
56E3
U
R
L
G
CAUTION
CB NA
THREE POLE W/ DS
N
CAUTION
B
N
CAUTION
BA
ELECTRICAL DRAWINGS FOR CUSTOMER CONNECTIONS
SINGLE POLE
Advanced Protection Technologies, Inc.
Clearwater, Florida
56E3
Listed
U
R
L
B
G
THREE POLE
Advanced Protection Technologies, Inc.
Clearwater, Florida
56E3
Listed
U
R
L
C
BA
G
Hot (BLK)
V
}
Neutral (WHT)
}
V
Hot (BLK)
Ground (GRN)
SPLIT 2 Hots, 1 Neu, 1 Grnd
CAUTION
N
CAUTION
N
TWO POLE
Advanced Protection Technologies, Inc.
Clearwater, Florida
TVSS 56E3
Listed
U
R
L
C
G
THREE POLE W/ DS
Advanced Protection Technologies, Inc.
Clearwater, Florida
56E3
Listed
U
R
L
3
1
5
7
2
46
G
CB NA
DELTA & HRG WYE 3 Hots, 1 Grnd
CAUTION
Advanced Protection Technologies, Inc.
G
Clearwater, Florida
THREE POLE
A
N
B
C
TVSS
U
L
56E3
R
Listed
3
1
5
2
4 6
Clearwater, Florida
Listed
Advanced Protection Technologies, Inc.
R
56E3
L
U
TVSS
A
B
N
C
CAUTION
7
8
CAUTION
A
N
CAUTION
ABNC
8
Phase A (BLK)
V
Phase B (BLK)
Phase C (BLK)
Ground (GRN)
Hot (BLK)
V
Neutral (WHT)
Ground (GRN)
SINGLE POLE 1 Hot, 1 Neu, 1 Grnd
Phase A (BLK)
A
Phase B (BLK)
B
Neutral (WHT)
N
V
}
Phase C (BLK)
C
Ground (GRN)
WYE 3 Hots, 1 Neu, 1 Grnd
Phase A (BLK)
Phase B (ORNG)
V
}
Phase C (BLK)
Neutral (WHT) Ground (GRN)
HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd
Phase A (BLK)
V
}
Phase C (BLK)
Ground (GRN)
CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd
9
Loading...
+ 19 hidden pages