Residential
surgeassure
TM
Surge Protective Device
S50A User’s Manual
surgeassure
14550 58th Street North Clearwater, Florida 33760
1.800.727.0669 - info@surgeassure.com - www.surgeassure.com
TM
![](/html/cd/cdbd/cdbda4fe1c93b48dcee35588e585aada4e4ed679ec713f9194938d7d361e5022/bg2.png)
Introduction
Thank you for choosing the surgeassureTM S50A Residential
Surge Protective Device.
Save this manual! It includes instructions for obtaining
warranty service and for returning a defective device.
Please read and understand all information in this manual
prior to installation. The procedures contained herein
are not intended to supersede local or national electrical
codes. Check all applicable electrical codes to ensure
compliance. In all instances, local and national electrical
code requirements are to be followed.
This manual provides instructions for installing the S50A
Surge Protective Device (SPD). The S50A SPD (Figure
1) can be mounted three ways. The preferred way is to
mount the SPD directly to the outside of the electrical
panel equipment using the pipe nipple on the body of the
SPD. Other options include standard 35mm DIN-rail (not
included) or via the attached L-bracket for standard at
mounting surface. Some of these methods require the
use of additional conduit and hardware (not provided).
See Figure 4 for further information on mounting methods.
Specications
Temperature Operating -40oC (-40oF) to 60oC (+140oF)
Temperature Storage -55
Wire Size & Installation Torque 10 AWG; 18 inch-pounds
Appropriate Circuit Breaker
based on conductor size
NEMA 250 Enclosure Rating
o
C (-67oF) to 65oC (+149oF)
30A (SPD includes internal OCP)
Type 4X with appropriate
sealing & sealing conduits
Parts List and Inspection
Items included in the package consist of the following:
• 1 - S50A Surge Protective Device including 3’ (~1m)
conductors
• 1 - ¾” conduit nut
• 1 - Data Sheet
• 1 - User’s Manual (this document)
Carefully inspect each item in the package for signs of
damage. If damage is found, please contact surgeassureTM
Technical Support: 1-800-727-0669. For more information
about this product or other surgeassureTM products, visit
www.surgeassure.com.
The S50A provides protection from damaging transient
voltage surges and spikes. Proper installation is imperative
to maximize the effectiveness and overall performance of
this device. This device must be installed by a licensed
electrician. The electrician should follow the steps outlined
in this manual to insure proper installation.
Note: surgeassureTM products are extensively tested to
industry standards as set by ANSI/IEEE C62.41.1-2002,
C62.41.2-2002, and C62.45-2002. The S50A is listed to the
most recent edition of UL 1449 Third Edition (Sept 2009).
During installation into an electrical system, the S50A must
NOT be energized until the electrical system is installed,
inspected and tested. All conductors must be connected
and functional, including neutral (if required).
Failure to follow the guidelines in this manual can lead to
abnormally high voltage being applied to the SPD. This
may cause the S50A unit to become inoperative. The
warranty does not cover an incorrectly installed device.
Do not high potential test the electrical system with the SPD
connected. Failure to disconnect the SPD during elevated
voltage testing will result in damage to the suppression
components and/or other electronic components (see
Safety Information).
Safety Information
This section provides pertinent safety information that must
be considered before installing the SPD.
• Do not install this device during a lightning storm.
• This device is rated NEMA 4X. Suitable for indoor
and outdoor applications. The customer must seal
the conduit nipple against the panel using watertight
ttings (not supplied) to ensure a watertight
connection.
• Do not install the surge protector in an excessively
hot or moist location.
• Other safety considerations are listed on the
following page.
!
BONDING BETWEEN CONDUIT CONNECTIONS IS
NOT AUTOMATIC AND MUST BE PROVIDED AS PART
CONDUCTING DIELECTRIC AND/OR HIGH POTENTIAL
TESTING WILL CAUSE INTERNAL DAMAGE TO THE
SPD UNIT. DO NOT PERFORM DIELECTRIC OR HIGH
POTENTIAL TESTS WITH THE PHASE OR NEUTRAL
CAUTION
OF THE INSTALLATION.
SPD WIRES CONNECTED
Page 2