One Town Center Road
Boca Raton, FL 33431
Phone: (561) 988-3600
FAX: (561) 988-3675
ADT-LCD40 Series
Remote Fire
Annunciators
for use with Unimode 200
Addressable Fire Alarm Control Panel
FIRE ALARM ANNUNCIATOR
AckSilence
Drill
Hold 2 sec.
Reset
Document #50520
7/25/00 Rev:
P/N 50520:D ECN 00-325
D
Fire Alarm System Limitations
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire. Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers.
A study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke
cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or
basement fire.
Particles of combustion or "smoke" from a developing
fire may not reach the sensing chambers of smoke
detectors because:
• Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors
by air outlets.
• Smoke detectors may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to
alarm smoke detectors. Smoke detectors are designed
to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are
often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may
not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
detectors are designed to protect property, not life.
IMPORTANT!
the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
Smoke detectors must be installed in
wiring, communications, signaling, and/or power.
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal. It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A maintenance agreement should be arranged through the local
manufacturer's representative. Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only. Adequate written
records of all inspections should be kept.
Heat
If
LimWarSm.p65 01/10/2000
Installation Precautions
WARNING -
connected to the fire alarm control panel.
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION -
Changes.
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific software. Reacceptance testing is required
after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation
at 0-49° C/32-120° F
RH (non-condensing) at 30°
useful life of the system's standby batteries and the
electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore,
it is recommended that this system and all peripherals
be installed in an environment with a nominal room
temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Several different sources of power can be
Disconnect all
System Reacceptance Test after Software
To ensure proper system operation, this
and at a relative humidity of 85%
C/86° F. However, the
Adherence to the following will aid in problem-free
installation with long-term reliability:
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected
to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning
Consult with the Technical Services Department
strikes.
if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains staticsensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
static charges are removed from the body. Use staticsuppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must
be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a
residential area is likely to cause interference, in
which case the user will be required to correct the
interference at his own expense.
LimWarSm.p65 01/10/2000
Canadian Requirements
This digital apparatus does not exceed the
Class A limits for radiation noise emissions from
digital apparatus set out in the Radio Interference Regulations of the Canadian Department
of Communications.
Le present appareil numerique n'emet pas de
bruits radioelectriques depassant les limites
applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le
ministere des Communications du Canada.
Notes
4
Document 50520 Rev D 7/25/00 P/N 50520:D
Table of Contents
Tabl e o f Co nte n ts
Section 1: ADT-LCD40 Series Annunciators ...........................................6
1.1 ADT-LCD40 and ADT-LCD40L ...................................................7
1.2 ADT-LCD40 Only ..........................................................................7
5.1 EIA-485 Shield Not in Conduit ......................................................25
Figure 5-1: EIA-485 Without Conduit ..................................26
5.2 EIA-485 Shield in Full Conduit ......................................................27
Figure 5-2: EIA-485 In Conduit ...........................................27
Section 6: Programming the Unimode 200 ...............................................28
Document 50520 Rev D 7/25/00 P/N 50520:D
5
ADT-LCD40 Series Annunciators
Section 1:
ADT-LCD40 Series Annunciators
FIRE ALARM ANNUNCIATORFIRE ALARM ANNUNCIATOR
AckSilence
Drill
Hold 2 sec.
ADT-LCD40
Reset
ADT-LCD40L
Note: Only Model ADT-LCD40L is listed for use in Canada.
The ADT-LCD40 Series Annunciators are compact, attractive,
40-character, backlit LCD fire annunciators designed for use with the
Unimode 200 Addressable Fire Alarm Control Panel. The
ADT-LCD40L operates the same as the ADT-LCD40, except it does not
have function switches or a key-switch. It should be noted that the
ADT-LCD40 Series Annunciator displays will mimic the LCD display
located on the Unimode 200 main circuit board.
If software with Part Number #UNIMODE200V3.0 is installed in the
ADT Unimode 200, the ADT-LCD40 Series Annunciator must have software with a Part Number of 73879 to operate with the control panel. If
software with a Part Number of #UNIMODE200V4.0 or higher is
installed in the Unimode 200, the ADT-LCD40 Series Annunciator must
have software with a Part Number of #LCD40V2.0 or higher to operate
with the control panel.
The ADT-LCD40 Series is capable of displaying English-language text
of system point status including device type, independent
point
alarm,
trouble or supervisory, zone and custom alpha labels programmed into
the control panel. The ADT-LCD40 Series also provide system status
LEDs to display Power, Alarm, Trouble and Supervisory conditions.
The ADT-LCD40 is capable of performing system acknowledge,
silence, drill and reset remotely while the ADT-LCD40L does not have
these features.
Communication between the control panel and the ADT-LCD40 Series
is accomplished over a two-wire serial interface employing the EIA-485
communication standard. Up to 32 annunciators may be connected to
the two-wire EIA-485 circuit. The annunciators may be powered from
the host FACP or remote UL listed, filtered, power supplies.
6
Document 50520 Rev D 7/25/00 P/N 50520:D
ADT-LCD40 Series AnnunciatorsADT-LCD40 and ADT-LCD40L
1.1ADT-LCD40 and ADT-LCD40L
• 40-character LCD display (20 characters x 2 lines) is backlit
under normal and alarm conditions
• System Status LEDs for Power (green), Alarm (red), Trouble
(yellow) and Supervisory (yellow)
• No programming necessary — duplicates messages at control
panel display
• Local piezo sounder with alarm and trouble resound
• Device type identifiers from the control panel
• Device & zone custom alpha labels from the control panel
• Time/date and device address from the control panel
• EIA-485 connects to control panel terminal port (requires
DIM-485 module)
• Plug-in terminal blocks for ease of installation and service
• DIP switches control piezo enable/disable and transmit/receive
mode
• Up to 32 ADT-LCD40 Series Annunciators per Unimode 200
• Mounting options:
Surface mounting in SBB-3 (2.75" depth)
✓
Semi-flush mounting in three-gang electrical box (P/N
✓
10103) with a minimum depth of 2.187"
Can be located up to 3,000 feet (900 m) from the panel
✓
• Backlight turns off during AC loss to conserve battery power but
will turn back on if an alarm condition occurs.
1.2ADT-LCD40 Only
• Enable/Disable key-switch
• Function switches for:
Acknowledge
✓
Signal Silence
✓
Drill
✓
System Reset
✓
• DIP switches control function switches and key-switch enable/
disable
Document 50520 Rev D 7/25/00 P/N 50520:D
7
ADT-LCD40 Series AnnunciatorsComponents
Figure 1-1: Components
Note: OPEN (Up)
OFF = Receive only
OFF = Key-switch Disable on ADT-LCD40 only
ROM
(not used on ADT-LCD40L)
ON = Piezo Enable
Future use
position on SW1
is OFF state (See
“Wiring to Ter minals” on page 9.).
Top view
Membrane Connector
Cable connection to membrane switches
for Acknowledge, Silence, Drill and Reset.
8
Document 50520 Rev D 7/25/00 P/N 50520:D
Piezo Sounder
The ADT-LCD40 sounder, if enabled, will
be activated when any new alarm or trouble
is received from the panel. It is silenced by
an Acknowledge switch. Piezo must not be
disabled without approval of the LAHJ
(Local Authority Having Jurisdiction).
ADT-LCD40 Series AnnunciatorsWiring to Terminals
Figure 1-2: Wiring to Terminals
Side view
P1
Terminal Block replacement
P/N 02108
+ EIA-485 OUT
+ EIA-485 IN
- EIA-485 OUT
- EIA-485 IN
no connection
+24 VDC IN
+24 VDC OUT
-24 VDC IN
-24 VDC OUT
Earth Ground Option
P2
Te r mi na l Bl oc k
replacement
P/N 02109
Note: These connections must be power-limited and the +24 VDC
nominal power must be filtered and nonresettable.
Current Consumption @ 24 VDC nominal (filtered and nonresettable)
Normal/Standby (no activity): 64 mA
Trouble Condition: 64 mA
Alarm: 66 mA
AC Fail (not backlit): 28 mA
Document 50520 Rev D 7/25/00 P/N 50520:D
9
ADT-LCD40 Series AnnunciatorsSW1 DIP Switch Settings
1.3SW1 DIP Switch Settings
The Up position on DIP switch SW1 is the Off state. Refer to “DIP
Switch Settings Example” on page 11, for an explanation of DIP switch
positions. SW1 switch settings follow:
1 - On (Down) = Receive/Transmit, Off (up) = Receive Only.
Set switch 1 to Off (Up) position for all ADT-LCD40 Series Annunciators except the last (or only) annunciator on the EIA-485 loop.
Set switch to On (Down) position for the last or only annunciator on
the EIA-485 loop to allow transmission of a supervision signal (and
function switch depressions on the ADT-LCD40) back to the FACP.
The last or only annunciator must be set for Receive/Transmit
(switch 1 in the Down position).
A break (open circuit) in the power or EIA-485 connections creates
an ADT-LCD40 Series Annunciator fault at the Unimode 200 panel.
All annunciators before the break will continue to display information (
but the function switches on the ADT-LCD40 will no longer
).
operate
ADT-LCD40 Only (not used on the ADT-LCD40L)
2 On (Down) = Key-switch enabled, Off (Up) = Key-switch disabled.
Switch 2 set to the On (Down) position enables key-switch
operation. The key-switch may now be used to enable the
ADT-LCD40 membrane switches, allowing remote switch functions, or lockout the switches, preventing remote switch functions
Switch 2 set to the Off (Up) position disables the key-switch
operation. Refer to “Switch Functions for ADT-LCD40 Only” on
page 14, for key-switch function description.
3 - On (Down) = Piezo sounder enabled, Off (Up) = Piezo sounder
disabled.
CAUTION:
Piezo sounder must not be disabled without prior
approval of the Local Authority Having Jurisdiction (LAHJ).
4 through 8 = Future use.
10
Document 50520 Rev D 7/25/00 P/N 50520:D
ADT-LCD40 Series AnnunciatorsDIP Switch Settings Example
.
Figure 1-3: DIP Switch Settings Example
Down Position = On State
Up (OPEN) Position = Off State
Note: SW1 DIP switch settings as illustrated in Figure 1-3 are as
follows:
1. DIP switch 1: On (Down) - Receive/Transmit. This setting is
used for the last or only ADT-LCD40 Series Annunciator on the
EIA-485 line
2. DIP switch 2: Used on ADT-LCD40 only - On (Down) = membrane function switches enabled.
3. DIP switch 3: Off (Up) = piezo sounder disabled (requires
approval of LAHJ)
4. DIP switches 4 through 8: not used
Document 50520 Rev D 7/25/00 P/N 50520:D
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.