ADTAPS-6R__INSTENGLB0.fm Page 1 Tuesday, November 21, 2000 11:30 AM
ADT Security Services, Inc.
1750 Clint Moore Road
Boca Raton, FL 33431
(561) 988-3600
ADT-APS-6R Auxiliary Power Supply
Installation Instructions
Document 5093 5
07/21/2000Revision:
PN 50935:B ECN 00-317
B
Fire Alarm System Limitations
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire. Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers.
A study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke
cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or
basement fire.
Particles of combustion or "smoke" from a developing
fire may not reach the sensing chambers of smoke
detectors because:
• Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors
by air outlets.
• Smoke detectors may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to
alarm smoke detectors. Smoke detectors are designed
to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are
often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may
not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
detectors are designed to protect property, not life.
IMPORTANT!
the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
Smoke detectors must be installed in
wiring, communications, signaling, and/or power.
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal. It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A maintenance agreement should be arranged through the local
manufacturer's representative. Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only. Adequate written
records of all inspections should be kept.
Heat
If
LimWarSm.p65 01/10/2000
Installation Precautions
WARNING -
connected to the fire alarm control panel.
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION -
Changes.
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific software. Reacceptance testing is required
after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation
at 0-49° C/32-120° F
RH (non-condensing) at 30°
useful life of the system's standby batteries and the
electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore,
it is recommended that this system and all peripherals
be installed in an environment with a nominal room
temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Several different sources of power can be
Disconnect all
System Reacceptance Test after Software
To ensure proper system operation, this
and at a relative humidity of 85%
C/86° F. However, the
Adherence to the following will aid in problem-free
installation with long-term reliability:
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected
to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning
Consult with the Technical Services Department
strikes.
if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains staticsensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
static charges are removed from the body. Use staticsuppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must
be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a
residential area is likely to cause interference, in
which case the user will be required to correct the
interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the
Class A limits for radiation noise emissions from
digital apparatus set out in the Radio Interference Regulations of the Canadian Department
of Communications.
Le present appareil numerique n'emet pas de
bruits radioelectriques depassant les limites
applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LimWarSm.p65 01/10/2000
ADTAPS-6R__INSTENGLB0TOC.fm Page 4 Tuesday, November 21, 2000 12:56 PM
Connecting the ADT-APS-6R to an ICM-4/ICE-4 Module......................1 4
Supplying Power to a M300CADT Module .............................................. 15
Configuring the ADT-APS-6R.............................................. .................... ...16
Servicing the ADT-APS-6R..........................................................................17
Appendix A - Unimode 4-16
Connecting the ADT-APS-6R to an MPS-24B............................................19
Appendix B - Unimode 300/400
Connecting the ADT-APS-6R to an MPS-400............................................21
Appendix C - Unimode II & Unimode 2020
Connecting the ADT-APS-6R to an MPS-24A ...........................................23
Connecting the ADT-APS-6R to an MPS-24B............................................24
4
ADT-APS-6R Installation PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 5 Tuesday, November 21, 2000 11:30 AM
1. Overview
Introduction
This document contains information for installing, servicing, and
configuring the ADT-APS-6R Auxiliary Power Supply. The table below
contains a list of document sources for supplemental information:
Control PanelsRefer to...Part Number
Unimode 4-16Unimode 4-16 Installation
Unimode II SeriesUnimode II Installation
Unimode 400 SeriesUnimode 400 Installatio n
Unimode 2020Unimode 2020 Installation
ADT Transponder
Series
AllADT Device Compatibility
Manual
Manual
Manual
Manual
ADT Transponder Manual50928
Document
A15019
A15583
50710
51167
51352
Description
The ADT-APS-6R Auxiliary Power Supply is a 150W cabinet-mounted
power supply, designe d t o power devi ces that requ ire filtere d, regulated,
non-resettable power, such as XP Transponder modules, Notification
Appliance Circuit Modul es and Control Modules. T he ADT-APS-6R
provides three 24 VDC (filtered) output circuits.
Table 1 Supplemental Documentation
APS-6Risoview.cdr
Figure 1 ADT-APS-6R Auxilliary Power Supply
ADT-APS-6R Instruction PN 50935:B 7/21/00
5
ADTAPS-6R__INSTENGLB0.fm Page 6 Tuesday, November 21, 2000 11:30 AM
1. OverviewDescription
The figures below identify the features of the ADT-APS-6R power
supply:
Trouble In (J4) - Trouble Out (J3)
“P” style connectors for internal cabinet
connections
Three 24 VDC output circuits
Two (2) power-limited
One (1) non power-limited
J1
J3
TB2
J2
LED Status Indicators:
Green LED – Indicates AC power on
Yellow LED – Indicates loss of AC or battery
JP3
J9
Fuse F2 for battery protection
(10A, 3AG, slow blow)
Fuse F1 for AC protection
(4A, 3AG, slow blow)
JP2
APS-6Rsidebrd.cdr
Jumpers JP2 and JP3 for
selecting 8-hour or 16-hour
delay for AC loss reporting
(default is immediate)
Figure 2 ADT-APS-6R Control Board
JP1
APS-6Rboard.cdr
Jumper JP1 for selecting AC input voltage
(120 VAC default)
Figure 3 ADT-APS-6R Main Board
6
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 7 Tuesday, November 21, 2000 11:30 AM
Specifications1. Overview
Specifications
The ADT-APS-6R is compatible with the Unimode II, Unimode 300/400,
Unimode 4-16 and Unimode 2020 control panels. Specifications for the
ADT-APS-6R are:
Electrical Specifications
AC Primar y In put Power
Wire Size: #14 AWG with
600 VAC insulation
24 VDC Secondary Input Power
(lead-acid batteries only)
Note: Batteries are charged by the system power supply.
24 VDC output power
Circuit 1
Circuit 2
Circuit 3
Fuses
F1 (AC supervision)
F2 (battery supervision)
Trouble supervision bus
J3 output
J4 input
Note: J3 and J4 can be
interchanged.
Loss of AC IndicationImmediate indication (default)
120 VAC, 60 Hz, 2.5 A
240 VAC, 50 Hz, 1.2 A
25 mA DC standby current
16 mA DC standby current (wit h A C fa il del a y
operating)
Total 6 A (4 A continuous)
3 A @24 VDC power-limited (+ 10, –15%)
3 A @24 VDC power-limited (+ 10, –15%)
6 A @24 VDC non power-limite d (+10, –15%)
Form A contact (open col lector)
Form A contact (open col lector)
8 or 16 hour delay
Mechanical Specifications
Size of ADT-APS-6R in enclosure 6.09 in. x 4.23 in. x 2.92 in.
Cabinets for mountingADT-CAB-3 Series, usin g CHS -4 and CHS -4L
Note: An optional module (such as an ICM-4) without an expansion card can
mount above an ADT-APS-6R in a CHS-4, a Unimode 4-16, and a
ADT-CAB-400AA.
ADT-APS-6R Instruction PN 50935:B 7/21/00
chassis, for Unimode 400, unimod e II and
Unimode 2020 contr ol pa nels.
ADT-CAB-400AA for Unimode 300/400
control panel; accepts one APS-6R.
Unimode 4-16 can accept one ADT-APS-6R .
Table 2 ADT-APS-6R Specifications
7
ADTAPS-6R__INSTENGLB0.fm Page 8 Tuesday, November 21, 2000 11:30 AM
1. OverviewSpecifications
NOTES
8
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 9 Tuesday, November 21, 2000 11:30 AM
2. Installation
WARNING: Use extreme caution when working with the APS-6R.
!
High voltage and AC line-connected circuits are present. Turn off and
remove all power sources. To reduce the risk of electric shock make
sure to properly ground the unit.
Introduction
This section contains instructions for mou nti ng, wirin g, config uri n g and
servicing the ADT-APS-6R.
Installation topics covered in detail:
TopicRefer to...
Mounting to a ADT-CAB-400AA
Backbox
Mounting to a ADT-CAB-3 Se ries
Cabinet
Field Wiring"Field Wiring an ADT-APS-6R" on
Wiring Multiple ADT-APS-6Rs"Connecting M u ltiple ADT-A P S - 6R
Connecting to an ICM/ICE"Connecting the ADT-APS-6R to an
Powering an M300CADT"Supplying Power to a M300CADT
Configuring"Configuring the ADT-APS-6R" on
Servicing"Servicing the ADT-APS - 6R" on
"Mounting an ADT-APS-6R in a
ADT-CAB-400 AA Backbox" on
page 10
"Mounting in ADT-CAB-3 Series
Cabinets " on page 11
page 12
Power Supplies" on page 13
ICM-4/ICE-4 Module" on page 14
Module" on page 15
page 16
page 17
ADT-APS-6R Instruction PN 50935:B 7/21/00
9
ADTAPS-6R__INSTENGLB0.fm Page 10 Tuesday, November 21, 2000 11:30 AM
2. InstallationMounting an ADT-APS- 6R in a AD T- CAB-400AA Backbox
Mounting an ADT-APS-6R in a ADT-CAB-400AA Backbox
An Auxiliary Power Supply is mounted as shown in the figure belo w.
To mount the ADT-APS-6R, follow these instructions:
StepAction
1Remove plastic co ver from APS-6R.
2If 240 VAC is to be used , c ut JP1 jumper at th is time. See "Config u ri ng the
ADT-APS-6R" on page 16.
3Place the APS-6R onto the mounting studs in the backbox.
4Insert a standoff through each of the printed circuit board mounting holes,
threading each stan doff to th e m ounting studs.
5Tighten the standoffs until the APS-6R is securely fastened to the backbox.
6Reinstall the plastic chassis c over.
ADT-CAB-400AA
Backbox
ADT-APS-6R
Assembly
Figure 4 Mounting an ADT-APS-6R to a ADT-CAB-400AA Backbox
Mounting
Studs
Standoff
(2 places)
APS-6R to CAB-AA.cdr
10
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 11 Tuesday, November 21, 2000 11:30 AM
Mounting in ADT-CAB-3 Series Cabinets2. Installation
Mounting in ADT-CAB-3 Series Cabinets
This section contains instructions for the installation of the Auxiliary
Power Supply into a ADT-CAB-3 Series cabinet (ADT-CAB-A3, ADTCAB-B3, ADT-CAB-C3 and ADT-CAB-D3).
These cabinets use a CHS-4L or CHS-4 Chassis to mount the
ADT-APS-6R.
Instructions for mounting:
StepAction
1Remove plastic co ver from APS-6R.
2If 240 VAC is to be used, cut JP1 jumper at this time. See "Con f ig u ri ng the
ADT-APS-6R" on page 16.
3Place the APS-6R onto the mounting studs of the chassis (Figure 5 on page
11).
4Insert a standoff through each of the printed circuit board mounting holes,
threading each standoff to the moun ting studs on the chas s i s .
5Tighten the standoffs until the APS-6R is securely fastened to the chassis.
6Reinstall the plastic chassis c over.
CHS-4 Series Chassis Mounting
The illustration below shows an ADT-APS-6R being mounted in a CHS4L chassis. Mounting in a CHS-4 chassis is accomplished in the same
way.
CHS-4L Chassis
Mounting Studs
Standoff
(2 places)
Figure 5 Mounting an ADT-APS-6R to a CHS-4L Chassis
ADT-APS-6R
Assembly
APS-6R to CHS-4L.cdr
ADT-APS-6R Instruction PN 50935:B 7/21/00
11
ADTAPS-6R__INSTENGLB0.fm Page 12 Tuesday, November 21, 2000 11:30 AM
2. InstallationWiring the ADT-APS-6R
Wiring the ADT-APS-6R
This section contains instructions for wiring the Auxiliary Power Supply
as follows:
• Typical field wiring from an ADT-APS-6R to a control panel and
optional devices.
• Wiring multiple ADT-APS-6R power supplies.
Field Wiring an ADT-APS-6R
You can use J1 and J2 in place of TB2 when the ADT-APS-6R is
powering internal modules (such as an ICM-4, ICE-4, ADT-UZC-256,
XPC-8) with compatible connectors.
Output Circuit 3 (J9) can be used as a s ource of power for the XPIQ Audio
Transponder only.
Note: When using the J9 connector do not use the J2 connector. This will satisfy the
0.25 (6.35mm) requirement for separation between power-limited and nonpowerlimited circuits.
Primary and Secondary Power Connections - See appendix for your
specific system information.
Caution: When finished wiring AC connections, install the press-fit
terminal block cover over TB1 AC connections.
!
Output Circuit 3: Non Power-limited, 6 A @24 VDC (+10, –15%)
Output Circuit 2 (24 VDC)
– + – + – +
J9
J2
TB2
JP2
JP3
J3
Figure 6 Typical Wiring for an ADT-APS-6R
Output Circuit 1 (24 VDC)
J1
+
Output Circuit 1: Power-limited
3 A @24 VDC (+10, –15%)
–
+
Output Circuit 2: Power-limited
3 A @24 VDC (+10, –15%)
–
Trouble Bus In/Out
BA TT (+)
BA TT (–)
HOT
NEUTRAL
EARTH
Secondary Power
24 VDC batteries.
Primary Power
120 VAC or 240 VAC.
Earth Ground -
EARTH
ground terminal on main power
supply. If two or more units are connected,
secondary units connect to earthground
on the previous ADT-APS-6R in the chain.
Connects to chassis or
APS-6Rsidebrd.cdr
12
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 13 Tuesday, November 21, 2000 11:30 AM
Wiring the ADT-APS-6R2. Installation
Connecting Multiple ADT-APS-6R Power Supplies
Typical trouble bus connections for multiple ADT-APS-6R power
supplies using trouble connectors J3 and J4.
Use Cable 71033 or 75098 (same cables; different lengths) for all wiring.
See appendix on your system for specific “Trouble Input” connection.
Note: J3 and J4 can be interchanged.
T o trouble input on main power
supply or control panel
J9
JP2
JP3
J1
J2
TB2
J3
J9
JP2
J1
J2
TB2
J3
JP3
J9
JP2
JP3
J1
J2
TB2
J3
First APS-6RLast APS-6R
Figure 7 Trouble Bus Connections for Multiple ADT-APS-6R Configurations
APS-6Rmultiple.cdr
ADT-APS-6R Instruction PN 50935:B 7/21/00
13
ADTAPS-6R__INSTENGLB0.fm Page 14 Tuesday, November 21, 2000 11:30 AM
2. InstallationWiring Applications
Wiring Applications
This section contains instructions for wiring the ADT-APS-6R assembly
as follows:
• Connecting the ADT-APS-6R to an ICM-4/ICE-4 module
• Supplying notification appliance power to a FCM module
Connecting the ADT-APS-6R to an ICM-4/ICE-4 Module
All four (4) NACs on the ICM-4 are powered from the ADT-APS-6R
output circuit 2 (J2) and the four (4 ) NACs on the ICE-4 are p owered from
circuit 1 (J1). The NACs share the total 3A available from each circuit.
Typical connections for wiring:
ICM-4
Blue
Black
ADT-APS-6R
J65 J
Blue
J65 J
Black
J9
JP2
JP3
ICE-4
J2
TB2
Auxiliary Power
Harness
PN 71091
J1
J3
14
APS-6Ricm.cdr
Figure 8 Typical ADT-APS-6R Wiring to an ICM-4/ICE-4 Module
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 15 Tuesday, November 21, 2000 11:30 AM
Wiring Applications2. Installation
Supplying Power to a M300CADT Module
The circuit is supervised and power-limited.
Typical connections for wiring:
J9
J2
J1
SLC loop
TB2
J3
6
6
2
1
1
6
6
5
2
2
1
1
8
7
8
7
9
9
10
10
14
14
0
15
150
8
7
7
8
9
9
0
0
ADDRESS
ADDRESS
0
0
11
11
12
12
1
1
13
13
2
2
3
3
4
4
T o next device
APS-6Rfcm.cdr
9
9
5
5
4
4
8
3
8
3
2
TENS
TENS
7
7
5
4
4
6
6
3
LOOP
LOOP
3
5
5
ONES
ONES
JP2
JP3
NAC
on SLC loop
Figure 9 Typical ADT-APS-6R Wiring to a M300CADT Module
ADT-APS-6R Instruction PN 50935:B 7/21/00
15
ADTAPS-6R__INSTENGLB0.fm Page 16 Tuesday, November 21, 2000 11:30 AM
2. InstallationConfiguring the ADT-APS-6R
Configuring the ADT-APS-6R
The ADT-APS-6R may be configured for the following:
• 8-hour delay for reporting loss of AC: cut jum per JP2.
• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.
• 240 VAC operation: cut jumper JP1.
The figure below illustrates the location of the jumpers:
J1
J3
J2
J9
TB2
JP3
JP1
Figure 10 Configuring the ADT-APS-6R
JP3
JP2
JP2
JP1
APS-6Rconfig.cdr
16
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 17 Tuesday, November 21, 2000 11:30 AM
Servicing the ADT-APS-6R2. Installation
Servicing the ADT-APS-6R
The only serviceable components on the ADT-APS-6R are fuses F1 and
F2. If a fuse fails, replace it with a fuse of the same type and rating:
• F1 AC protect ion - 4A, 3 A G
• F2 Battery protection - 10A, 3 AG
To replace either fuse remove the vertical PC board as follows:
1.Turn off and remove all power sources.
2.Remove plastic cover.
3.Remove the two retaining screws securing vertical board.
4.Unplug the vertical PC board from the connectors.
5.Replace fuses as required.
6.Reinstall board in reverse order, install plastic cover and connect all
power.
The figure below illustrates the location of the fuses.
Retaining Screw (typ)
F2 Fuse
J1
J3
TB2
J2
JP3
J9
F1 Fuse
Connector (typ)
Main Circuit Board
Figure 11 Servicing the ADT-APS-6R
JP2
APS-6Rservice.cdr
ADT-APS-6R Instruction PN 50935:B 7/21/00
17
ADTAPS-6R__INSTENGLB0.fm Page 18 Tuesday, November 21, 2000 11:30 AM
2. InstallationServicin g the ADT-APS-6R
NOTES
18
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 19 Tuesday, November 21, 2000 11:30 AM
Appendix A - Unimode 4-16
Connecting the ADT-APS-6R to an MPS-24B
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-24B terminal block
TB1, Pin 3(
• Connect secondary power from TB3 to MPS-24B terminal block
TB3, Pin 1(+) and Pin 2(–)
• Connect trouble input from J3 to MPS-24B terminal block P4
J9
J1
J2
TB2
J3
NEUT
) and Pin 4(
EARTH
TB1
CB1
P1
7
5
3
2
1
MPS-24BPCC
REV ___
HOT
AC NEUT
2 3 4
ACHO T
)
COMMON
R55
1 2 3 4 6 7 8
P2
+24 VRESET
TB2
+24 VPOWER
1 2 3 4
JP3
COMMON
AC BATT +EF -EF
BATT +
1 2
TROUBLES
BATT -
TB3
P3
P4
JP2
JP3
APS-6R to MPS-24B.cdr
Figure 12 Wiring to MPS-24B
ADT-APS-6R Instruction PN 50935:B 7/21/00
19
ADTAPS-6R__INSTENGLB0.fm Page 20 Tuesday, November 21, 2000 11:30 AM
Appendix A - Unimode 4-16Connecting the ADT-APS-6R to an MPS-24B
NOTES
20
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 21 Tuesday, November 21, 2000 11:30 AM
Appendix B - Unimode 300/400
Connecting the ADT-APS-6R to an MPS-400
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-400 terminal block TB1
(
and
NEU
• Connect secondary power from TB3 to MPS-400 terminal block
TB1 (+ and –)
• Connect trouble input from J3 to MPS-400 terminal block J4
HOT
)
POWER INPUT-12 0V,60 Hz, and24 V BATT
NEUTRAL
J9
JP3JP2
J1
J2
TB2
J3
TB1
ToTransformer AssemblyT2
ToTransformer Assembly T1
J6
CPUPOWER
J1
ACCESSORIES
J2
EARTH HOTBATT+ BATT-
AFP-400CONNECTOR
TB3
TB2
+-+-+-
SUPERVISORY
TB4
JP2S2
SECUR ITY
TB5
TB7
B+ B- A+ A-B+ B- A+ A-
TB6
TB8
TB9
TB10
S2
APS-6R to MPS-400.cdr
Figure 13 Wiring to MPS-400
ADT-APS-6R Instruction PN 50935:B 7/21/00
21
ADTAPS-6R__INSTENGLB0.fm Page 22 Tuesday, November 21, 2000 11:30 AM
Appendix B - Unimode 300/400Connecting the ADT-APS-6R to an MPS-400
NOTES
22
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0.fm Page 23 Tuesday, November 21, 2000 11:30 AM
Appendix C - Unimode II & Unimode 2020
Connecting the ADT-APS-6R to an MPS-24A
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-24A terminal block
TB1, Pin 5(
• Connect secondary power from TB3 to MPS-24A terminal block
TB2, Pin 1(+) and Pin 2(–)
• Connect trouble input from J3 to MPS-24A terminal block P5
J9
J1
J2
TB2
J3
NEUT
) and Pin 7(
EARTH GND AC NEUT RAL AC HOT
TB1
HOT
)
POWER LIM ITED
BAT+ BAT-
TB2
+24R CO MMON +24 COMMON
F1CB1
P3
JP5
P2
P5
P4
R27
JP3JP2
APS-6R to MPS-24A.cdr
Figure 14 Wiring to MPS-24A
ADT-APS-6R Instruction PN 50935:B 7/21/00
23
ADTAPS-6R__INSTENGLB0.fm Page 24 Tuesday, November 21, 2000 11:30 AM
Appendix C - Unimode II & Unimode 2020Connecting the ADT-APS-6R to an MPS-24B
Connecting the ADT-APS-6R to an MPS-24B
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-24B terminal block
TB1, Pin 3(
• Connect secondary power from TB3 to MPS-24B terminal block
TB3, Pin 1(+) and Pin 2(–)
• Connect trouble input from J3 to MPS-24B terminal block P4
J9
J1
J2
TB2
J3
NEUT
) and Pin 4(
EARTH
TB1
CB1
P1
7
5
3
2
1
MPS-24BPCC
REV ___
HOT
AC NEUT
2 3 4
)
COMMON
1 2 3 4 6 7 8
P2
+24 VRESET
TB2
ACHO T
R55
+24 VPOWER
1 2 3 4
JP3
COMMON
AC BATT +EF -EF
BATT +
1 2
TROUBLES
BATT -
TB3
P3
P4
JP2
JP3
APS-6R to MPS-24B.cdr
Figure 15 Wiring to MPS-24B
24
ADT-APS-6R Instruction PN 50935:B 7/21/00
ADTAPS-6R__INSTENGLB0IX.fm Page 25 Tuesday, November 21, 2000 12:57 PM
Index
Index
Numerics
16-hour delay
240 VAC
operation
use of
8-hour delay
16
16
10, 11
16
A
AC protection
ADT-CAB-3 Series cabinet
ADT-CAB-400AA
ADT-UZC-256