ADT Security Services 400 User Manual

ADT Security Services, Inc.
1750 Clint Moore Road Boca Raton, FL 33431 (561) 988-3600
Unimode 400 Multi-Net
Analog Fire Panel
Operations Manual
Document 50709 12/15/99 Revision:
PN 50709:A1 ECN 99-551
A
Installation Precautions
- Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72­1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120O F and at a relative humidity of 85% RH (non-condensing) at 30 useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15-27
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
O
C/86O F. However, the
O
C/60-80O F.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Further­more, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
FCC Warning
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Technical Publishing Document PRECAULG.PM6 12/31/96
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communica­tions du Canada.
1. Introduction
Overview ......................................................................................................................1
Operating Features ........................................................................................................ 1
Components...................................................................................................................1
2. Using the Control Panel
Overview ......................................................................................................................3
System Status Indicator LEDs ......................................................................................3
Control Keys .................................................................................................................4
3. Operating Modes
Normal Operation ......................................................................................................... 5
Trouble Operation ........................................................................................................5
Fire Alarm ....................................................................................................................6
Supervisory Signal ........................................................................................................ 7
Non-Alarm Point Operation .........................................................................................7
Trouble Monitor Point Operation ................................................................................. 7
Notification Appliance Circuit (NAC) Operation ........................................................ 8
Control-By-Event Operation ........................................................................................ 8
Releasing Functions ...................................................................................................... 8
Intelligent Detector Functions .................................................................................... 10
Pre-Alarm Operation (AWACS) ................................................................................ 11
Time Functions ........................................................................................................... 11
Table of Contents
Overview ............................................................................................................11
Operating Coding Functions .............................................................................. 12
Presignal/Positive Alarm Sequence (PAS) Operation .......................................12
Special System Timers ....................................................................................... 13
Waterflow Circuits Operation ............................................................................ 13
Disable/Enable Operation ..................................................................................13
Style 6 Operation ............................................................................................... 13
4. Read Status
Overview ....................................................................................................................15
How to Enter Read Status ........................................................................................... 15
Read Status Options ...................................................................................................15
Read Status for Points and Zones ......................................................................16
Read Status for a Detector, Module, or Output .................................................16
Read History ...................................................................................................... 18
View Alarm History ........................................................................................... 18
View or Print Hidden History ............................................................................ 18
Presignal Delay ..................................................................................................19
Releasing Zones ................................................................................................. 19
Time Control Zones ...........................................................................................19
Holiday Zones .................................................................................................... 20
NAC Coding Zone .............................................................................................20
Pre-Alarm Zone .................................................................................................20
System Parameters ............................................................................................. 21
Annunciator Display Selections ......................................................................... 22
Example of Annunciator Display Selections .....................................................22
Unimode 400 Operations PN 50709:A1 12/15/99 iii
Table of Contents 5. Voice Alarm Systems
5. Voice Alarm Systems
Overview ....................................................................................................................23
Operating Features ...................................................................................................... 23
In this Section ............................................................................................................. 23
Before you Begin ........................................................................................................24
AMG-1/AMG-EAudio Message Generator .............................................................. 25
AMG-1/AMG-E Overview ................................................................................ 25
AMG-1/AMG-E Operating Features .................................................................25
Operating the AMG-1 ........................................................................................ 26
Selecting AMG Group Functions ............................................................................... 27
Selecting AMG Tones and Messages.......................................................................... 28
ATG-2 Audio Tone Generator ...................................................................................31
ATG-2 Overview ............................................................................................... 31
How to Operate the ATG-2 ................................................................................32
Selecting Tones for the ATG-2 ..........................................................................32
Selecting a Primary (Evac) Channel Tone.......................................................... 33
Selecting a Secondary (Alert) Channel Tone .....................................................33
Select Operating Mode ......................................................................................33
Fire Fighter's Telephones (FFT-7/FFT-7S) ................................................................ 34
Overview ............................................................................................................34
FFT-7 Operating Components ........................................................................... 34
How to Operate the FFT-7 ................................................................................. 34
Audio Amplifiers ........................................................................................................35
Overview ............................................................................................................35
Audio Amplifier Features .................................................................................. 35
AA-30 Audio Amplifiers ............................................................................................ 36
AA-100/AA-120 Audio Amplifiers ...........................................................................37
Adjusting the Audio Gain Level (AA-30, AA-100/AA-120) ....................................38
Selecting the AA-100/AA-120 Backup Tone ............................................................. 38
AMG Voice Message Options .................................................................................... 39
Overview ............................................................................................................39
Installation .........................................................................................................39
iv Unimode 400 Operations PN 50709:A1 12/15/99
1. Introduction
Overview
The Unimode400 is a modular, intelligent Fire Alarm Control Panel (FACP) with an extensive list of powerful features. The CPU module, power supply module, and cabinet combine to create a complete fire control system for most applications. Optional modules mount to the chassis to provide additional output circuits.
Operating Features
Alarm Verification selection per point, with tally.
Positive Alarm Sequence (PAS) and Presignal per NFPA 721993.
Silence Inhibit timer and Auto Silence timer.
March time/temporal code for Notification Appliance Circuits (NACs).
Zone coding for NACs if using an optional ADT-UZC-256.
Alarm Silence/System Reset/Alarm Activate functions through M500M monitor
modules.
Automatic time-of-day and day-of-week control functions, with holiday option.
User-defined password and key-protected nonvolatile memory.
AWACS (Advanced Warning Addressable Combustion Sensing) with nine field-
adjustable Pre-Alarm levels with programmable Control-by-Event (CBE)
Operate automatic smoke or heat detector sounder base on action Pre-Alarm level,
with general evacuation on alarm level.
Security alarm point option with separate audible signal code.
Centralized voice paging and audible alarm signaling options.
Programmable Control-by-Event control of outputs from individual alarm or
supervisory addressable devices.
Components
Figure 1 shows components that affect operation of the control panel:
EIA-232 PC/Terminal Port
EIA-232 Printer Port
Control Keys
Programming Keypad
EIA-485 Terminal Mode Port
EIA-485 ACS Port
80-character (2 x 40) Liquid Crystal Display (LCD)
System Status LED Indicators
Figure 1 Control Panel Components
Unimode 400 Operations PN 50709:A 10/20/97 1
Notes
2 Unimode 400 Operations PN 50709:A 10/20/97
2. Using the Control Panel
Overview
Table 1 lists the controls and indicators and where to find information on their use:
Controls/Indicators Covered in...
Eight System Status Indicator LEDs System Status Indicator LEDs on page 3. Five control keys Control Keys on page 4. A panel sounder with a piezo that
Section 3. Operating Modes on page 5. provides unique sounds for alarm, trouble and supervisory/security conditions
Table 1 Control and Indicators
System Status Indicator LEDs
The control panel contains eight LED indicators with labels as shown in Figure 2:
Figure 2 System Status Indicator LEDs
Table 2 contains descriptions of the System Status Indicator LEDs:
Indicator Color When Active... To Turn Off...
AC Power Green Lights when the proper primary AC
power is applied.
Fire Alarm Red Flashes when a non-acknowledged Fire
Alarm exists. Lights steadily after you acknowledge the alarm.
Turn off AC power.
Clear the alarm condition and reset the system.
Pre-Alarm Warning
Security Alarm
Supervisory Signal
System Trouble
Disabled Points
Alarm Silenced
Yellow Flashes when a non-acknowledged
Pre-Alarm exists. Lights steadily after you acknowledge the Pre-Alarm.
Blue Flashes when a non-acknowledged
Security Alarm exists. Lights steadily after you acknowledge the alarm.
Yellow Flashes when a non-acknowledged
Supervisory Alarm exists. Lights steadily after you acknowledge the alarm.
Yellow Flashes when a non-acknowledged
System Trouble exists. Lights steadily after you acknowledge the trouble.
Yellow Lights when one or more system devices
are disabled.
Yellow Lights after an alarm condition occurs
and after pressing <Alarm Silence>.
Clear the alarm condition. (Action Pre-Alarm requires a system reset.)
Clear the Security Alarm condition and reset the system.
Clear the signal. (Tamper inputs require a system reset.)
Clear the trouble condition.
Enable or remove the disabled device.
Press <Alarm Activate> or <System Reset>.
Table 2 Descriptions of System Status Indicator LEDs
Unimode 400 Operations PN 50709:A 10/20/97 3
2. Using the Control Panel Control Keys
Control Keys
The control panel provides five control keys, Acknowledge/Step, Alarm Silence, Alarm Activate, System Reset, and Lamp Test.
Acknowledge Step Use the <Acknowledge/Step> key to respond to new alarm or
trouble signals. Pressing <Acknowledge/Step> causes the control panel to do the following:
silence the control panel sounder;
change all indicators from flashing to steady;
send an Acknowledge message to the history file, an optional printer, and an optional ADT-LCD-80; and
send a signal to silence the sounder on the ADT-LCD-80 and ACS annunciators.
You can also press the <Acknowledge/Step> key to display multiple alarms or troubles. If more than one alarm or trouble exists, the control panel displays the next alarm or trouble for 3 seconds (or until you press <Acknowledge/Step>), then displays the next alarm or trouble.
Alarm Silence Use the <Alarm Silence> key to silence the control panel sounder as
well as sounders connected to Notification Appliance Circuits. Pressing <Alarm Silence> causes the control panel to do the following:
turn off the control panel sounder;
turn off all silenceable output circuits;
light the Alarm Silenced LED; and
send an Alarm Silenced message to the history file, optional printer, and an optional ADT-LCD-80.
Alarm Activate Use the <Alarm Activate> key to test notification appliances. Press
and hold the Alarm Activate switch for 2 seconds (to prevent accidental activation). The control panel does the following:
turns on all silenceable NACs;
turns off the Alarm Silenced LED; and
sends a Manual Evacuate message to the history file, optional printer, and an optional ADT-LCD-80.
System Reset Use the <System Reset> key to reset the control panel. Press <System
Reset> and the control panel does the following:
turns off all alarm-activated M500CH modules and NAC circuits;
breaks resettable power to four-wire detectors; and
sends an All Systems Normal message to the history file, optional printer, and an optional ADT-LCD-80.
Any alarm or trouble that exists after a System Reset reactivates NACs, control outputs, and panel audio and visual indicators.
Lamp Test Use the <Lamp Test> key to test the control panel LEDs and sounder.
Press and hold <Lamp Test> and the control panel does the following:
lights all control panel LEDs;
turns on the control panel sounder; and
lights all segments of the LCD display.
4 Unimode 400 Operations PN 50709:A 10/20/97
3. Operating Modes
Normal Operation
The system operates in Normal mode when no alarms or troubles exist. In Normal mode, the control panel displays a system message as follows:
YOUR CUSTOM FORTY CHARACTER MESSAGEHERE ALL SYSTEMS NORMAL11:30A TUE 02/11/97
Figure 3 All Systems Normal Message
In Normal mode, the control panel does the following functions at regular intervals:
Polls all Signaling Line Circuit (SLC) devices and the four NACs to check for valid replies, alarms, troubles, circuit integrity, and so on.
Checks power supply troubles and batteries every 10 seconds.
Sends a supervisory query on the ADT-LCD-80 and verifies proper response.
Refreshes the LCD and the optional ADT-LCD-80 display and updates time.
Scans the keypad for a System Reset or an Enter key press.
Performs a detector automatic test operation.
Tests system memory.
Note: M500CH modules report both open and short circuit messages.
Trouble Operation
The system goes into Trouble mode when the control panel detects an electrical or mechanical fault. With no alarms, a control panel in Trouble mode does the following:
Produces a pulsed audible tone;
The System Trouble LED flashes;
The trouble relay activates (MPS-400, TB5); and
Sends a message to the LCD display, an optional ADT-LCD-80, an optional printer, and the history file.
Figure 4 shows a typical Trouble message:
Type of event (trouble)
TROUBL PULL STATION I.C.U. WEST WING Z1 INVALID REPLY 11:45PM TUE 02/11/97
Software zone assigned (Zone 1)
Figure 4 Trouble Message
1. Press <Acknowledge/Step> to silence the panel sounder and switch the System Trouble LED from flashing to steady—regardless of the number of troubles, alarms, and supervisory signals.
Type of device
Custom descriptor for this device location
Time and date
Type of trouble
2. Pressing <Acknowledge/Step> while at least one new alarm or trouble exists, causes the control panel to send an Acknowledge message to the history file and an optional printer.
Unimode 400 Operations PN 50709:A 10/20/97 5
3. Operating Modes Fire Alarm
If the trouble clears (before or after pressing <Acknowledge/Step>), the control panel sends a Clear Trouble message to the printer. Figure 5 shows a sample Trouble Message:
TROUBL CONTROL MODULE ADDRESS 21 Z00 OPEN CIRCUIT 08:10A 08/20/95 M21 TROUBL CONTROL MODULE ADDRESS 22 Z00 OPEN CIRCUIT 08:12A 08/20/95 M22
Figure 5 Sample Trouble Message
If all troubles clear and no supervisory or fire conditions exist, the control panel does the following:
Returns to Normal mode;
Sends an “All Systems Normal” message to the LCD display, the history file, an optional ADT-LCD-80, an optional printer; and
Restores troubles automatically even if troubles are not acknowledged.
Pressing <Alarm Silence> when only troubles exist, gives the same result as pressing <Acknowledge/Step>. The Alarm Silenced LED does not light unless an alarm exists in the system.
If multiple trouble conditions exist in the system, the LCD and optional ADT-LCD-80 displays automatically step through each trouble event every 3 seconds in the following order:
1. Alarms, in order of address;
2. Supervisory, in order of address; or
3. Troubles, in order of address.
Press <Acknowledge/Step> and the display stops on the current trouble event for 1minute. Press <Acknowledge/Step> to continue.
Fire Alarm
The system goes into Fire Alarm mode when the control panel detects a fire alarm. During Fire Alarm mode, the control panel does the following:
Produces a steady audible tone;
Activates the System Alarm relay (MPS-400, TB3) and flashes the System Alarm LED;
Displays Alarm in the status banner on the LCD display;
Latches alarms so they cannot clear until the alarm initiating device returns to its normal condition and the operator resets the control panel;
Initiates any Control-by-Event actions;
Starts timers (such as Silence Inhibit, Auto Silence); and
Activates the general alarm zone (Z00).
Status banner ALARM
ALARM:PULL STATION I.C.U. WEST WING VISITORS LOUNGE 11:55PM TUE 02/11/97
Figure 6 Fire Alarm Display
6 Unimode 400 Operations PN 50709:A 10/20/97
Supervisory Signal 3. Operating Modes
Supervisory Signal
Note: You can program Supervisory signals as Tracking or Latching.
Supervisory signals cause the control panel to do the following:
Produce a warbling audible tone;
Turn on the Supervisory relay (MPS-400, TB4) and flash the Supervisory LED;
Display “Active” in the status banner on the control panel; and
Turn off the panel sounder for all Silenced alarms.
Status banner ACTIVE
ACTIVE TAMPER I.C.U. WEST WING VISITORS LOUNGE 11:55PM TUE 02/11/97
Figure 7 Typical Supervisory Signal Display
Non-Alarm Point Operation
Non-Alarm points are M500M addressable modules that activate Control-by-Event. These points do not activate the System Alarm LED or the panel sounder. Non-Alarm points use three type codes: Non-Fire, Hazard Alert, and Fire Control.
Type Code Does this... Used for...
Non-fire (Tracking)
Hazard Alert (Latched)
Fire Control (Tracking)
Activates Control-by-Event only. Energy management or other
non-fire situations.
Sends a message to the LCD display, history file, printer, and ADT-LCD­80 (status – Active), and overrides code selection for NACs, regardless of the zone F8 coding selection.
Sends messages to the LCD, history file, printer and ADT-LCD-80.
Monitoring critical processes or other hazardous situations, such as a tornado.
Air handler shutdown, intended to override automatic fire functions.
Table 3 Non-Alarm Points
Trouble Monitor Point Operation
Trouble Monitor-type M500M modules monitor remote power supplies or other external equipment. These types of M500M modules operate like troubles—but with the following differences:
The LCD display status banner displays “Active”;
The type code is “Trouble Mon”;
The modules latch—until the troubles are returned to normal condition and an operator resets the control panel; and
M500M modules can have Control-by-Event.
Unimode 400 Operations PN 50709:A 10/20/97 7
3. Operating Modes Notification Appliance Circuit (NAC) Operation
Notification Appliance Circuit (NAC) Operation
The four NACs (TB7-TB10 on the MPS-400) have Control-by-Event and trouble functions like M500CH addressable modules on the SLC loop. NAC circuits differ from M500CH modules in the following ways:
Addresses (last three characters in LCD field) are B01, B02, B03, or B04;
The default type code field is “Bell Circuit”; and
Control panel NACs, except those controlled with M500CH modules, can be used for coded functions (March Time, California Code, Temporal, and Two-stage).
Control-By-Event Operation
Note: Zones F0-F9 are reserved for special functions such as cross-zoning (refer to the Unimode400 Programming Manual).
Control-by-event (CBE) control is done through 99 software zones. Each input point (detector, M500M) and output point (M500CH, NAC) can be programmed to list up to five software zones. Non-Alarm or Supervisory points do not activate software zone Z00 (general alarm). You can list zone Z00 for output points, but you do not need to list Z00 for input points.
Input and output devices with listed software zones work as follows:
Inputs – When an input device (detector or M500M) activates, so do all software zones listed to the input device.
Note: Refer to Appendix A for more information about releasing functions.
Outputs – When a software zone activates, the output device turns on.
CBE Example Detector D102 lists zone Z05. B01 lists zone Z05 and zone Z07.
1. Detector D102 activates.
2. Zone Z05 activates.
3. B01 activates.
Releasing Functions
Overview Zones R0-R9 are reserved for releasing zones—providing up to ten
independent releasing operations. Each releasing zone includes the following options:
Option Description
Cross-zoning Select one of three types of cross-zoning. Refer to Table 5. Delay Timer Select a 0–60 second delay before activating a zone. Abort An abort switch-type code used to abort activation of a zone. Manual Release Allows immediate zone activation by overriding the abort function,
cross-zone function, and delay timer.
Man. Rel. Delay Same as Manual Release, except releasing occurs 10 seconds after
“Man. Rel. Delay” is activated.
Soak Timer Automatically shuts off the releasing device. Select 0001-9999 seconds
for a Soak Timer or 0000 seconds for no Soak Timer.
Second Shot Reactivates release output after the Soak Timer times out.
Table 4 Cross Zoning Options
8 Unimode 400 Operations PN 50709:A 10/20/97
Releasing Functions 3. Operating Modes
Using Cross Zoning Options Cross Zoning lets you program the control panel to
activate a releasing zone after two initiating devices are tripped. (If not using Cross Zoning, set CROSS= to N.) Table 5 contains a summary of the types of cross zoning and the conditions for activating a releasing zone.
Type Activates when...
Y Two or more detectors, all mapped to one of the ten releasing zones (R0-R9), are
tripped.
Z Two or more detectors, mapped to two different software zones and one of the ten
releasing zones (R0-R9), are tripped.
H At least one smoke detector and at least one heat detector, all mapped to one of the
ten releasing zones (R0-R9), are tripped.
Table 5 Cross Zoning Types
Note: Only the first non-special zone listed in the zone map is used to determine Cross=Z.
Cross Zoning Example Table 6 lists examples of devices mapped to releasing zones
(ZR1 stands for Releasing Zone 1).
Device Address Device Type Zone Mapping
D101 Detector Smoke ZR1 Z01 D102 Detector Smoke ZR1 Z01 D103 Detector Smoke ZR1 Z02 D104 Detector Heat ZR1 Z02 B01 Output Circuit (Rel Ckt) ZR1
Table 6 Devices Mapped to Releasing Zones
The following explanations apply to the examples listed in Table 6:
Cross=N An alarm from any detector activates the releasing circuit.
Cross=Y An alarm from any two detectors activates the releasing circuit.
Cross=Z Release requires the activation of two detectors mapped to different
• zones: D101 and D102 cannot activate the releasing circuit because both detectors are mapped to Z01; D101 and D103 can activate the releasing circuit because they are mapped to different zones.
Cross=H Release requires activation of heat detector D104 and one smoke
• detector (D101, D102, or D103).
Unimode 400 Operations PN 50709:A 10/20/97 9
3. Operating Modes Intelligent Detector Functions
Intelligent Detector Functions
Note: For instructions on selecting Intelligent Detector Functions, refer to the Unimode400 Programming Manual.
Table 7 contains descriptions for intelligent detector functions used with the control panel.
Function Description
Analog Display The control panel reads and displays analog information from the
198 analog detectors. The display shows the percent of the alarm threshold for each detector.
Sensitivity Adjust Nine selections for manually setting intelligent detector alarm
levels within the UL range. If using Ionization detectors in duct applications, set Sensitivity Adjust to Level 1.
Day/Night Sensitivity Operation
Maintenance Alert When compensation reaches the limit of the amount of drift
Automatic Test Operation
Type Code Supervision
LED Control Operation
Alarm Verification and Counter Operation
You can program the system to automatically force smoke detectors to minimum sensitivity during the day. Refer to “Time Control Zones” on page 19.
compensation that can be safely applied, the control panel reports a special trouble condition, per national fire code standards. This condition also activates if the detector remains at very high or very low measured air levels for an extended time.
The control panel performs an automatic test of each detector every 256 minutes. Failure to meet the test limits causes an AUTO TEST Fail trouble.
The control panel monitors hardware device type codes (500 Series detectors, 200 Series detectors, 3251 detectors, M500M, and M500CH) for each installed device at regular intervals (an interval can take up to 30 minutes for full capacity system). If a mismatch of type compared to the program occurs, the control panel generates a point trouble labelled Invalid Type.
A global program selection to prevent detector LEDs from blinking during normal operation. A typical application is a sleeping area where a blinking light can distract people. As a standard function, the control panel allows all LEDs to turn on in alarm.
The control panel performs alarm verification on programmed 500Series, 200 Series, and 3251 intelligent smoke detectors. The verification time is a global program selection of 0–30 seconds. Each detector includes a verification counter, which displays the number of times that a detector entered verification but did not time-out to alarm. The counter increments to 99 and holds.
Table 7 Intelligent Detector Functions
10 Unimode 400 Operations PN 50709:A 10/20/97
Loading...
+ 30 hidden pages