ADTRAN TRACER User Manual

Page 1
61280004L1-1A-1A PAGE I
TRACER USERS MANUAL
Page 2
PAGE II 61280004L1-1A-1A
Page 3
61280004L1-1A-1A PAGE III
INSTALLATION
CONTENTS
PAGE
SECTION 1TRACER DESCRIPTION ..................................................... 1
CHANNEL SELECTION.................................................3
FORWARD ERROR CORRECTION ....................................4
E1 OPERATION .......................................................4
TRACER SYSTEM CONFIGURATION ..................................6
Baseband Processor or BBP........................................ 6
VT-100 RS-232 Interface ............................................. 8
Alarm Contacts ............................................................. 8
IF Signal ....................................................................... 8
AC/DC Power................................................................ 9
Controls and Indicators ............................................... 9
Radio Frequency Convertor or RFC ........................... 11
Antenna Selection ...................................................... 13
SECTION 2INSTALLATION ..............................................................15
UNPACK, INSPECT ........................................................15
RACK-MOUNTED RFC CONFIGURATION .........................15
MAST-MOUNTED RFC CONFIGURATION .........................15
INSTALLATION ..............................................................16
LOCATION AND MOUNTING.........................................16
POWER REQUIREMENTS ........................................... 16
GROUNDING ......................................................... 16
E1 INTERFACE ......................................................18
LINK PLANNING ...........................................................19
SETTING THE TRANSMITTER POWER ...................................22
SETTING THE RFC FREQUENCY PLAN ................................23
CONNECTING THE BBP AND THE RFC .............................. 24
APPLYING POWER ........................................................25
AUTOMATIC BBP FREQUENCY PLAN .................................. 25
Page 4
PAGE IV 61280004L1-1A-1A
SPREADING CODE ........................................................25
CO-LOCATING MULTIPLE 2.4 GHZ SYSTEMS .......................25
ANTENNA ALIGNMENT .................................................... 26
RF LOW ...................................................................27
REMOTE BERT ..........................................................27
ALARM CONTACTS ........................................................27
SECTION 3OPERATION ................................................................29
VT-100 USER INTERFACE .............................................29
RS-232 INTERFACE .................................................... 29
CABLE CONNECTIONS ....................................................29
PASSWORD ................................................................30
MAIN MENU SELECTIONS ............................................... 31
SECTION 4TROUBLESHOOTING .......................................................37
GENERAL .................................................................. 37
PROBLEM DESCRIPTIONS AND RECOMMENDED ACTIONS ........... 38
TROUBLESHOOTING USING THE FRONT PANEL INDICATORS ..... 38
TROUBLESHOOTING USING THE VT-100 USER INTERFACE..44
SECTION 5SPECIFICATIONS ........................................................... 49
RF TRANSMITTER ........................................................49
RF RECEIVER............................................................. 49
FREQUENCY PLANS .......................................................49
SPREAD SPECTRUM DATA PUMP ......................................49
E1 INTERFACE SPECIFICATIONS ........................................ 50
USER INTERFACE ......................................................... 50
RS-232 TERMINAL INTERFACE........................................ 50
MECHANICAL & ENVIRONMENTAL .......................................50
POWER.....................................................................51
GLOSSARY .............................................................................55
APPENDIX ACABLE CONNECTIONS ................................................... A-1
Page 5
61280004L1-1A-1A PAGE V
Page 6
PAGE VI 61280004L1-1A-1A
Page 7
61280004L1-1A PAGE 1
SECTION 1 TRACER DESCRIPTION
INTRODUCTION
The Single E1 version of Tracer provides single E1 transport via a
2.4 GHz, direct sequence, spread spectrum microwave link. The transmitter output power is 20 dBm maximum while the receiver sensitivity is -91 dBm or better. System performance is determined, in part, by the engineering of the microwave link. Each Tracer radio is comprised of two components - the baseband processor and the radio frequency converter (RFC). The E1 interface (G.703, G.704 compliant) is provided on the back of the baseband processor, which is mountable in a 515 mm rack. The radio frequency converter is rackmountable adjacent to the baseband processor or mastmountable in a weatherproof enclosure, located up to 110 meters apart, using RG-8 style coax. A single coaxial cable connects the baseband processor (via a Type N connector) to the RFC and another coaxial cable connects the RFC to the antenna (via a Type N connector).
Page 8
PAGE 2 61280004L1-1A SECTION 1
APPLICATIONS
Any application that would typically use metallic E1 as a transport can use the Tracer instead. The figure below illustrates a typical application.
Antenna Antenna
RF Cable
Rackmount RFC
VT-100
RS-232
Terminal
E1, Mastmounted RFC
TRACER Baseband Processor
E1
E1 Equipment
IF Cable
RF Cable
TRACER Baseband Processor
E1
E1 Equipment
E1, Rackmounted RFC
Figure 1-1. Typical Application
The Tracer can be used in any application requiring that data be shared at a high rate of speed. In addition to telephony applications, Tracer can be used in data communications such as inter-networking, video conferencing, and telemetry.
SPREAD SPECTRUM
Spread spectrum is a form of communication in which the bandwidth of a message signal is intentionally increased or “spread.” There are two methods of spreading -- frequency hopping and direct sequence. Tracer employs direct sequence spread spectrum.
Rackmount RFC
Page 9
61280004L1-1A PAGE 3
T
RACER DESCRIPTION
DIRECT SEQUENCE
A direct sequence transmitter spreads the signal by mixing the data with the output of a pseudorandom number generator which changes state at a rate higher than the data rate. This rate is called the “chipping” rate. The Tracer chipping rate is twelve times the data rate.
CODING
Many different pseudorandom sequences exist. The sequences are called pseudorandom because, although they appear noise­like, they are determinant and repeat after a specific number of chips. The longer a code is, the better correlation characteristics it possesses. These traits allow multiple spread spectrum systems to operate in the presence of one another with minimal interference if they are operating with different sequences. The Tracer allows the selection of one of ten different 120-bit long sequences.
CHANNEL SELECTION
There is 83.5 MHz of spectrum in the 2.4 GHz band in which Tracer operates. A Tracer system fully uses the available bandwidth
-- transmitting in one half and receiving in the other. The figure below illustrates the bandwidth division.
2400 MHz
2441 MHz
2483.5 MHz
Figure 1-2. Bandwidth Division
Page 10
PAGE 4 61280004L1-1A SECTION 1
The transmitter at one end of a link will transmit in the lower half of the spectrum. Consequently the receiver at the other end will receive in the lower half of the band and transmit in the upper half. Thus, a system will operate in one of two frequency plans -
- transmit in the upper and receive in the lower or vice versa. These two plans are called Plan A and Plan B. One end of a path will be on Plan A and the other will be on Plan B. Shipment of a link will consist of an A and a B unless specified otherwise.
FORWARD ERROR CORRECTION
With the addition of overhead data, error detection and correction capability can be added to a data stream. Error correction can be accomplished by allowing the receiver to request the re­transmission of an errored block once detected. The Tracer, on the other hand, implements forward error correction (FEC) which adds enough overhead data for the receiver to detect and correct errors in the data stream. This capability comes at the cost of bandwidth. The addition of FEC decreases the required signal­to-noise (S/N) ratio by approximately 5.5␣ dB to achieve a given bit error rate (BER).
E1 INTERFACE
The E1 interface conforms to the ITU G.703 and G.704 electrical and signaling interface recommendations. Two interfacing configurations are allowed - a pair of BNC coaxial connectors or a 15 pin sub-D connector and RJ48 connector.
The coaxial connection provides a 75 unbalanced connection. The shield of the TX coaxial connection is attached to earth ground. A strap is provided to optionally connect the shield of the RX coaxial connection to ground as described in G.703. The 15 pin sub-D and RJ48 connection provides a 120 balanced connection.
Page 11
61280004L1-1A PAGE 5
TRACER DESCRIPTION
Tracer SYSTEM CONFIGURATION
A Tracer system is composed of three major subsystems -- a baseband processor, a radio frequency convertor, and an antenna. The following section describes the system components.
BASEBAND PROCESSOR OR BBP
The baseband processor or BBP is a 1-U, 515 mm rackmountable unit. This unit provides the system electrical interfaces, user controls and indicators, and performs the spread spectrum processing for the system. The front panel provides all of the electrical interface points -- E1 interface, VT-100 compatible terminal, alarm contacts, IF signal, and DC power (from facility or optional AC adapter).
The BBP front and rear panels are illustrated in the figures below.
E1
ALM
TEST
LBK
CVCRC
POWER
LOS/OOF
TRACER
FREQ
SYSTEM
PLAN APLAN A
RF LOW
PLAN BPLAN B
LINK DOWNLINK DOWN
Figure 1-3. BBP
IF MAJ
E1
G.703
75 OHM
RS232
RXTX
MIN DC POWER
NOCOM NC NO COMNC
Figure 1-4. BBP Rear Panel
Page 12
PAGE 6 61280004L1-1A SECTION 1
A block diagram of the BBP is shown in the figure below.
µ
Σ
Figure 1-5. BBP Block Diagram
VT-100 RS-232 INTERFACE
An RS-232 interface is provided via a 25-pin D connector for attaching a VT-100 compatible terminal. The active signals used on this interface are listed below
Signal Name Pin Number Source
Receive Data ...................2 ................ Terminal/Modem
Transmit Data .................3 ................ Tracer
Request to Send .............. 4 ................ Terminal/Modem
Clear to Send ..................5 ................ Tracer
Data Set Ready ................ 6 ................ Tracer
Signal Ground ................ 7
Page 13
61280004L1-1A PAGE 7
TRACER DESCRIPTION
The management system allows the E1 interface to be provisioned. The line code can be selected as AMI or HDB3. The signaling can be selected as channel associated signaling (CAS) or common channel signaling (CCS). Alarm conditions can also be monitored. The management system will report the following alarms on the E1 interface:
• Loss of signal
• Bipolar violation
• CRC error
• Framing error
• Remote alarm
A seven-day error history of the E1 interface and radio link is also provided. Fifteen-minute histories are provided for the most recent eight hours of operation.
The status of the microwave link can also be monitored from the management system. The transmitter power setting as well as an indication of the received microwave signal level are provided.
ALARM CONTACTS
Two classes of alarm, MAJOR and MINOR, are provided. A MAJOR alarm is signaled if, for any reason, the microwave path is not operational. A MINOR alarm is signaled when the data path is operating, but impaired. A minor alarm will be activated when an alarm is sensed on the E1 interface or when the received RF signal level falls below approximately -80 dBm. Both normally-open and normally-closed contacts are provided for each alarm class. Access is provided by a six-position terminal strip on the front of the baseband processor.
IF SIGNAL
The Type N Connector provides the interface point between the baseband processor and the radio frequency converter (RFC). This connection provides the signal, power, and configuration information to the RFC. A coaxial cable (ADTRAN part number 3125RF027@A) is provided for connecting the BBP to the RFC for the rackmount model. Cable for connecting the BBP to a mastmount RFC must be provided by the customer after the length of the cable has been determined.
Page 14
PAGE 8 61280004L1-1A S
ECTION 1
AC/DC POWER
The unit receives power via one of two connectors. Power for the entire system is provided by these interfaces. The 3 pin circular DIN connector is provided to connect an ADTRAN supplied desktop AC adapter providing 24 volts DC. The three-pin terminal block allows the connection of any DC power source providing between 21 and 60 volts DC. The power consumption of the entire system is approximately 30 watts.
CONTROLS AND INDICATORS
The system may be configured via the front panel, which is accessible behind a drop-down panel on the right half of the BBP. The front panel is illustrated in the figures below.
TEST
POWER
E1
CVCRC
LOS/OOF
ALM LBK
PLAN A PLAN B
FREQ
SYSTEM
RF LOW LINK DOWN
TRACER
Figure 1-6. BBP Front Panel with Door Closed
Figure 1-7. BBP Front Panel with Door Open
Page 15
61280004L1-1A PAGE 9
TRACER DESCRIPTION
As a rule, a green LED indicates a good situation, a red LED indicates an error situation, and a yellow LED indicates a configuration option. LEDs indicating overall system integrity are listed below.
Self Test ........................ Blinking red if the self-test has completed
and failed; Solid red if self-test is in progress or did not complete
Power ........................... Green if DC voltage is applied
The LEDs associated with the E1 interface are listed below.
CV/CRC ....................... Red if the incoming E1 stream contains code
violations, or a CRC error
LOS/OOF ..................... Red if there is no signal present at the E1
interface or if framing synchronization is lost
Loopback ..................... Solid yellow if the E1 interface is in local
line loopback. Blinking yellow if the E1 interface is in link loopback.
ALM ............................. Solid red if an AIS is detected at the
incoming E1, blinking red if a remote alarm signal is found
The functions of the LEDs which relate system configuration information are listed below.
Frequency Plan A ........Yellow if frequency plan A is selected
Frequency Plan B ........ Yellow if frequency plan B is selected
Remote Test Active ...... Yellow if the remote test is active
Remote Test Fail .......... Red if the remote test failed
The LEDs that indicate error conditions in the spread spectrum data pump and RFC are listed below. All of these LEDs are visible through the front panel. Any one of these LEDs indicates and error condition that precludes system operation.
Link Down................... Red if the RF link is not operational
E1 interface will transmit AIS on the affected E1 to indicate an error
RF Low ........................ Red if the received RF carrier level is
below -80 dBm.
Page 16
PAGE 10 61280004L1-1A SECTION 1
The controls available from the control panel are listed below.
Name Function
Reset ............................ Reset the system
LBK .............................. Toggles E1 between normal and local line
loopback modes
CRC4 ON .................... Affects the E1 Performance Monitoring
characteristics. ES (errored second) is one or more CRC4 errors or Loss of Frame. SES (severely errored second) is more than one Loss of Frame, one or more Loss of Receive Signal or more than 805 CRC4 errors.
CRC4 OFF ................... Affects the E1 Performance Monitoring
characteristics. ES (errored second) is one or more BPV (bipolar violations) for an AMI configured circuit or one or more Code Errors for an HBD3 configured circuit. SES (severely errored second) is Loss of Signal or Frame, 805 or more BPV
(bipolar violations) or Code Errors.
CAS ..............................Selects Channel Associated Signalling
CCS .............................. Selects Common Channel Signalling
HDB3 ........................... Selects HDB3 Line Coding
AMI .............................. Selects AMI Line Coding
Remote Test ................. Initiate a remote test across the RF link
The monitor points provided on the front panel of the system are described below.
EYE I ............................ Demodulated received baseband output
EYE Q .......................... Demodulated received baseband output
EYE CLK...................... Recovered clock for observing EYE pattern
RSSI ............................. DC voltage indicating strength of the
received signal at the antenna
+5 ................................. System 5 volts
-5.................................. System -5 volts
+12 ............................... System +12 volts
-12................................ System -12 volts
RF PWR ....................... DC voltage supplying RF power
GND ............................ System ground
Page 17
61280004L1-1A PAGE 11
TRACER DESCRIPTION
NON-VOLATILE MEMORY
The Tracer system contains non-volatile memory to retain certain configuration settings. These settings include:
Frequency plan Chipping code (if set from VT-100) Password Password enabling Site name E1 line coding (if set from VT-100) E1 framing (if set from VT-100)
BUILT-IN TESTS
The Tracer has several features to aid in site setup and later debugging. These diagnostics include E1 loopbacks and a link test with BERT (Bit Error Rate Test) data. A link test is performed by pressing the test button. The remote unit will then send a pseudorandom data pattern and the local end will compute a BER. After the conclusion of the test, the remote end will automatically be instructed to terminate the pattern generation. If any bit errors are introduced, the Remote Test Fail LED will illuminate.
Page 18
PAGE 12 61280004L1-1A SECTION 1
RADIO FREQUENCY CONVERTER OR RFC
The radio frequency converter (RFC) provides the radio frequency (RF) interface between the baseband processor and the antenna. The RFC is partitioned, functionally, into two major components
- the transmitter and the receiver.
The major connections illustrated are transmit signal, receive signal, and the IF signal connection.
The RFC unit is enclosed in a metal enclosure approximately
26.7cm x 14cm x 2.5cm and is mounted in a 515 mm rackmountable housing or mastmountable, weatherproof enclosure. The RFC is illustrated below.
RSSI
GND
TX-PWR
RX
IF TX
Figure 1-8. RFC Module
Three SMA connectors, located on the RFC module, provide RF and IF connection points. A test point is provided for monitoring the received signal strength indicator (RSSI). The voltage (relative to the GND test point) present on this test point represents the level of the received signal. This signal is used to align the antenna when installing the system and to verify the link is performing as designed. Another test point is provided to monitor the transmitter output power during system configuration. The only connections that must be made in the field are a coax connection between the baseband processor and the RFC and a coax connection between the RFC and the antenna. These connections require male, type N coax connectors.
The IF connector provides the connection between the baseband processor and the rackmounted or mastmounted RFC. (An 8” IF cable [ADTRAN part # 3125RF027@A] is provided for rackmount systems). The TO ANTENNA connection provides the connection between the RFC and the antenna.
Page 19
61280004L1-1A PAGE 13
TRACER DESCRIPTION
RX
TX
RF1
SAW
2018 2058
PA
2321 2281
LPF
333
Splitter
AGC
IF
Splitter
AGC
RF2
Figure 1-9. RFC Block Diagram
The RFC module is enclosed in either an ETSI-compliant rackmount housing, or a weather-tight enclosure suitable for mastmounting near the antenna for enhanced system performance. The RFC mastmount and rackmount housings are illustrated below.
Figure 1-10. Front and Rear of Rackmount RFC Housing
WARNING
Housing Assembly and Guide
Mounting Clearances
for Mounting Bracket
Holes
Figure 1-11. Mastmount RFC Housing
Page 20
PAGE 14 61280004L1-1A
ANTENNA SELECTION
Tracer is intended to be coupled with an antenna that is directional (thus providing signal gain). There are several reasons for this requirement:
• Tracer operates in point-to-point applications so omnidirectional
antennas cannot be used.
• The low power transmitter is intended to be used with a high-
gain antenna for long links.
• Directional antennas minimize the interference that a site is
susceptible to and also minimizes the site’s interference to other sites.
The antenna requirements are listed below.
Minimum gain ............. 15 dBi
Minimum return loss .. 15 dB
Connector.................... N-type
Impedance ................... 50
Page 21
61280004L1-1A PAGE 15
SECTION 2 INSTALLATION
UNPACK, INSPECT
Carefully inspect the Tracer for any shipping damages. If damage is suspected, file a claim immediately with the carrier then contact ADTRAN Customer Service. If possible, keep the original shipping container for use in shipping the Tracer back for repair or for verification of damage during shipment.
Before beginning installation, verify that all of the following components are present.
RACKMOUNTED RFC CONFIGURATION:
Provided by ADTRAN --
• Baseband processor
• Rackmounted RFC
• BBP to RFC IF interconnect cable
Provided by customer --
• Antenna feedline cable
• Antenna and mounting hardware
• VT-100 terminal and RS-232 interface cable (optional)
• 21 to 60 volt DC power source (available from ADTRAN), either polarity referenced to ground
MASTMOUNTED RFC CONFIGURATION:
Provided by ADTRAN --
• Baseband processor
• Mastmounted RFC
Page 22
PAGE 16 61280004L1-1A SECTION 2
Provided by customer --
• E1 interface cables
• Antenna feedline cable
• Antenna and mounting hardware
• BBP to mastmounted RFC IF interconnect cable
• VT-100 terminal and RS-232 interface cable (optional)
• 21 to 56 volt DC power source (available from ADTRAN), either polarity referenced to ground
INSTALLATION
LOCATION AND MOUNTING
Install the Tracer in a location that requires minimal antenna feedline length (the loss in this cable directly affects overall system performance). The BBP is designed to be mounted in a rack, above the RFC. Although no space is needed between the units, certain regulations may require at least 19.05 mm (.75") of space above and below the BBP.
POWER REQUIREMENTS
The Tracer can operate from a supply between 21 and 56 volts DC, with either polarity referenced to ground, and consumes 30 watts. Amperage is determined by dividing the wattage (30) by the input voltage (i.e., 30 watts/48 volts = .625 amps),
Page 23
61280004L1-1A PAGE 17
NSTALLATION
I
GROUNDING
The following grounding instructions are derived from the Underwriters’ Laboratory UL 1459 Standard for Safety: Telephone Equipment dated September 20, 1993.
An equipment grounding conductor that is no smaller in size than the ungrounded branch-circuit supply conductors is to be installed as part of the circuit that supplies the product or system. Bare, covered, or insulated grounding conductors are acceptable. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green, or green with one or more yellow stripes. The equipment grounding conductor is to be connected to ground at the service equipment.
The attachment-plug receptacles in the vicinity of the product or system are all to be of a grounding type, and the equipment grounding conductors serving these receptacles are to be connected to earth ground at the service equipment.
A supplementary equipment grounding conductor shall be installed between the product or system and ground that is in addition to the equipment grounding conductor in the power supply cord.
The supplementary equipment grounding conductor shall not be smaller in size than the undergrounded branch-circuit supply conductors. The supplementary equipment grounding conductor shall be connected to the product at the terminal provided, and shall be connected to ground in a manner that will retain the ground connection when the product is unplugged from the receptacle. The connection to ground of the supplementary equipment grounding conductor shall be in compliance with the rules for terminating bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/ NFPA 70. Termination of the supplementary equipment grounding conductor is permitted to be made to building steel, to a metal electrical raceway system, or to any grounded item that is permanently and reliably connected to the electrical service equipment ground.
Bare, covered, or insulated grounding conductors are acceptable. A covered or insulated grounding conductor shall have a continuous outer finish that is either green, or green with one or more yellow stripes.
Page 24
PAGE 18 61280004L1-1A S
ECTION 2
The supplemental equipment grounding terminals are located on the rear of the BBP adjacent to the power connectors and on the rear of the rackmounted RFC. The mastmounted RFC has a ground lug mounted on the installation bracket.
E1 INTERFACE
The E1 interface conforms to the ITU G.703 and G.704 electrical and signaling interface recommendations. Two interfacing configurations are available:
• A 75 unbalanced BNC coaxial connector.
• A 120 balanced 15 pin connector / RJ 48 with the pinouts shown
below.
15 Pin RJ-48 Pin Function Pin Function
1 E1 Out ring 1 E1 Out ring 2 Frame ground 2 E1 Out tip 3 E1 In ring 3 N.C. 4 Frame ground 4 E1 In ring 5 N.C. 5 E1 In tip 6 N.C. 6 N.C. 7 N.C. 7 N.C. 8 N.C. 8 N.C. 9 E1 Out tip 10 N.C. 11 E1 In tip 12 N.C. 13 N.C. 14 N.C. 15 N.C.
Page 25
61280004L1-1A PAGE 19
NSTALLATION
I
The BNC configuration interface provides a 75 unbalanced connection. The shield of the OUT coaxial connection is attached to earth ground. A jumper is provided to optionally connect the shield of the INPUT coaxial connection to ground as described in G.703. This jumper is located on the inside of the E1 interface board, between the two BNC connectors. The E1 module must be removed to access this option.
The 15-pin / RJ-48 configuration interface provides a 120 balanced connection.
Three loopback functions are provided for diagnostic capability. The local line loopback loops the incoming E1 signal back out at the E1 framer. The remote link loopback loops the E1 data back to the local end from the remote end. This allows a BERT to be run across the microwave link and back. The local link loopback allows the local unit to loop E1 data back towards the remote end. The available loopback functions are illustrated below.
E1
Local
RF Link21 3
Remote
Figure 2-1. E1 Loopback Locations
E1
Page 26
PAGE 20 61280004L1-1A SECTION 2
LINK PLANNING
I M P O R T A N T
The appropriate transmitter power must be calculated as part of the link planning.
The factors that must be taken into account when planning a link are optimal received signal level, transmitter power, antenna feedline loss (each end), antenna gain (each end), free space path loss, and required fade margin.
I M P O R T A N T
The optimal signal level for the receiver is -60 dBm.
ANTENNA FEEDLINE LOSS
Feedline loss is a function of feedline type and length. Feedline loss per 30.48 meters for several types of coax at IF and RF frequencies is detailed in the table below. The IF loss applies to BBP/RFC interconnection, and the RF loss applies to RFC/antenna interconnection. Cable manufacturers’ specifications may vary.
IF Loss/30.48 m RF Loss/30.48 m
Cable (in dB) (in dB)
RG58 ......................... 5.7 ................................ 80
RG8 (air)................... 2.7 ................................ 20
RG8 (foam) ................. 2 ................................... 9
1
/4" Waveguide ......... 1.42 .............................. 5.91
3
/8" Waveguide ......... 1.25 .............................. 5.76
1
/2" Waveguide ......... 0.81 .............................. 3.83
7
/8" Waveguide ......... 0.44 ............................... 2.2
1
/4" Waveguide ...... 0.33 .............................. 1.62
1
5
/8" Waveguide ...... 0.27 .............................. 1.41
1
Page 27
61280004L1-1A PAGE 21
NSTALLATION
I
ANTENNA GAIN
Best performance will result from the use of a parabolic dish antenna. Antenna gain is determined by the size of the dish, with typical figures detailed below. Dish manufacturers will be able to supply gains for other types of antenna.
Dish Diameter Gain
(in cm) (in dBi)
60 ..................... 21
120 .................... 27
180 .................... 31
243 .................... 33
304 .................... 35
365 .................... 37
PATH LOSS
The free space path loss is given by
Loss(dB) = 96.6 + 20 log10f + 20log10D * 1.609344
where
D is distance in kilometers f is operating frequency in GHz
A tabulation of various path loss is given below.
Link Distance Path Loss (in km) (in dB)
1 ........................... 108
2 ........................... 115
3 ........................... 118
4 ........................... 121
5 ........................... 122
6 ........................... 124
7 ........................... 125
8 ........................... 127
9 ........................... 128
10 ......................... 128
11 ......................... 129
12 ......................... 130
Link Distance Path Loss (in km) (in dB)
13 ......................... 131
14 ......................... 131
15 ......................... 132
16 ......................... 133
17 ......................... 133
18 ......................... 134
19 ......................... 134
20 ......................... 135
21 ......................... 135
22 ......................... 135
23 ......................... 136
24 ......................... 136
Page 28
PAGE 22 61280004L1-1A
INSTALLATION
PATH AVAILABILITY
The availability of a path can be expressed by:
availability = (1 - C x T x 2.5 x 10-6 x f x (D x 1.609344)3 x 10-F
where
C is the climate factor T is the terrain factor f is the frequency in GHz D is the path length in kilometers F is the fade margin in dB
Climate factors are given below.
Climate
Climate Factor
1
Very Dry ..............
Temperate ............1/
Humid .................1/
/
8
4
2
Terrain factors are listed below
Terrain
Terrain Factor
Smooth .................... 4
Average .................... 1
Mountainous ...........
1
/
4
/10
) x 100%
The nominal received signal level is -60 dBm. For help in link planning, use the path loss calculation worksheet below.
- 91 dBm Minimum Signal Power
+ _______ Transmitter Feedline Loss
- _______ Transmitter Antenna Gain
+ _______ Path Loss
- _______ Receiver Antenna Gain
+ _______ Receiver Feedline Loss
+ _______ Required Fade Margin
= _______ (dBm) Transmitter Power Setting
Page 29
61280004L1-1A PAGE 23
ECTION 2
S
SETTING THE TRANSMITTER POWER
The transmitter power is set by way of a two-position, momentary toggle switch on the front panel of the BBP or via the configuration page of the VT-100 interface. The RFC must be attached by way of the IF cable during this operation. Attach an RF power meter to the N-type antenna connector on the RFC, and adjust the power by way of the potentiometer or VT-100 until the desired transmitter power is obtained. For convenience, the transmitter power adjustment should be made before the RFC is installed on the mast.
SETTING THE RFC FREQUENCY PLAN
The frequency plan designates on which frequencies the Tracer transmits and receives. Plan A corresponds to a transmitting (Tx) frequency of 2421 MHz and a receive (Rx) frequency of 2462 MHz. Plan B corresponds to a Tx frequency of 2462 MHz and a Rx frequency of 2421 MHz. Shipment of a link consists of one RFC set to Plan A and the other set to Plan B unless specified otherwise. The RFC plan can, however, be changed in the field if required. This procedure involves configuring the RFC interconnect cables.
For rackmounted systems, do the following to reconfigure the RFC interconnect:
1. Remove the four screws which retain the RFC cover and remove the cover.
2. The RF unit may be identified by following the connection from the port labelled “IF” on the rear of the RFC. This connection terminates at the RF unit. The diplexer may be identified by following the connection from the “Antenna” port on the rear of the RFC. This connection terminates at the diplexer, illustrated in the figure below.
2462
Antenna
PLAN A
2421
Figure 2-2. Diplexer
Page 30
PAGE 24 61280004L1-1A
INSTALLATION
3. Unscrew the cable assemblies from the ports labelled “Tx” and “Rx” on the RFC, and the ports labelled “2421” and “2462” (or “J1” and “J2” on some models) on the diplexer, depending on the frequency Plan (Plan A or Plan B).
4. Unscrew the cable assembly from the port labelled “Antenna” on the diplexer.
5. Remove the four screws from the bottom of the RFC that hold the diplexer in place.
6. Turn the diplexer over revealing the opposite frequency plan (from Plan A to Plan B, or vice versa).
7. Realign the diplexer with the screw holes and replace the four screws that attach it to the bottom of the RFC.
8. Reattach the loose cable assembly (from step 4) to the port labelled “Antenna” on the diplexer.
9. Reattach the cable assemblies from the ports labelled “Tx” and “Rx” on the RFC, and the ports labelled “2421” and “2462” (or “J1” and “J2” on some models) on the diplexer. Cable connections should be aligned to each other as follows.
Plan A Tx = 2421 Rx = 2462
Plan B Tx = 2462 Rx = 2421
10. Replace and secure the RFC cover.
For mastmounted systems, do the following to reconfigure the RFC interconnect:
1. Remove the lid of the mast RFC.
2. Disconnect the three cables attached to the diplexer. The diplexer may be identified by following the antenna connector to the middle connector of the diplexer. Leave the cables in the same positions.
3. Remove the two screws securing the diplexer and rotate the diplexer to reveal the opposite frequency plan label.
4. Reinstall the two screws and reattach the cables in the same positions.
5. Reinstall the lid of the mast RFC.
Page 31
61280004L1-1A PAGE 25 SECTION 2
CONNECTING THE BBP AND THE RFC
The BBP and the RFC are connected by an IF cable, either supplied by ADTRAN (for rackmount assembly) or by the customer (for mastmount assembly). This single connection provides everything the RFC requires. The cable assembly attaches to the ports labeled “IF” on the BBP and the RFC.
APPLYING POWER
If the ADTRAN-supplied tabletop power source is used, simply plug it into the circular receptacle located in the “DC Power” area on the rear of the BBP. If a source of 21 to 60 volts DC (30 watts), either polarity referenced to ground, is available, it may be attached to the terminal block located on the rear of the BBP. The positive lead should be attached to the “+” side of the block and the negative lead should be attached to the “-” side of the block.
C A U T I O N
Power sources must not be attached to both the circular connector and the terminal blocks at the same time or damage will occur.
AUTOMATIC BBP FREQUENCY PLAN
Upon the initial application of power, the BBP will default to the factory-preset Frequency Plan, or to the Frequency Plan determined by the cable configuration of the RFC. The LED will indicate which frequency plan is active. On subsequent reboots, such as after a loss of power, the BBP will default to the most recently-used Plan setting.
SPREADING CODE
The spreading code for each end must be the same. The choice of operating code is selectable by the operator or the installer. Tracer is shipped in a matched (default) configuration.
Page 32
PAGE 26 61280004L1-1A
INSTALLATION
CO-LOCATING MULTIPLE 2.4 GHZ SYSTEMS
When multiple 2.4 GHz transmitters are to be co-located (installed in the same equipment room or on the same tower), it is advised to set all systems as follows:
1. If more than one 2.4 GHz system is transmitting from the same
location, set the antenna polarity of one system horizontal and the other system(s) vertical. (The antennas should be marked as to which mounting position is vertical or horizontal.) This will provide approximately 30 dB of isolation between the different antennas.
2. If more than one Tracer system is installed, set the co-located
transmitters to the same frequency plan (example: Plan A, Tx=2421; or Plan B, Tx=2462) and set each to a different spreading code. This keeps the transmitters on the additional system(s) from interfering with the co-located receiver(s).
3. If the systems are from different manufacturers, set the transmit
frequencies as close as possible with different spreading codes. Other manufacturers may not use the exact frequency plans as the Tracer system, but keeping the frequencies close will reduce the probability of the transmitter(s) interfering with the co­located receiver(s).
This equipment is authorized under CFR 47 Part 15.247. With this authorization by the FCC, this equipment shall not be co­located with a similar transmitter that transmits identical information.
ANTENNA ALIGNMENT
After the transmitter power for each end has been adjusted and the BBP and RFC have been installed and connected, the antenna should be connected to the RFC via the feedline. The antennas should be aimed toward one another as precisely as possible and the received signal strength indicator (RSSI) voltage measured. The RSSI voltage is a function of the signal strength at the receiver and is used to measure the received signal strength. RSSI varies approximately from 0 to 4 volts, with 0 volts corresponding to a weaker received signal and 4 volts corresponding to a stronger received signal.
Page 33
61280004L1-1A PAGE 27 SECTION 2
RF LOW
The “RF Low” LED indicates that the received signal is within 10dB of the minimum received signal strength (-80 dBm). If this indicator is on, the link performance may be marginal. The antennas should be peaked in azimuth and elevation until the desired signal level is achieved. RSSI may be monitored on either the RF unit or the front of the BBP. If the received signal is too strong and RSSI reaches a maximum such that the peak cannot be discerned, then the transmitter on the far end should be turned down.
At this point the radio link should be operational. Proper operation can be determined by the status of the “LINK DOWN” LED. If this LED is on, the link is not operational. If this LED is not on, the link is operating. Certain types of interference can cause one end of a path to operate and the other end to fail. In some instances, this may be corrected by swapping the frequency plan at each end, thus avoiding the interference if it is stronger at one end than the other. Changing the spreading code at each end may also allow interference to be mitigated.
REMOTE BERT
The Tracer includes a Bit Error Rate Tester (BERT) to verify that the installed system is operating correctly. When the “Remote Test” button is pushed on the local BBP, the remote end will send a BERT pattern for approximately ten seconds. The “Remote TST” indicator will turn yellow and remain on for the duration of the test. If no bit errors are detected, the “Remote TST” indicator will turn off. If any bit errors are detected, the “Remote Fail” indicator will turn red. This test should be run after the radio link has been aligned. If the test fails, refer to Section 4, “Troubleshooting,” for guidance.
Page 34
PAGE 28 61280004L1-1A
INSTALLATION
ALARM CONTACTS
Two classes of alarm, MAJOR and MINOR, are provided. A MAJOR alarm is signaled when the microwave path is not operational. A MINOR alarm is activated when any of the following conditions are detected at one of the E1 interfaces:
Loss of Signal Code Violation CRC error Framing Error Remote Error
Both normally-open and normally-closed contacts are provided for each alarm class. Access is provided by a six-position terminal strip on the baseband processor.
Page 35
61280004L1-1A PAGE 29
SECTION 3 OPERATION
VT-100 USER INTERFACE
The Tracer may be accessed with a VT-100 compatible terminal set to 9600 bits per second, 8 data bits, and no parity, connected to the RS-232 port on the back of the unit. Once a terminal is connected, pressing the ESC key will present the System Status screen. If password access has been enabled, then press “Enter” or “Return” in order to see the “Enter Password:” message. Tracer is shipped with password protection disabled.
RS-232 INTERFACE
The Tracer has an RS-232 interface for system management via an attached VT-100 terminal, personal computer, or modem. The RS-232 port is configured as a DCE with the following pin assignments:
CABLE CONNECTIONS
The cable connections required for various configurations are detailed in Appendix A of this manual.
Signal Pin Name Number Direction
TXD .................. 2 ............... To Tracer
RXD .................. 3 ............... From Tracer
RTS ...................4 ............... To Tracer
CTS................... 5 ............... From Tracer
DSR .................. 6 ............... From Tracer
Ground ............. 7
Page 36
PAGE 30 61280004L1-1A SECTION 3
PASSWORD
Tracer provides optional password protection of the terminal interface. If enabled, a password prompt is presented at power­up, reboot, or after thirty minutes of inactivity on the terminal. The default configuration is “No password.” Password protection is enabled via the configuration menu. The password is also set via the configuration menu.
If the password is forgotten, physical access to Tracer is required to access the terminal interface. The password may be bypassed by holding in the LPBK button while the system is rebooted. This will bring up the terminal interface and allow the password to be changed or disabled via the configuration screen.
CAUTION
This procedure is service-affecting.
MAIN MENU SELECTIONS
SYSTEM STATUS PAGE
This page displays the status of major system components. This is a status screen only; no configurations can be performed. More detailed information can be obtained by way of the Main Menu.
Current System Status Elapsed Time 00:06:07
----- ADTRAN Technical Support - 256/963-8716 ----­ | C | / ->>---->>---->>--->[RF UP]>---->>---->>---->>- \ | C | E1 ===| S |#(- -)#| S |=== E1 | U | \ ---<<----<<----<<--[RF UP]-<<----<<----<<----< / | U |
----- ----­ Local Tracer Remote Tracer Freq Plan A Freq Plan B
Tx Pwr Rx Pwr Tx Pwr Rx Pwr Max [ ] [X] Nominal Max [ ] [X] Nominal [ ] [X] [ ] [X] [ ] [X] Site: Adtran [ ] [X] [ ] [X] [ ] [X] [X] [X] RFC Link Up: Yes [X] [X] [X] [X] Code Sync: Yes [X] [X] [X] [X] Carrier Sync: Yes [X] [X] [X] [X] E1 Link Sync: Yes [X] [X] [X] [X] Chipping Code: 9 [X] [X] [X] [X] [X] [X] Min [X] [X] Min Min [X] [X] Min ============================================================================== Press 'm' - Main menu:
Figure 3-1. Current System Status Page
Page 37
61280004L1-1A PAGE 31
PERATION
O
The upper portion of the screen indicates how long the system has been running since the last reset operation. The “E1” label will be highlighted if any error conditions exist on that E1 interface.
The status of the radio link is indicated as Up or Down. The left portion of the screen reports the status of the local system (the system to which the terminal is attached); the right portion reports the status of the remote system. The approximate transmitter and receiver signal levels are shown via the “fuel gauges.” If the link is down and remote end data is unavailable, the fuel gauges will show “-” instead of “x.” The RFC Link, Code Sync, Carrier Sync, and E1 Link status will all report “yes” if the link is operational. Chipping code indicates the code to which the system is set. At any point in the VT-100 menu structure, press the Escape key to return to this screen.
MAIN MENU PAGE
Pressing “M” on any screen will take the user to the Main Menu, from which the subsequent screens can be accessed.
Site: Adtran
1) E1 Status Page
2) Link Performance History
3) E1 Performance History
4) Alarm Page
5) Test Menu
6) Configuration Menu
7) Remote Access
======================================================================== Press ESC for System Status:
TRACER Main Menu, Rev: A
Figure 3-2. Main Menu Page
Page 38
PAGE 32 61280004L1-1A
ECTION 3
S
E1 STATUS PAGE
The status of the E1 interface is displayed on this screen. This is a status screen only.
TRACER E1 Status Menu
Site: Adtran
Loop/Normal State Normal Rx Remote Alarm No Rx Carrier Loss No Rx Loss of Sync No Error Detection CRC4 Enabled (*) Signaling CCS (*) Line Code HDB3 (*)
(*) Indicates last set by front panel. Otherwise last set by terminal. ============================================================================== Press 'm' - Main menu:
Figure 3-3. E1 Status Page
LINK PERFORMANCE HISTORY
This screen presents detailed error statistics for the RF link. The data is presented as RFCL (Radio Frequency Converter Link) and LINK (RF Link) representing seconds out of service for each. The RFCL represents the communications channel between the BBP and RFC via the IF interconnect cable. The counts for the most recent 24 hours are recorded in 15-minute increments. Twenty­four-hour totals are recorded for the most recent days.
TRACER Link Performance History
24 Hour Registers 15 Minute Registers
-RFCL--LINK-- -RFCL-LINK--------RFCL-LINK­ 00000 00000 <-- Current --> 000 000
-1: ----- ----- - 1: 000 000 -17: --- ---
-2: ----- ----- - 2: --- --- -18: --- ---
-3: ----- ----- - 3: --- --- -19: --- ---
-4: ----- ----- - 4: --- --- -20: --- ---
-5: ----- ----- - 5: --- --- -21: --- ---
-6: ----- ----- - 6: --- --- -22: --- ---
-7: ----- ----- - 7: --- --- -23: --- ---
- 8: --- --- -24: --- ---
- 9: --- --- -25: --- ---
-10: --- --- -26: --- ---
-11: --- --- -27: --- ---
-12: --- --- -28: --- ---
-13: --- --- -29: --- ---
-14: --- --- -30: --- ---
-15: --- --- -31: --- ---
-16: --- --- -32: --- ---
======================================================================== Press 'm' - Main menu, 'p' - Prev pg, 'n' - Next pg:
Site: Adtran
Figure 3-4. Link Performance History Page
Page 39
61280004L1-1A PAGE 33
OPERATION
E1 PERFORMANCE HISTORY PAGE
This screen presents detailed error statistics for E1. The data is presented as Errored Seconds and Severely Errored Seconds. The counts for the most recent 24 hours are recorded in 15-minute increments. Twenty-four-hour totals are recorded for the most recent days.
TRACER E1 Performance History
24 Hour Registers 15 Minute Registers
---ES---SES-- --ES-SES-----------ES-SES­ 00000 00000 <-- Current --> 000 000
-1: ----- ----- - 1: 000 000 -17: --- ---
-2: ----- ----- - 2: --- --- -18: --- ---
-3: ----- ----- - 3: --- --- -19: --- -----
-4: ----- ----- - 4: --- --- -20: --- ---
-5: ----- ----- - 5: --- --- -21: --- ---
-6: ----- ----- - 6: --- --- -22: --- ---
-7: ----- ----- - 7: --- --- -23: --- ---
- 8: --- --- -24: --- ---
- 9: --- --- -25: --- ---
-10: --- --- -26: --- ---
-11: --- --- -27: --- ---
-12: --- --- -28: --- ---
-13: --- --- -29: --- ---
-14: --- --- -30: --- ---
-15: --- --- -31: --- ---
-16: --- --- -32: --- ---
============================================================================== Press 'm' - Main menu, 'p' - Prev pg, 'n' - Next pg:
Site: Adtran
Figure 3-5. E1 Performance History Page
Page 40
PAGE 34 61280004L1-1A SECTION 3
ALARM PAGE
This screen presents alarm information for the system. The E1 alarm is described in the chapter entitled “Troubleshooting.” If any of the E1 alarms are active, a minor alarm will be indicated at the alarm contacts. The RF link alarm will be activated when communication between the BBP and the RFC has failed. Code Sync, Carrier Sync, and Link Sync alarms indicate that various portions of the spread spectrum data pump are not operating. Any of these alarms will cause a major alarm to be activated at the alarm contacts. An RX Remote Alarm is an indication alarm from the receive portion of the circuit to indicate that a failure has occurred in the receive direction. RX Carrier Loss and RX Loss of Sync indicate the E1 has lost sync.
TRACER Alarm Page
Site: Adtran
Code Sync Alarm Off Carrier Sync Alarm Off Link Sync Alarm Off
Rx Remote Alarm Off Rx Carrier Loss Off Rx Loss of Sync Off
============================================================================== Press 'm' - Main menu:
Figure 3-6. Alarm Page
Page 41
61280004L1-1A PAGE 35
OPERATION
TEST MENU
This screen allows each E1 to be put into loopback mode.
TRACER Test Menu
Site: Adtran
1) Local E1 Line Loopback
2) Local E1 Link Loopback
3) Remote E1 Link Loopback
============================================================================== Press 'm' - Main menu:
Figure 3-7. Test Menu
Each menu selection is described below:
1.Loops the local E1 interface towards the local customer equipment.
2. Loops the local E1 interface towards the remote customer equipment, over the RF link.
3. Loops the remote E1 interface towards the local customer equipment, over the RF link.
E1
Local
RF Link21 3
Remote
E1
Figure 3-8. E1 Loopback Locations
Page 42
PAGE 36 61280004L1-1A
SECTION 3
This screen allows all system configurations to be performed.
TRACER Configuration Menu
Site: Adtran
1) E1 Signaling
2) E1 Line Code
3) E1 CRC Detection
4) Set Chipping Code
5) Set TX Power
6) Set Freq Plan
7) Reset all statistics
8) Enable/Disable Password
9) Change Password
10) Change Site ID
============================================================================== Press 'm' - Main menu:
Figure 3-9. Configuration Menu
The menu selections are described below.
E1 Framing allows each E1 to be configured for CAS or CS framing.
E1 Line Code allows each E1 to be configured for AMI or HDB3.
E1 CRC Detection enables or disables CRC4 detection.
Set Chipping Code allows the chipping code to be selected. Each
end of the link must be configured for the same chipping code.
Set Tx Power allows the transmitter power to be adjusted.
Set Freq Plan manually allows the frequency plan to be set to A or
B. One end of a link must be set to A and the other set to B. This function is automatically set when the BBP is attached to the corresponding RFC.
Reset All Statistics resets all Performance History counters and
timers.
Enable/Disable Password enables or disables the Password feature.
Change Password allow the user to change the password.
Change Site ID allows a unique text identifier for each radio,
displayed at the top of each page.
Page 43
61280004L1-1A PAGE 37
OPERATION
REMOTE ACCESS
This allows access to the remote radio via the RF communications link. When accessed, the user will be able to identify remote mode by each screen titled "Remote." The remote menus are accessed via a 2400 bps link causing screen refresh to be slower than local mode. All pages are displayed as if the user were connected to the VT-100 terminal at the remote end of the link. Every screen that can be accessed at the local radio can be accessed at the remote radio via this option.
Remote Current System Status
----- ADTRAN Technical Support - 256/963-8716 ----­ | C | / ->>---->>---->>--->[RF UP]>---->>---->>---->>- \ | C | E1 ===| S |#(- -)#| S |=== E1 | U | \ -<<----<<----<<----[RF UP]<----<<----<<----<<- / | U |
----- ----­ Local Tracer Remote Tracer Freq Plan A Freq Plan B
Tx Pwr Rx Pwr Tx Pwr Rx Pwr Max [ ] [X] Nominal Max [ ] [X] Nominal [ ] [X] [ ] [X] [ ] [X] Site: Adtran [ ] [X] [ ] [X] [ ] [X] [X] [X] RFC Link Up: Yes [X] [X] [X] [X] Code Sync: Yes [X] [X] [X] [X] Carrier Sync: Yes [X] [X] [X] [X] E1 Link Sync: Yes [X] [X] [X] [X] Chipping Code: 9 [X] [X] [X] [X] [X] [X] Min [X] [X] Min Min [X] [X] Min ============================================================================== Press 'm' - Main menu, '~' to exit remote mode:
Elapsed Time 00:21:13
Figure 3-10. Remote Current System Status
Page 44
PAGE 38 61280004L1-1A
Page 45
61280004L1-1A PAGE 39
SECTION 4 TROUBLESHOOTING
GENERAL
If you experience a problem with the Tracer system, check to ensure that all connectors, coaxial cables, antennas and T1s are all properly connected; and that the system configuration ensures proper transmit and receive levels for the RF equipment. Then, if the problem persists, follow the actions recommended in this section. For further assistance, call ADTRAN Technical Support at (256)␣ 963-8716.
N O T E
Each Tracer is completely system-tested and all specifications verified prior to shipment. Most problems on a new link tend to have installation­related solutions, but in some cases, the equipment may be at fault.
Page 46
PAGE 40 61280004L1-1A SECTION 4
PROBLEM DESCRIPTIONS AND RECOMMENDED ACTIONS
Each problem described below is followed by a list of Possible Causes, each of which is followed by a number (or numbers) corresponding to a Recommended Action (or Actions).
I M P O R T A N T
If problems persist after you have followed the Recommended Actions, contact ADTRAN Technical Support at (800) 726-8663.
TROUBLESHOOTING USING THE FRONT PANEL INDICATORS
“LINK ERRORLIGHT IS LIT, OR LINK IS DOWN
This alarm will activate when the RF link is not operational.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• The RF link is down. .................................................................... 1-10
• The RX power is below the -91 dbm threshold. .................... 1-4,7-10
• The far-end transmitter is off, or is transmitting
low power ................................................................................ 1-4,7-10
• The RF path is not aligned. .......................................................1,2,10
• Water is in the antenna feedhorn or connectors............................ 1,4
• Both units are set to the same frequency. ..................................... 5,10
• Both units are not set to the same PN code. ..................................... 6
• The connection between the BBP and the RFC
is faulty. ...................................................................................... 1,7-10
• The connection between the RFC and the
antenna is faulty. ........................................................................ 1,7-10
• The BBP or RFC is faulty. ................................................................. 10
RECOMMENDED ACTIONS:
1. Check the RX power using the VT-100 user interface or RSSI voltage.
2. Check the far-end transmitter for operation and proper transmit
power.
3. Check the RF path using a spectrum analyzer or RSSI voltages for
4. Check the antenna feedhorn and all outdoor connections for water.
Page 47
61280004L1-1A PAGE 41
TROUBLESHOOTING
5. Change the frequency of one radio through the VT-100 user interface
or front panel button.
6. Set both units to the same PN code.
7. Check all connections between the BBP, the RFC, and the antenna.
8. Check the IF and RF cables for shorts.
9. Check the connections inside the mast-mount or rack-mount RFC.
10. Replace the RFC.
“LBK” IS LIT
This alarm will activate when a software or manual T1 loopback has been established.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• A loopback has been commanded from the
VT-100 user interface. .................................................................... 1,2
• The “LBK” button has been pressed. .............................................. 1,2
RECOMMENDED ACTIONS:
1. Through the VT-100 user interface, deactivate the loopback in the
Loopback Menu.
2. Press the “LBK” button to deactivate the loopback.
NO “POWER” LIGHT
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• DC voltage is not applied. ........................................................... 1,2,4
• The polarity of the power connection is reversed............................. 2
• The AC transformer is not functioning properly. .......................... 3,4
• The AC transformer is not connected to the DC
jack on the BBP, or not connected to AC outlet. ............................ 3,4
RECOMMENDED ACTIONS:
1. Verify that the DC voltage is between 21-56 VDC (±).
2. Verify that negative voltage is applied to the negative terminal, and
positive voltage applied to the positive terminal.
3. Verify that the “Power” light is lit on the AC transformer.
4. Verify that the AC transformer is connected to an AC power cord
on the transformer, and connected to the DC jack on the BBP. Verify
Page 48
PAGE 42 61280004L1-1A SECTION 4
that the AC power cord is connected to an AC outlet. Verify that the AC outlet has proper AC voltage present.
“TESTLIGHT IS LIT OR BLINKING
The test alarm will remain on (solid) during power-up, indicating a self-test is in progress. The light will flash or remain on (solid) if the self-test fails.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• One-flash interval indicates a RAM test failure. ............................... 1
• Two-flash interval indicates the T1-C mux failed
internal test. ....................................................................................... 1
• Three-flash interval indicates the E1 framer failed. .......................... 1
• Five-flash interval indicates a DSP failure......................................... 1
• On (solid) indicates a faulty internal component. ............................ 1
RECOMMENDED ACTIONS:
1. Replace the BBP or the RFC.
“TST” LIGHT IS LIT AFTER PRESSING “REMOTE TESTBUTTON
The Remote Test light will activate during a remote test in progress. The Remote Test performs a 10-second bit error rate test (BERT) over the RF link to the far-end.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• A Remote Test has been activated from the front panel “Remote Test” button or the VT-100 user
interface.............................................................................................. 1
RECOMMENDED ACTIONS:
1. Allow the remote test to complete. If the Remote Test Fail light does
not activate, the remote test passed. If the Remote Test Fail light activates, see section on FAIL light is lit after pressing Remote Test button.
Page 49
61280004L1-1A PAGE 43
T
ROUBLESHOOTING
“FAILLIGHT IS LIT AFTER PRESSING “REMOTE TESTBUTTON
The Remote Fail light will activate after a Remote Test has failed.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• The 10-second BERT has failed over the RF link to
the far-end. ......................................................................................... 1
• The RX power may be below or near the -91 dbm
threshold. ........................................................................................... 1
RECOMMENDED ACTIONS:
1. Check the RX power level using the VT-100 user interface or the
RSSI DC voltage test points. Verify the RX power is between -55 &
-91 dbm.
“RF LOWLIGHT IS ON
This alarm will activate if the RX power is below -80␣ dbm.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• The RX power is below -80 dBm. ............................................. 1-5,7,8
• The far-end transmitter is off, or is transmitting low
power. ........................................................................................ 2-5,7,8
• The RF path is not aligned. ............................................................ 3,8
• Water is in the antenna feedhorn or connectors............................ 4,8
RECOMMENDED ACTIONS:
1. Verify the RX power is between -55 & -91 dBm using the VT-100
user interface or RSSI DC voltage test points.
2. Check the far-end transmitter for operation and proper transmit
power.
3. Check the RF path using a spectrum analyzer or RSSI voltages for
proper alignment. Have path professionally re-aligned and check system path engineering.
4. Check the antenna feedhorn and all outdoor connections for water.
5. Check all connections between the BBP, the RFC, and the antenna.
6. Check the IF and RF cables for shorts.
7. Check the connections inside the mast-mount or rack-mount RFC.
8. Replace the RFC.
Page 50
PAGE 44 61280004L1-1A SECTION 4
TROUBLESHOOTING USING THE VT-100 USER INTERFACE
This section provides information for troubleshooting the Alarm Menu on the VT-100 user interface. The conditions present in the Alarm Menu are software indications and should match the front panel LED indications.
RF LINK ALARM OR CODE SYNC AL ARM
The RF Link Alarm will activate when the link is down or not operational.
The Code Sync Alarm will activate when data synchronization has not been achieved between the RF link.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• The RF link is down. .................................................................... 1-10
• The RX power is below the -91 dbm threshold. .................... 1-4,7-10
• The far-end transmitter is off, or is transmitting
low power. ............................................................................... 1-4,7-10
• The RF path is not aligned. .......................................................1,3,10
• Water is in the antenna feedhorn or connectors............................ 1,4
• Both units are set to the same frequency. ..................................... 5,10
• Both units are not set to the same PN code. ..................................... 6
• The connection between the BBP and the RFC is faulty. .......... 1,7-10
• The connection between the RFC and the antenna is faulty. ... 1,7-10
• The BBP or RFC is faulty. ................................................................. 10
RECOMMENDED ACTIONS:
1. Check the RX power using the VT-100 user interface or RSSI voltage.
2. Check the far-end transmitter for operation and proper transmit
power.
3. Check the RF path using a spectrum analyzer or RSSI voltages for
proper alignment. Have path professionally re-aligned and check system path engineering.
4. Check the antenna feedhorn and all outdoor connections for water.
5. Change the frequency of one radio through the VT-100 user interface
or front panel button.
6. Set both units to the same PN code.
7. Check all connections between the BBP, the RFC, and the antenna.
8. Check the IF and RF cables for shorts.
9. Check connections inside the mast-mount or rack-mount RFC.
10. Replace the RFC.
Page 51
61280004L1-1A PAGE 45
TROUBLESHOOTING
CARRIER SYNC ALARM OR T1 MUX FRAMER AL ARM
The Carrier Sync alarm will activate when frequency synchronization has not been achieved between the RF link.
The T1 Mux Framer alarm will activate when synchronization between the T1 mux on each radio has not been achieved.
RECOMMENDED ACTION
POSSIBLE CAUSE (SEE LIST BELOW)
• The RF link is down. .................................................................... 1-10
• The RX power is below the -91 dbm threshold. .................... 1-4,7-10
• The far-end transmitter is off, or is transmitting
low power................................................................................ 1-4,7-10
• The RF path is not aligned. .......................................................1,3,10
• Water is in the antenna feedhorn or connectors............................ 1,4
• Both units are set to the same frequency. ..................................... 5,10
• Both units are not set to the same PN code. ..................................... 6
• The connection between the BBP and the RFC is
faulty. .......................................................................................... 1,7-10
• The connection between the RFC and the antenna is
faulty. .......................................................................................... 1,7-10
• The BBP or RFC is faulty. ................................................................. 10
RECOMMENDED ACTIONS:
1. Check the RX power using the VT-100 user interface or RSSI voltage
(refer to RSSI voltage chart)
2. Check the far-end transmitter for operation and proper transmit
power.
3. Check the RF path using a spectrum analyzer or RSSI voltages for
proper alignment. Have path professionally re-aligned and check system path engineering.
4. Check the antenna feedhorn and all outdoor connections for water.
5. Change the frequency of one radio through the VT-100 user interface
or front panel button.
6. Set both units to the same PN code.
7. Check all connections between the BBP, the RFC, and the antenna.
8. Check the IF and RF cables for shorts.
9. Check connections inside the mast-mount or rack-mount RFC.
10. Replace the RFC.
Page 52
PAGE 46 61280004L1-1A SECTION 4
E1 ALARMS
The following definitions of E1 alarms apply to Tracer.
Local Alarm is caused by a locally detected facility failure.
Remote Alarm is an alarm received at the receive portion of the
circuit to indicate that a failure has occurred in the receive direction.
ALM indicates one of two main problems. First, if a solid red line it indicates a local failure with the E1 signal (Usually the incoming E1 line on the back of the Tracer). A blinking light on the ALM indicates there is a problem on a remote E1(A machine sending an E1 to the Tracer is connected to has a local failure). When a unit has a local failure it sends out a signal on the E1 lines going out from it saying there is a failure.
• When 192 consecutive zeroes are detected at the E1 interface the ALM LED will light. The remote Tracer will transmit an AIS on the effected E1 to indicate an error.
• When an E1 interface receives a Remote Alarm the ALM LED will blink. The Tracer at the remote end will pass the Remote Alarm though on the effected E1.
• When an E1 interface receives an AIS the ALM LED will light continuously. The remote E1 will transmit the AIS signal.
CV/CRC is a light that will blink when there is a Code Violation(CV -- related to Bipolar Violations usually) or a CRC4 error on the incoming E1. E1's can have a crc error checking signal mixed in the signalling bits. First thing they should do if this comes on, however, is to be sure that the E1's connected to the Tracer really do have the CRC4 signalling bits turned on. If there is any question about this then CRC4 checking on the dip switches should be turned off, which will simply ignore any CRC bits.
LOS is a Loss Of Signal, meaning the Tracer is receiving no E1 signal on the E1 RX port. OOF means Out Of Frame error, meaning we have lost framing synch.
When the RF link is down an AIS will be transmitted on the E1. No E1 alarm LEDs will be lit in this situation, but the LINK DOWN LED will illuminate.
Page 53
61280004L1-1A PAGE 47
TROUBLESHOOTING
Alarm Indication Signal (AIS) An unframed all ones signal that replaces the normal traffic signal when a maintenance alarm indication has been activated. Its purpose is to notify facilities at the receive end of a circuit that a local alarm has occurred upstream in the circuit.
Page 54
PAGE 48 61280004L1-1A
Page 55
61280004L1-1A PAGE 49
SECTION 5 SPECIFICATIONS
This section lists the specifications for the Tracer system.
RF TRANSMITTER
Output Power .............. +20 dBm, maximum
Frequency Range ......... 2400 -2483.5 MHz
Channel Bandwidth .... 40 MHz (Two Channels)
RF RECEIVER
Receive Level Range .......... -30 to -91 dBm (10-6 BER minimum)
Receive Level (nominal) ... -60 dBm
FREQUENCY PLAN
Plan A .......................... TX=2.422 GHz, RX=2.462 GHz
Plan B........................... TX=2.462 GHz, RX=2.422 GHz
SPREAD SPECTRUM DATA PUMP
Modulation .................. DQPSK
Spreading Method ....... Direct Sequence
Code Length ................ 120 bits
Processing Gain........... >12 dB
Number of Codes ........ 10
Chipping Rate ............. 12
Page 56
PAGE 50 61280004L1-1A
ECTION 5
S
E1 INTERFACE SPECIFICATION
Electrical...................... G.703
Framing ....................... G.704 CRC-4, CAS, CCS
Jitter ............................. G.823
Line Code .................... AMI, HDB3
Data Rate ..................... 2.048 Mbps
Mechanical .................. 75 unbalanced -- BNC
120 balanced -- DB 15 / RJ-48
Alarms ......................... loss of signal, code violation, CRC error,
framing error, remote alarm
Loopbacks ................... local line, remote link, local link
USER INTERFACE
Panel ............................ Alarm LEDs, Configuration Switches,
Monitor Jacks
Diagnostics .................. E1 Loopback, Remote Test with built in
BERT
Test Points ................... RSSI, System Voltages, QPSK Constellation
Alarms ......................... Major normally open
Major normally closed
Minor normally open
Minor normally closed
ASCII Terminal............ Menu-Driven User Interface, Control of the
Remote End, Password Protected
(Optional), Event History
RS-232 TERMINAL INTERFACE
Data Rate ..................... 9600 bps
Data Bits ...................... 8
Parity ........................... None
Stop Bits....................... 1
Terminal Emulation .... VT-100
Page 57
61280004L1-1A PAGE 51
SPECIFICATIONS
MECHANICAL & ENVIRONMENTAL
Baseband Processor
Operating Temperature -25°C to +65°C
Size .............................. 42.4cm x 4.4cm x 29.2cm
Humidity ..................... 95%, Non-condensing
Weight ......................... 2.7 kg
Rack RFC
Operating Temperature -40°C to +65°C
Size .............................. 42.4cm x 4.4cm x 29.2cm
Humidity ..................... 95%, Non-condensing
Weight ......................... 4.8 kg
Mast RFC
Operating Temperature -40°C to +65°C
Size .............................. 22.5 cm diameter x 52.5 cm
Humidity ..................... 100%
Weight ......................... 8.1 kg
POWER
Input Voltage ............... 21 to 60 volts DC
100 to 220 volts AC, 50 or 60 Hz (with optional AC adapter) Power Consumption ... 30 watts
Connector.................... 3 pin DIN (AC adapter)
3 pin screw clamp terminal block (DC)
Page 58
PAGE 52 61280004L1-1A
Page 59
61280004L1-1A PAGE 53
GLOSSARY
ACRONYMS USED IN THIS MANUAL
AMI .............. Alternate Mark Inversion
BER .............. Bit error rate
BBP .............. Baseband Processor
CAS .............. Channel associated signaling
CCS .............. Common channel signaling
CRC ............. Cyclic Redundancy Check
DCE ............. Data Communications Equipment
DTE ............. Data Terminal Equipment
FAS .............. Frame Alignment Signal
FCC ............. Federal Communications Commission
FEC .............. Forward error correction
HDB3 ........... High-density bipolar of order 3
IF ................. Intermediate Frequency
ISM .............. Industrial, Scientific, and Medical
LBK .............. Loopback
QPSK ........... Quadrature Phase Shift Keying
RF ................ Radio frequency
RFC .............. Radio frequency converter
RFCL ........... Radio frequency converter link (IF cable)
RSSI ............. Received signal strength indicator
Rx ................ Receive
Tx ................ Transmit
Page 60
PAGE 54 61280004L1-1A
Page 61
61280004L1-1A PAGE A - 1
CABLE CONNECTIONS
APPENDIX A CABLE CONNECTIONS
The cable connections required for various configurations are detailed below.
TERMINAL CONNECTION (DB25)
Tracer (DCE) Terminal (DTE)
Number Name Number Name
2 ............... TXD
3 ............... RXD 3 ............... RXD
4 ................ RTS 4 ............... RTS
5 ................ CTS 5 ............... CTS
6 ................ DSR 6 ............... DSR
7 ............. Ground 7 ............ Ground
2 ...............TXD
PERSONAL COMPUTER CONNECTION (DB9)
Tracer (DCE) Computer (DTE) Number Name Number Name
2 ............... TXD
3 ............... RXD 2 ............... RXD
4 ................ RTS 7 ............... RTS
5 ................ CTS 8 ............... CTS
6 ................ DSR 6 ............... DSR
7 ............. Ground 5 ............ Ground
3 ...............TXD
Page 62
PAGE A - 2 61280004L1-1A APPENDIX A
MODEM CONNECTION (DB25)
Tracer (DCE) Modem (DCE) Number Name Number Name
2 ............... TXD
3 ............... RXD
4 ................ RTS 5 ............... CTS
5 ................ CTS 4 ............... RTS
6 ................ DSR 20 ..............DTR
7 ............. Ground 7Ground
3 ...............RXD
2 ...............TXD
E1 NETWORK INTERFACE
15 Pin RJ48 Pin Function Pin Function
1 E1 Out ring 1 E1 Out ring 2 Frame ground 2 E1 Out tip 3 E1 In ring 3 N.C. 4 Frame ground 4 E1 In ring 5 N.C. 5 E1 In tip 6 N.C. 6 N.C. 7 N.C. 7 N.C. 8 N.C. 8 N.C. 9 E1 Out tip 10 N.C. 11 E1 In tip 12 N.C. 13 N.C. 14 N.C. 15 N.C.
Loading...