BATTERY BACKUP UNIT (L4)
JOBAID
PRICING AND AVA ILA BILITY 800.827.0887
TECHNICAL SUPPORT 888.4ADTRAN
RETURN FOR REPAIR 256.963.8722
61175044L4-22A
BATTERY BACKUP
UNIT
Battery Backup
1175044L4
CAUTION
This equipment MUST only be installed in a DC-C bonding and
grounding environment per Telcordia GR-1089-CORE, Issue 3. It
may not be utilized in a DC-I (isolated) bonding and grounding
environment.
SAFETY INFORMATION
When using your telephone equipment, please follow these basic safety
precautions to reduce the risk of fire, electrical shock, or personal injury:
1. Do not use this product near water, such as a bathtub, wash bowl, kitchen
sink, laundry tub, in a wet basement, or near a swimming pool.
2. Avoid using a telephone (other than a cordless-type) during an electrical
storm. There is a remote risk of shock from lightning.
3. Do not use the telephone to report a gas leak in the vicinity of the leak.
4. Use only the power cord, power supply, and/or batteries indicated in the
manual. Do not dispose of batteries in a fire; they may explode. Check with
local codes for special disposal instructions.
MOUNTING INSTRUCTIONS
CAUTION
Electronic equipment can be damaged by static electrical discharge.
Before handling equipment, wear an antistatic discharge wrist strap
to prevent damage to electronic components. Place equipment in
antistatic packing material when transporting or storing. When
working on equipment, always place them on an approved antistatic
mat that is electronically grounded.
Wallmount instructions (cont’d)
4. Remove the two closure screws on the battery box and open the cover.
5. Use a long shaft screwdriver to tighten the three support screws.
6. Make the connections to your ADTRAN product. (Refer to the documentation provided
with your ADTRAN system for detailed instructions on making the connections.)
GROUNDING
18 AWG or larger ground wire is recommended to connect an additional gr ound conductor
to “ground bus” in the customer equipment room.
WARRANTY
Wa rranty for Carrier Network produc ts manufactured by ADTRAN and supplied under Buyer's
order for use in the U.S. is ten ( 10) years except batteries which carry a manufacturer’s warranty
of one year. For a complete copy of ADTRAN's U.S. Carrier Networks Equipment Warranty, dial
(877) 457-5007 and request Document 414.
COMPLIANCE CODES
Code Input Output
PC F C
TC X X
IC E —
MAINTENANCE
! Life expectancy: 3-5 years of standby use.
! Battery performance is adversely affected by extreme temperatures.
! Old batteries should be recycled. Reference ADTRAN document 60000120-36A for more
information.
JOBAid, 61175044L4-22A, January 2004 Technical Support 1-888-4ADTRAN (1-888-423-8726) 2004 ADTRAN, All Rights Reserved
C A U T I O N
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
!
Unpack the Backup system and inspect for damage. If damage is apparent, refer
1
to your carrier or supplier for r e medy. It is not necessar y to r em ove th e batte ries
during installation.
CAUTION
Fully loaded Battery Box weighs 30 lbs.
Wall mount the battery box with the following minimum clearances:
2
Top - 9”
Left Side - 1”
Right Side - 5”
Bottom - 3”
1. Using the template provided (61175044L4-19), mark and drill three pilot
holes using a size I (0.228” diameter) drill bit.
2. Insert 1/4” x 3/4” flat-head wood screws (supplied) into the three pilot holes,
leaving 1/8” to 3/16” space between the screw head and the backboard.
3. With an assistant, mount the battery box on the three support screws on the
backboard.
BATTERY SPECIFICATIONS
! Part Number: 311212V02
! Suppliers: YUASA and PANASONIC
! Batteries: 7 Amp/ hr
! Battery type: Lead acid
! DC Output: -54 VDC, 60 W (average), 100 W
! Backup Time: Up to 8 hours
! Battery Charging: 16 hr nominal, 24 hr maximum
! Wire Gauge: 18 AWG
! Preferred Temperature: 68º F (20º C)
The device complies with Part 15 of the FCC rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired
operation.
Changes or modifications not expressly approved by ADTRAN could void the user's
authority to operate this equipment.
BATTERY BACKUP UNIT (L4)
FUSE
! Part Number: 32543A03
! Rating: 3A, 250V
! Dimensions: 5 mm x 20 mm
SAMPLE WIRING DIAGRAM
The following is an illustration of a typical wiring connection between ADTRAN systems using an AC/DC power supply and battery charger and the
battery backup unit. Please refer to your particular product documentation for specific wiring instructions for your product.
-48 VDC Backup
Battery Unit
Battery Backup
1175044L4
JOBAID
61175044L4-22A
JOBAid, 61175044L4-22A, January 2004 Technical Support 1-888-4ADTRAN (1-888-423-8726) 2004 ADTRAN, All Rights Reserved