AC/DC POWER SUPPLY AND BATTERY CHARGER
A
JOB
PRICING AND AVAILABILITY 800.827.0887
TECHNICAL SUPPORT 888.4ADTRAN
RETURN FOR R EPAIR 256.963.8722
ID
61175044L2-22B
AC/DC POWER
SUPPLY AND
BATTERY CHARGER
P/N: 1175043L1
CLEI: SIMPAAAARA
P/N: 1175043L2
CLEI: SIMPAADARA
P/N: 1175043L3
CLEI: SIMPAAEARA
Note: The AC/DC Power Supply
and Battery Charger is
designed for use with the
Total Access 750 and 850.
It is not used with the Total
Access 612/616/624 units.
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
MOUNTING INSTRUCTIONS
Remove the Total Access 750/850 AC/DC Power Supply
1
(ADTRAN P/N 1175043Lx) from the box and inspect for
damage. If damage is apparent, contact your carrier or
supplier.
Place the power supply with the power cord oriented
2
downward.
Use four #6 x 3/8" machine screws (supplied) to mount the
3
power supply to either side of the Total Access 750/850 shelf.
Note: Threaded mounting holes are provided on both sides of
the shelf.
Note: For battery backup installations, it is recommended to
mount the power supply on the left side of the Total
Access 750/850 shelf, next to the battery cover hinge.
Note: Alternatively, the power supply can be mounted to the
backboard with four #6 x 1" wood screws (not supplied).
The device complies with Part 15 of the FCC rules. Operation is
subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
Changes or modifications not expressly approved by ADTRAN
could void the user's authority to operate this equipment.
WARRANTY
Warranty for Carrier Network products manufactured by
ADTRAN and supplied under Buyer's order for use in the U.S. is
ten (10) years. For a complete copy of ADTRAN's U.S. Carrier
Networks Equipment Warranty: (877) 457-5007, Document 414.
STATUS LEDS
AC Power Operation (AC power only) Battery O peration ( AC power supply or battery backup)
GREEN OK GREEN OK (charging)
YELLOW Power Fail YELLOW Discharging
RED Power Fail RE D Low (<-40 V)
OFF Power Fail OFF Disconnected
RELAYS
Alarm Relay
Provided for customer use
■
Condition Alarm Relay
Normal Open
AC Power Fa ilure/
Battery Backup engaged
Battery voltage <-45V Stays closed if voltage <-45 VDC to indicate that battery is becoming depleted
Battery Disconnect Relay
Disconnects battery pack from the system if the battery voltage falls below -40 VDC
■
Prevents damage to batteries
■
Cycles open/closed once per second if AC voltage <88 Vrms at full load and battery
backup is connected
CIRCUIT BREAKER
3- amp circuit breaker
■
Protects unit from over - current
■
Rocker button extends out from front panel when tripped
■
Reset by pushing in on the rocker button
■
GROUNDING
■ An 18 AWG or larger ground wire is required to connect additional ground connector to "ground
bus" in customer equipment room.
ELECTRICAL SPECIFICATIONS TELECOMMUNICATIONS CODES
AC input: 115 V nominal
■
■ Range: 90 to 132 VAC
DC output: -54 V, 60 W average, 100 W peak
■
Battery charging: 16 hr nominal, 24 hr maximum
■
■ Battery discharge: Up to 8 hours
Code Input Output
PC F C
TC — —
IC E —
JOBAid, 61175044L2-22B, December 2002 Technical Support 1-888-4ADTRAN (1-888-423-8726) Copyright 2002 ADTRAN, All Rights Reserved
BATTERY BACKUP UNIT
A
JOB
ID
61175044L2-22B
BATTERY
BACKUP
UNIT
P/N: 1175044L2
CLEI: SIMPBBBARA
Note: Battery Backup Unit is
designed for use with the
Total Access 612, 616, 624,
750 and 850 units.
MOUNTING INSTRUCTIONS
Unpack the Total Access 750/ 850 Battery Backup Unit and inspect
1
for damage. If damage is apparent, refer to your carrier or supplier
for remedy.
Note: It is not necessary to remove the batteries during
installation process.
The battery box must be mounted with the following minimum
2
clearances:
Top-9" (for Total Access 750/850)
Top- 5" (for Total Access 612/616/624)
Left Side-5"
Right Side-1”
Bottom-3"
Using the template provided, mark and drill three pilot holes for #10
3
mounting screws.
Insert #10 x 3/ 4" flat- head wood screws (supplied) into the three
4
pilot holes, leaving 1/ 16" space between the screw- head and the
backboard.
CAUTION: Fully loaded Battery box weighs 30 lbs.
Mount the battery box on the three support screws on the backboard.
5
Remove the two closure screws on the battery box and open the
6
cover.
Use a long shaft screwdriver to tighten the three support screws.
7
WARRANTY
Warranty for Carrier Network products manufactured by ADTRAN and
supplied under Buyer's order for use in the U. S. is ten (10) years, except
for batteries which carry manufacturer's warranty. For a complete copy of
ADTRAN's U. S. Carrier Network Equipment
Warranty: (877) 457- 5007, Document 414.
BATTERY SPECIFICATIONS
Batteries: 7 Amp/ hr (4 batteries per pack)
■
Case size: 6" W x 3 3/ 4" H x 2 1/ 2" D
■
Battery type: Lead acid
■
Voltage: -54 VDC
■
Backup Time: Up to 8 hours
■
Wire Gauge: 18 AWG
■
Preferred Temperature: 68º F (20º C)
■
The device complies with Part 15 of the FCC
rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that may
cause undesired operation.
Changes or modifications not expressly approved by
ADTRAN could void the user's authority to operate this
equipment.
CAUTION!
During
Note: The connection for the Total
Access 850 will be identical
to the Total Access 750.
1175044L2
BATTERY BACKUP
Total Access 750
wall installation,
position the
chassis so front
panels face up.
V.35
AC/DC Power Supply
Battery Charging Unit
P/N: 1175043Lx
AC Power Input
1175044L2
BATTERY BACKUP
-48 VDC
Total Access 750
WARNING:
20 Hz FUSE
MUST BE REMOVED
BEFORE REMOVING COVER.
MANAGEMENT
-54 VDC Output to
Total Access 750
-54VDC
120VAC/
OUTPUT
2A 60HZ INPUT
BATTERY
INPUT
GROUND
+
Charging/Discharging Line
T1
FT1
DC
POWER
AC ALARM
OUTPUT
-
-54 VDC Battery
P2
Terminal
LX IN
access
LY IN
R1-I
cover
EU2
T1-I
LX OUT
R-O
LY OUT
T-O
EU1
MLT-A
MLT-B
-48ALM
MJ
MJR
-48 R
MJV
MJVR
-48 V
To Alarms
TELECOMMUNICATIONS CODES
CAUTION
shown in 61200624L1-19A.
AC Power Input
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
Code Input Output
IC — C
TC — —
PC E —
MAINTENANCE
■ Life expectancy: 3- 5 years on standby use
■ Battery performance is adversely affected by extreme emperatures.
■ Old barreries should be recycled. Reference 60000120-36A for
further information.
-48 VDC
Total Access 612/616/624
During wall installation, position
the Total Access 612/616/624 as
9902271
JOBAid, 61175044L2-22B, December 2002 Technical Support 1-888-4ADTRAN (1-888-423-8726) Copyright 2002 ADTRAN, All Rights Reserved