ADTRAN 61175044L2-22B User Manual

AC/DC POWER SUPPLY AND BATTERY CHARGER
A
JOB
PRICING AND AVAILABILITY 800.827.0887
TECHNICAL SUPPORT 888.4ADTRAN
RETURN FOR R EPAIR 256.963.8722
ID
61175044L2-22B
AC/DC POWER
SUPPLY AND
BATTERY CHARGER
P/N: 1175043L1 CLEI: SIMPAAAARA P/N: 1175043L2 CLEI: SIMPAADARA P/N: 1175043L3 CLEI: SIMPAAEARA
Note: The AC/DC Power Supply
and Battery Charger is designed for use with the Total Access 750 and 850. It is not used with the Total Access 612/616/624 units.
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
MOUNTING INSTRUCTIONS
Remove the Total Access 750/850 AC/DC Power Supply
1
(ADTRAN P/N 1175043Lx) from the box and inspect for damage. If damage is apparent, contact your carrier or supplier.
Place the power supply with the power cord oriented
2
downward.
Use four #6 x 3/8" machine screws (supplied) to mount the
3
power supply to either side of the Total Access 750/850 shelf.
Note: Threaded mounting holes are provided on both sides of
the shelf.
Note: For battery backup installations, it is recommended to
mount the power supply on the left side of the Total Access 750/850 shelf, next to the battery cover hinge.
Note: Alternatively, the power supply can be mounted to the
backboard with four #6 x 1" wood screws (not supplied).
The device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the user's authority to operate this equipment.
WARRANTY
Warranty for Carrier Network products manufactured by ADTRAN and supplied under Buyer's order for use in the U.S. is ten (10) years. For a complete copy of ADTRAN's U.S. Carrier Networks Equipment Warranty: (877) 457-5007, Document 414.
STATUS LEDS
AC Power Operation (AC power only) Battery O peration ( AC power supply or battery backup)
GREEN OK GREEN OK (charging)
YELLOW Power Fail YELLOW Discharging
RED Power Fail RE D Low (<-40 V)
OFF Power Fail OFF Disconnected
RELAYS
Alarm Relay
Provided for customer use
Condition Alarm Relay
Normal Open
AC Power Fa ilure/ Battery Backup engaged
Battery voltage <-45V Stays closed if voltage <-45 VDC to indicate that battery is becoming depleted
Battery Disconnect Relay
Disconnects battery pack from the system if the battery voltage falls below -40 VDC
Prevents damage to batteries
Cycles open/closed once per second if AC voltage <88 Vrms at full load and battery backup is connected
CIRCUIT BREAKER
3- amp circuit breaker
Protects unit from over - current
Rocker button extends out from front panel when tripped
Reset by pushing in on the rocker button
GROUNDING
An 18 AWG or larger ground wire is required to connect additional ground connector to "ground
bus" in customer equipment room.
ELECTRICAL SPECIFICATIONS TELECOMMUNICATIONS CODES
AC input: 115 V nominal
Range: 90 to 132 VAC
DC output: -54 V, 60 W average, 100 W peak
Battery charging: 16 hr nominal, 24 hr maximum
Battery discharge: Up to 8 hours
Code Input Output
PC F C
TC
IC E
BATTERY BACKUP UNIT
A
JOB
ID
61175044L2-22B
BATTERY
BACKUP
UNIT
P/N: 1175044L2 CLEI: SIMPBBBARA
Note: Battery Backup Unit is
designed for use with the Total Access 612, 616, 624, 750 and 850 units.
MOUNTING INSTRUCTIONS
Unpack the Total Access 750/ 850 Battery Backup Unit and inspect
1
for damage. If damage is apparent, refer to your carrier or supplier for remedy.
Note: It is not necessary to remove the batteries during
installation process.
The battery box must be mounted with the following minimum
2
clearances:
Top-9" (for Total Access 750/850) Top- 5" (for Total Access 612/616/624) Left Side-5" Right Side-1” Bottom-3"
Using the template provided, mark and drill three pilot holes for #10
3
mounting screws.
Insert #10 x 3/ 4" flat- head wood screws (supplied) into the three
4
pilot holes, leaving 1/ 16" space between the screw- head and the backboard.
CAUTION: Fully loaded Battery box weighs 30 lbs.
Mount the battery box on the three support screws on the backboard.
5
Remove the two closure screws on the battery box and open the
6
cover.
Use a long shaft screwdriver to tighten the three support screws.
7
WARRANTY
Warranty for Carrier Network products manufactured by ADTRAN and supplied under Buyer's order for use in the U. S. is ten (10) years, except for batteries which carry manufacturer's warranty. For a complete copy of ADTRAN's U. S. Carrier Network Equipment Warranty: (877) 457- 5007, Document 414.
BATTERY SPECIFICATIONS
Batteries: 7 Amp/ hr (4 batteries per pack)
Case size: 6" W x 3 3/ 4" H x 2 1/ 2" D
Battery type: Lead acid
Voltage: -54 VDC
Backup Time: Up to 8 hours
Wire Gauge: 18 AWG
Preferred Temperature: 68º F (20º C)
The device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the user's authority to operate this equipment.
CAUTION!
During
Note: The connection for the Total
Access 850 will be identical to the Total Access 750.
1175044L2
BATTERY BACKUP
Total Access 750
wall installation,
position the
chassis so front
panels face up.
V.35
AC/DC Power Supply Battery Charging Unit
P/N: 1175043Lx
AC Power Input
1175044L2
BATTERY BACKUP
-48 VDC
Total Access 750
WARNING: 20 Hz FUSE
MUST BE REMOVED
BEFORE REMOVING COVER.
MANAGEMENT
-54 VDC Output to Total Access 750
-54VDC
120VAC/
OUTPUT
2A 60HZ INPUT
BATTERY
INPUT
GROUND
+
Charging/Discharging Line
T1
FT1
DC
POWER
AC ALARM
OUTPUT
-
-54 VDC Battery
P2
Terminal
LX IN
access
LY IN
R1-I
cover
EU2
T1-I
LX OUT
R-O
LY OUT
T-O
EU1 MLT-A
MLT-B
-48ALM MJ
MJR
-48 R
MJV
MJVR
-48 V
To Alarms
TELECOMMUNICATIONS CODES
CAUTION
shown in 61200624L1-19A.
AC Power Input
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
Code Input Output
IC C
TC
PC E
MAINTENANCE
Life expectancy: 3- 5 years on standby use
Battery performance is adversely affected by extreme emperatures.
Old barreries should be recycled. Reference 60000120-36A for
further information.
-48 VDC
Total Access 612/616/624
During wall installation, position the Total Access 612/616/624 as
9902271