ALARM RELAYS
There are eight alarm relays that provide normally open or normally closed contacts for each of the following alarms:
Visual Critical
Visual Major
Visual Minor
Audible Critical
Audible Major
Auxiliary 1
Auxiliary 2
POWER SUPPLY 48 PIN CONNECTOR PINOUT
TOTAL ACCESS 4303 PLUS DC POWER SUPPLY
DC SUPPLY
CLEI: SLPOCDBC_ _
DC SUPPLY
PLUS
1202335L1
POWER TEMP
61202335L1-22A
0401
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
FRONT PANEL LEDs
POWER Off Both –48 VDC fuses blown, power not supplied to the shelf,
or incorrect polarity on the voltage supplied to the shelf
Green Power supplied is the correct voltage and polarity; backplane
and hot insertion voltages correct
Amber –48 VDC input and hot insertion voltage present; no back-
plane voltage
Red –48 VDC input present; no backplane voltage and no hot
insertion voltage
TEMP Off Normal
Red Over-temperature condition
DESCRIPTION
The Total Access®4303 Plus DC Power Supply is a removable assembly that provides the voltages necessary for proper system operation. The unit features LEDs for over­temperature and DC output, an input fuse, and the ability to be hot-swapped when used with another DC supply in the same chassis. The supply interfaces to the Total Access backplane through a 48-pin connector. The unit accepts one or two –48 VDC inputs from the backplane and supplies –48 VDC fused output for use with external input logic, +5 VDC as hot insertion bias voltage for modules, and +2.1 VDC for back­plane termination. In addition, the Total Access 4303 Plus DC Supply provides alarm relay ouputs when installed in slot PS-A.
The following features are supported on the Total Access 4303 Plus DC Power Supply:
Thermal limit indicator with open collector output
DC status indicator on the 2.1 and 5 volt outputs with open collector output
Short circuit protection
Compatible with existing Total Access DC Power Supplies (P/N 1200335L1)
SPECIFICATIONS
Specifications
Input Voltage –42 VDC to –56 VDC Operating Temperature –40°C to +65°C Storage Temperature –40°C to +85°C Relative Humidity Up to 95% noncondensing Over Temperature Indication 90°C ±5% –48 VDC Short Circuit Protection Fused 1-amp slow blow Backplane Voltage Short Circuit Protection Self-mending Compliance FCC Part 15, UL 60950, NEBS Level III,
GR-1089-CORE
Pin # Row A Signal Row B Signal Row C Signal
1 AUD_CRIT_NO AUD_CRIT_COM AUD_CRIT_NC 2 AUD_MAJ_NO AUD_MAJ_COM AUD_MAJ_NC 3 AUD_MIN_NO AUD_MIN_COM AUD_MIN_NC 4 VIS_CRIT_NO VIS_CRIT_COM VIS_CRIT_NC 5 VIS_MAJ_NO VIS_MAJ_COM VIS_MAJ_NC 6 VIS_MIN_NO VIS_MIN_COM VIS_MIN_NC 7 AUX1_RLY_NO AUX1_RLY_COM AUX1_RLY_NC 8 AUX2_RLY_NO AUX2_RLY_COM AUX2_RLY_NC 9 –48V_A PS_OK PS_TEMP 10 –48V_B 2.1V PS_PRESENT 11 2.1V 2.1V 2.1V 12 –48V_AB_RTN 2.1V VCC 13 GND GND GND 14 GND GND PSRLY_CLK 15 GND PSRLY_LOAD PSRLY_DATAIN 16 FR_GND –48V PSRLY_DATAOUT
JOBAID
#61202335L1-22A#
TURNUP STEPS
To install the Total Access 4303 Plus DC Power Supply, perform the following steps:
After unpacking the Total Access 4303 Plus DC Power Supply, inspect it for damage. If damage is found, file a claim with the carrier and then contact ADTRAN®Customer Service.
Pull the ejector tab on the bottom of the Total Access 4303 Plus DC Power Supply into the down position.
Hold the Total Access 4303 Plus DC Power Supply by the front panel while supporting the bottom edge of the module and align the module edge with the guide groove for slot PS-A or PS-B in the chassis. If using only one Total Access Plus DC Power Supply module, insert the module in slot
PS-A in order to use the alarm relay outputs.
Gently but firmly push the module into the selected slot. Simultaneous thumb pressure at the top (above the POWER LED) and at the bottom (below the electrostatic caution symbol) of the module will ensure a good seat of the module pins into the backplane connector.
Apply power to the shelf and verify that the POWER LED is green. If the POWER LED does not illuminate, disconnect power, and verify polarity.
Push the ejector tab up and closed against the module front panel.
To verify one or both –48 VDC supply voltages, use the SCU terminal and navigate to the following path:
System Status/System Alarms/–48V Bus
COMPLIANCE
This product is NRTL listed to the applicable UL standards. The Total Access 4303 Plus DC Power Supply is intended for installation in a type “B” or “E” enclosure in a Restricted Access Only area. The Total Access 4303 shelf Frame Ground terminal must be connected to an earth ground to ensure that the front panel of the Total Access 4303 Plus DC Power Supply is properly grounded via the backplane connector.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the user’s authority to operate this equipment.
WARRANTY
ADTRAN will replace or repair this product within the warranty period if it does not meet its published specifications or fails while in service. Warranty information can be found at www.adtran.com/warran­ty. U.S. and Canada customer Faxback: 877-457-5007, Document 414.
TOTAL ACCESS 4303 PLUS DC POWER SUPPLY
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com