ADTRAN 4303 DC User Manual

TOTAL ACCESS®4303 DC POWER SUPPLY
DC SUPPLY
CLEI: SLPOCD0C_ _
DC SUPPLY
1200335L1
61200335L1-22A
0210
For a complete Installation and Maintenance Practice (P/N 61200335L1-5): (877) 457-5007, faxback Document 862. Please have your fax number ready.
C A U T I O N C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
FRONT PANEL LEDs
POWER Off Both -48V fuses blown, power not supplied to the shelf, or
incorrect polarity on the voltage supplied to the shelf
Green Power supplied is the correct voltage and polarity; backplane
and hot insertion voltages correct
Amber -48 V input and hot insertion voltage present; no backplane
voltage
Red -48 V input present; no backplane voltage and no hot
insertion voltage
TEMP Off Normal
Red Over-temperature condition
FUNCTIONALITY
The Total Access 4303 DC Power Supply furnishes the voltages necessary for proper backplane operation. The DC Power Supply also provides the voltages that enable hot insertion of the option cards and SCUs. The DC Power Supply does not, however, provide the voltages necessary to power individual option cards or the SCUs as each card has itís own DC-DC supply.
In addition, the DC Power Supply in slot PS-A provides alarm relay output functionality. If only one DC Power Supply is used, place the DC Power Supply in PS-A to provide alarm relay facilities. The DC Power Supply, as well as all Total Access 4303 option modules and SCUs, has protection against the wrong voltage polarity being applied to the shelf.
JOBAID
#61200335L1-22A#
INSTALLATION
Insert the module into either the slot labeled PS-A or PS-B.
When power is supplied to the shelf, verify that the Power LED is green.
If power is supplied to the shelf and the Power LED does not illuminate, remove
power and verify polarity.
To verify one or both -48V supply voltages, use the SCU terminal menus (see SCU
Job Aid, 61200334L1-22) and navigate the following path:
System Status/System Alarms/-48V Bus
SPECIFICATIONS
Specifications
Input Voltage -42 to -54 DC Operating temperature 0ºC to 50ºC Storage temperature -40ºC to 70ºC Over-temperature Indication 90ºC ± 10ºC
-48V short circuit protection Fused (1 amp) Backplane voltage short circuit protection Self-mending Relative Humidity To 95% noncondensing Compliance FCC Part 15, UL 60950, NEBS Level 3 Warranty 10 years
COMPLIANCE
The Total Access 4303 DC Power Supply is NRTL listed to the applicable UL standards. The Total Access DC Power Supply is to be installed in a restricted access location and in a Type “B” or “E” enclosure only.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the user’s authority to operate this equipment.
WARRANTY
Warranty for Carrier Networks products manufactured by ADTRAN and supplied under Buyer’s order for use in the U.S. is ten (10) years. For a complete copy of ADTRAN’s U.S. and Canada Carrier Networks Equipment Warranty (P/N 60000087-10): (877) 457-5007, Faxback Document 414.
Code Input Output
Power Code (PC) F C Telecommunication Code (TC) – Installation Code (IC) A
TOTAL ACCESS®4303 DC POWER SUPPLY
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com
61200335L1-22A