ADTRAN 239 H4R User Manual

JOBAID
239 H4R
CLEI: T1R5YP3D_ _
239 H4R
1221445L1
LP1
NET
LP2
LP1
LP2 LL RL
(Y) (G)
/
CUST
61221445L1-22B
0205
CARD EDGE PIN ASSIGNMENTS
LOOPBACK AND CONTROL CODES
Refer to the Installation and Maintenance Practice of the H4TU-C or H4TU-R used in the circuit for a list of loopback codes.
For a complete Installation and Maintenance Practice (P/N 61221445L1-5) faxback: (877) 457-5007, faxback Document 755. Please have your fax number ready.
C A U T I O N C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
STATUS LEDs
LP1/LP2 NET Off No span power present
Solid Green Synchronized with an SNR margin greater than the user defined SNR
Margin Alarm Threshold
Fast Blinking (Blinking 3 times per second) Attempting to synchronize with the
Green H4TU-C
Slow Blinking (Blinking 1 time per second) Synchronized with an SNR margin
Green greater than the user defined SNR Margin Alarm Threshold and the
pulse attenuation is greater than the user defined Loop Attenuation Alarm Threshold
Solid Yellow Synchronized with an SNR margin greater than 0 dB but less than
the user defined SNR Margin Alarm Threshold
Slow Blinking Synchronized with an SNR margin greater than 0 dB but less than the
Yellow user defined SNR Margin Alarm Threshold and the pulse attenuation
is greater than the user defined Loop Attenuation Alarm Threshold
Solid Red Synchronized with an SNR margin of 0 dBSlow Blinking (Blinking 1 time per second) Synchronized with an SNR margin of 0 dB
Red and the pulse attenuation is greater than the user defined Loop
Attenuation Alarm Threshold
LP1/LP2 CUST Off No span power present
Solid Green Synchronized with an SNR margin greater than the user defined SNR
Margin Alarm Threshold
Fast Blinking (Blinking 3 times per second) Attempting to synchronize with the
Green H4TU-R
Slow Blinking (Blinking 1 time per second) Synchronized with an SNR margin
Green greater than the user defined SNR Margin Alarm Threshold and the
pulse attenuation is greater than the user defined Loop Attenuation Alarm Threshold
Solid Yellow Synchronized with an SNR margin greater than 0 dB but less than the
user defined SNR Margin Alarm Threshold
Slow Blinking Synchronized with an SNR margin greater than 0 dB but less than the
Yellow user defined SNR Margin Alarm Threshold and the pulse attenuation
is greater than the user defined Loop Attenuation Alarm Threshold
Solid Red Synchronized with an SNR margin of 0 dBSlow Blinking (Blinking 1 time per second) Synchronized with an SNR margin of 0 dB
Red and the pulse attenuation is greater than the user defined Loop
Attenuation Alarm Threshold
LL/RL Green Indicates a loopback at the H4R toward the H4TU-R is active
Yellow Indicates a loopback at the H4R toward the H4TU-C is activeBlinking Armed but not in loopback.
Yellow
Pin No. Designation Description Pin No. Designation Description
1 GND Ground 7 NC No Connection
2 NC No Connection 8 T Network Loop 2 Tip
3 T1 Customer Loop 1 Tip 9 R Network Loop 2 Ring
4 R1 Customer Loop 1 Ring 10 GND Ground
5 T1 Network Loop 1 Tip 11 T Customer Loop 2 Tip
6 R1 Network Loop 1 Ring 12 R Customer Loop 2 Ring
#61221445L1-22B#
239 H4R
HDSL4 LOOP SPECIFICATIONS FOR OPTIMUM OPERATION
NOTE: The H4TU-Cs P/N 1221401L6, 1221403L6, 1221404L6 support only one H4R in the HDSL4
circuit.
HDSL4 circuit containing no H4Rs will reach up to 16 kft on the local loop (24
AWG )
HDSL4 circuit containing one H4R will reach up to 16 kft on the first segment and
15 kft on the second segment (24 AWG).
HDSL4 circuit containing two H4Rs will reach to 13.5 kft on the first segment, 14 kft
on the second segment, and 15 kft on the third segment (24 AWG). *
NOTE: Refer to the H4TU-C or H4TU-R Installation and Maintenance Practice, Section HDSL4,
Deployment Guidelines, for other loop parameters including Insertion Loss, Pulse Attenuation, and Resistance Budgets for span powering
*This is one example of a circuit with 2 H4Rs. Other loop length configurations are possible in compliance with loop resistance restraints. Refer to the H4R Installation and Maintenance Practice, Section HDSL4 Deployment Guidelines, for other loop parameters including Insertion Loss, Pulse Attenuation, and Resistance Budgets for span powering.
UNIT RESISTANCE
Measurements are with no power applied
The H4R Tip-to-Ring resistance is approximately 6 for each pair.
COMPLIANCE
This product complies with UL 60950, third edition. It is intended for installation in restricted access locations only and in equipment with a Type “B” or “E” installation code. Ensure chassis ground is properly connected.
WARRANTY
Warranty for Carrier Networks products manufactured by ADTRAN and supplied under Buyer’s order for use in the U.S. is ten (10) years. For a complete copy of ADTRAN’s U.S. and Canada Carrier Networks Equipment Warranty (P/N 60000087-10): call (877) 457-5007, faxback Document 414.
H4TU-C VMDF H4R1 H4R2 H4TU-R
TURNUP & TROUBLESHOOTING GUIDE
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com
61221445L1-22B
239 H4R Capacity Guidelines for ADTRAN Housings
PART No. Description CLEI CODE Slot Stub H4R Capacity Material
Above Below
Ground Ground
1150027L1 239/439 Housing DDMOABA1MA 4 Air 4 4 Stainless/Poly 1150027L2 239/439 Housing DDMOBBA1MA 4 Gel 4 4 Stainless/Poly 1152010L3 239/439 Housing DDMOBAE1RA 2 Gel 2 2 Polymer 1152010L4 239/439 Housing DDMOAAE1RA 2 Air 2 2 Polymer 1150057L1 Universal Housing DDMODAO1RA 4 Air 4 4 Stainless Steel 1150057L2 Universal Housing DDMOCAO1RA 4 Gel 4 4 Stainless Steel 1150058L1 Universal Housing DDMOEEO1RA 8 Air 8 8 Stainless Steel 1150058L2 Universal Housing DDMOFE01RA 8 Gel 8 8 Stainless Steel 1190816L1 16-Slot BG Housing DDMOES0IRA 16 Air 16 16 Stainless Steel 1190816L2 16-Slot AG Housing DDMOFS0IRA 16 Gel 16 16 Stainless Steel 1190816L3 16-Slot AG Housing DDMOMS01RA 16 Air 16 16 Stainless Steel
239 H4R Capacity Guidelines for Other Housings
Manufacturer Description Manufacturer’s Part Number Slot Stub H4R Capacity Material
Above Below
Ground Ground
ADC Radiator II SPX-HRXC-30-AG-016GT 16 Air 16 16 Stainless Steel ADC Radiator II SPX-HRXC-30-BG-016GT 16 Gel 16 16 Stainless Steel ADC Radiator SPX-HRXC-30-B1 8 Air 8 8 Stainless Steel Circa Telecom HDSL-12A 760005 12 Air 12 12 Polymer Circa Telecom HDSL-12B 760006 12 Gel 12 12 Polymer Arris Keptel®Inter Link™809 RF809A3-XXX or RF809B3-XXX 12 Gel 8
1
N/A Polymer
Arris Keptel®Inter Link™818/819 RF819A1 or RF819A2 25 Air 12 216
3, 4
Polymer
Arris Keptel®Inter Link™818/819 RF819B1 or RF819B2 25 Gel 12 216
3, 4
Polymer
Arris Keptel®Inter Link
RF820AX or
820 Family RF820BX 2-8 Air Full Full Polymer
Arris Keptel®Inter Link
RF820AX or
820 Family RF820BX 2-8 Gel Full Full Polymer
1
The recommended 8 slot assignments for above ground installation are as follows: 1, 3, 4, 6, 7, 9, 10, 12.
2
The recommended 12 slot assignments for above ground installation are as follows: Chamber 1: 1, 4, 7, 8, 11, 14 and Chamber 2: 15, 17, 19, 20, 23, 25
3
For 16 slot use, the ambient air temperature measured 1 ft away and parallel to the housing should not exceed 115ºF (46.1ºC).
4
The recommended 16 slot assignments for below ground installation are as follows: Chamber 1: 1, 3, 5, 7, 8, 10, 12, 14 and Chamber 2: 15, 16, 18, 19, 20, 22,
24, 25
Code Input Output
Power Code (PC) C C
Telecommunication Code (TC) X X
Installation Code (IC) A
First Segment
Second Segment Third Segment