ADC DVLRCS800 User Manual

FCC ID: F8I-DVLRCS800 - User Manual Part 4
ADCP-75-124 Issue B April 2002 Section 4: Operation
Use the following procedure to turn-up the system:
1. Temporarily disconnect the external alarm system or notify the alarm system provider that testing is in progress.
2. If turning-up multiple HU and RU systems that have not been configured for operation before, temporarily disconnect the CAN cables from the NET IN and NET OUT ports of each HU.
Note: By default, all HU’s and RU’s are programmed with the same site number and
name. This can cause problems for the Digivance EMS if multiple HU’s with the same site number and site name are networked together through the CAN interface. It is therefore advisable to temporarily disconnect the CAN interface cables from the HU until a unique site number and name can be entered for each HU and its corresponding RU.
3. Determine if the forward path composite input signal level at the Host Unit FORWARD RF IN port is between –10 and –40 dBm and adjust level by installing an external
attenuator if required. Refer to Section 2.3 for the calculation and adjustment procedure.
4. Connect the EMS computer (if not already connected) to the SERVICE connector on the HU or STM front panel. If necessary, a separate laptop computer loaded with the EMS software can be temporarily connected and used to initially configure the system.
5. Place the ON/OFF switch on the HU in the ON position (press I).
6. Place the ON/OFF switch on the STM in the ON position (press I).
7. Wait 6 to 8 seconds for the HU and the RU modules to initialize and then observe the LED indicators on the HU, STM and LPA. Refer to Section 5 for the troubleshooting procedures if the indicators do not respond as specified.
HOST UNIT SPECTRUM TRANSPORT MODULE LINEAR POWER AMPLIFIER
POWER Green
AC POWER Green FAIL Off
STANDBY Off STANDBY Off HOST UNIT Green HOST UNIT Green
REMOTE UNIT Green
DRIVE Green, Yellow, or Red PA Green PORT 1/PORT 2 Green VSWR Green PORT 3 Green
(diversity unit only)
STM Green
PORT 1/PORT 2 Green
PORT 3 Green (diversity unit only)
SHUTDOWN Red Digital Display FORCED
SHUTDOWN
8. Start up the Digivance EMS software program. The EMS main window will open as shown in Figure 4-1. Note: The EMS software should be installed on a PC-type computer and the PC’s COM port should be configured to interface with the HU. For information about installing the EMS software and configuring the PC’s COM port, refer to the Digivance Element Management System Software User Manual (ADCP-75-125).
© 2002, ADC Telecommunications, Inc.
Page 4-3
ADCP-75-124 Issue B April 2002 • Section 4: Operation
Click to view drop down menu
Figure 4-1. Digivance Element Management System Main Window
9. Open the View drop down menu and connect to the Host and Remote pair by selecting “NotNamed/NotNamed”. The HOST Alarms display and the REMOTE Alarms display will open within the main window as shown in Figure 4-2.
10. Download the system software to both the Host and the Remote unit. Refer to Section 2.2 for details.
Host/Remote pair site name
Clicking on the tabs in this list will open the cor­responding display.
Page 4-4
© 2002, ADC Telecommunications, Inc.
Figure 4-2. Selecting Display Tabs
ADCP-75-124 Issue B April 2002 Section 4: Operation
11. Click on the HOST Config tab and on the REMOTE Config tab (see Figure 4-2). The HOST Config display and the REMOTE Config display will open within the main window.
12. Enter the Site Name and Site Number for both the HOST and the REMOTE unit. Refer to
Section 2.4 for details.
13. Reconnect the CAN cables to the HU’s NET IN and NET OUT ports.
14. Verify that no Major (except Major Extern Alarm) or Minor alarms are being reported in either the HOST or REMOTE Alarm displays and that all alarm fields (except Major Extern Alarm) are green.
15. Click on the HOST RF tab (see Figure 4-2). The HOST RF display will open within the main window.
16. Enter the Host Fwd Att (Forward Attenuation) values. This sets the forward input RF signal level at the HU. Refer to Section 2.5 for details. By default, this value is set to 0 dB. If the DRIVE LED on the HU front panel was red, it should turn green when this step is completed.
17. Determine if the RF output power at the STM ANTENNA is at the correct level per channel up to a composite maximum of +44.5 dBm. Refer to Section 2.6 for details.
18. Click on the REMOTE LPA tab (see Figure 4-2). The REMOTE PA display will open within the main window.
19. Enter the Remote Fwd Att value. This adjusts the RF output signal level at the STM ANTENNA port. Refer to Section 2.7 for details. By default this value is set to 0 dB.
20. Place the RF ON/OFF switch (on LPA front panel) in the ON position.
21. Verify that the SHUTDOWN LED indicator (on LPA front panel) turns from red to off and the Digital Display message changes from FORCED SHUTDOWN to NORMAL OPERATION.
22. Click on the HOST RF tab (see Figure 4-2). The HOST RF display will open within the main window.
23. Enter the Host Rev Att (Reverse Attenuation), and Host Div Rev Att (Diversity Reverse Attenuation) values. This sets the reverse output RF signal levels at the HU. Refer to
Section 2.8 for details.
24. If a delay adjustment is required per the system design plan, enter the Host Fwd Delay, Host Rev Delay, and Host Div Rev Delay values. By default, the delay values are set to 0. Refer to Section 2.9 for details.
25. If a separate laptop computer loaded with the EMS software was used to initially configure the system, disconnect the laptop computer from the SERVICE connector on the HU front panel.
Note: Each HU and RU pair will generally remain permanently connected to a PC-type
desktop computer loaded with the EMS software. When two or more systems are connected together through the CAN interface, only one EMS computer is required to manage the networked HU and RU systems. The EMS computer may be connected to the SERVICE port on any one of the HUs in the network.
Page 4-5
© 2002, ADC Telecommunications, Inc.
ADCP-75-124 Issue B April 2002 • Section 4: Operation
26. Reconnect the external alarm system or notify the alarm system provider that the turn-up process has been completed.
2.2 Download HU and RU System Software
The HU’s and RU’s may require a system software download to make them operational. Use the following procedure to download the system software:
1. Click on the HOST Prg Load tab and on the REMOTE Prg Load tab. The HOST Prg
Load display and the Remote Prg Load display will open within the EMS main window
as shown in Figure 4-3.
Click to start down­load to HOST.
Verify software version before starting download.
Click to open Select Control Program window for HOST
Click to start down­load to REMOTE.
Click to open Select Control Program win­dow for REMOTE.
Verify software version before starting download.
Figure 4-3. HOST and REMOTE Prg Load Displays
2. Click on the HOST Select button (see Figure4-3). The Select Control Program File window will open as shown in Figure 4-4. Browse until the folder where the Control Program files are located is selected and the software files are displayed in the window.
Page 4-6
© 2002, ADC Telecommunications, Inc.
Loading...
+ 9 hidden pages