AC Tech ESV751N01SXB, ESV251N02SXB, ESV371N02YXB, ESV751N02YXB, ESV112N02YXB Operating Instructions Manual

...
V0100
SV01B
Operating Instructions
SMVector
- frequency inverter
0.5 … 10 HP (0.37 kW… 7.5 kW)
Copyright © 2006 AC Technology Corporation
All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from AC Technology Corporation. The information and technical data in this manual are subject to change without notice. AC Technology Corporation makes no warranty of any kind with respect to this material, including, but not limited to, the implied warranties of its merchantability and fitness for a given purpose. AC Technology Corporation assumes no responsibility for any errors that may appear in this manual.
All information given in this documentation has been carefully selected and tested for compliance with the hardware and software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for damages that may occur. Any necessary corrections will be implemented in subsequent editions.
This document printed in the United States
1
1 Safety information ................................................................3
2 Technical data ......................................................................5
2.1 Standardsandapplicationconditions......................................................5
2.2 Ratings......................................................................................................6
3 Installation ............................................................................8
3.1 Dimensionsandmounting........................................................................8
3.2 Electricalinstallation.................................................................................9
3.2.1
PowerConnections...................................................................................9
3.2.2
Fuses/cablecross-sections....................................................................11
3.2.3
Controlterminals.....................................................................................12
4 Commissioning ..................................................................13
4.1 LocalKeypad&Display.........................................................................13
4.2 DriveDisplaysandModesofOperation.................................................14
4.3
Parametersetting....................................................................................14
4.4
Electronicprogrammingmodule(EPM).................................................14
4.5
Parametermenu.....................................................................................15
4.5.1
BasicSetupParameters.........................................................................15
4.5.2
I/OSetupParameters.............................................................................18
4.5.3
AdvancedSetupParameters..................................................................22
4.5.4
PIDParameters.......................................................................................25
4.5.5
VectorParameters..................................................................................27
4.5.6
NetworkParameters...............................................................................29
4.5.7
DiagnosticParameters...........................................................................29
5 Troubleshooting and Diagnostics ....................................31
5.1 Status/WarningMessages......................................................................31
5.2 DriveCongurationMessages...............................................................32
5.3
FaultMessages.......................................................................................33
Contents
This documentation applies to the SMV frequency inverter, and contains important technical data and describes installation, operation, and commissioning.
These instructions are only valid for SMV frequency inverters with software rev 20 (see drive nameplate).
Please read the instructions before commissioning.
CA B D E F
Type: ESV751N04TXB
Id-No: 00000000
INPUT:
3 (3/PE) 400/480 V
2.9/2.5 A 50-60 HZ
OUTPUT:
3 (3/PE) 0 - 400/460 V
2.4/2.1 A
0.75 KW/1HP 0 - 500 HZ
For detailed information
refer to instruction
Manual: SV01
000000000000000000
ESV751N04TXB000XX####
V0101
E
Hardware Version
F
Software Version
• 1 SMV inverter (ESV...) Lenze/AC Tech
.
Lenze/AC Tech representative.
2
About these instructions
A
Certifications
C
Input Ratings
B
Type
D
Output Ratings
Scope of delivery Important
with EPM installed (see Section 4.4)
• 1 Operating Instructions
After receipt of the delivery, check immediately whether the items delivered match the accompanying papers. not accept any liability for deficiencies claimed subsequently.
Claim
• visible transport damage immediately to the forwarder.
• visible deficiencies / incompleteness immediately to your
1 Safety information
General
Some parts of Lenze / AC Tech controllers can be electrically live and some surfaces can be hot. Non-authorized removal of the required cover, inappropriate use, and incorrect installation or
operation creates the risk of severe injury to personnel or damage to equipment. All operations concerning transport, installation, and commissioning as well as maintenance must
be carried out by qualified, skilled personnel who are familiar with the installation, assembly, commissioning, and operation of variable frequency drives and the application for which it is being used.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not change any insulation distances during transport, handling, installation or maintenance.
Do not touch any electronic components or contacts. This drive contains electrostatically sensitive components, which can easily be damaged by inappropriate handling. Static control precautions must be adhered to during installation, testing, servicing and repairing of this drive and associated options. Component damage may result if proper procedures are not followed.
This drive has been tested by Underwriters Laboratory (UL) and is an approved component in compliance with UL508 Safety Standard.
This drive must be installed and configured in accordance with both national and international standards. Local codes and regulations take precedence over recommendations provided in this and other Lenze / AC Tech documentation.
The SMVector drive is considered a component for integration into a machine or process. It is neither a machine nor a device ready for use in accordance with European directives (reference machinery directive and electromagnetic compatibility directive). It is the responsibility of the end user to ensure that the machine meets the applicable standards.
Electrical connection
When working on live drive controllers, applicable national safety regulations must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g.
cable cross-sections, fuses, protective earth [PE] connection). While this document does make recommendations in regards to these items, national and local codes must be adhered to.
The documentation contains information about installation in compliance with EMC (shielding, grounding, filters and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required limit values demanded by EMC legislation.
Application
The drive must not be used as a safety device for machines where there is a risk of personal injury or material damage. Emergency Stops, over-speed protection, acceleration and deceleration limits, etc must be made by other devices to ensure operation under all conditions.
The drive does feature many protection devices which are aimed at protecting the drive and the driven equipment by generating a fault and shutting the drive and motor down by removing power. Mains power variances can also result in shutdown of the drive. When the fault condition disappears or is cleared, the drive can be configured to automatically restart, it is the responsibility of the user and/or OEM and/or integrator to ensure that the drive is configured for safe operation.
3
Safety information
4
Safety information
All safety information given in these Operating Instructions have the same layout:
Signal Word! (characterizes the severity of the danger)
Note (describes the danger and informs on how to proceed)
Icon
Signal Words
Warning of hazardous electrical voltage
DANGER!
Warns of impending danger.
Consequences if disregarded: Death or severe injuries.
Warning of a general danger
WARNING!
Warns of potential, very hazardous situations.
Consequences if disregarded: Death or severe injuries.
Warning of damage to equipment
STOP!
Warns of potential damage to material and equipment.
Consequences if disregarded: Damage to the controller/drive or its environment.
Information
Note
Designates a general, useful note.
If you observe it, handling the controller/drive system is made easier.
Note for UL approved system with integrated controllers: UL warnings are notes which
apply to UL systems. The documentation contains special information about UL.
Warnings!
• Suitable for use on a circuit capable of delivering not more than 200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive.
• Use minimum 75 °C copper wire only.
• Shall be installed in a pollution degree 2 macro-environment.
Operation
Systems including controllers must be equipped with additional monitoring and protection devices according to the corresponding standards (e.g. technical equipment, regulations for prevention of accidents, etc.). The controller may be adapted to your application as described in this documentation.
DANGER!
• After the controller has been disconnected from the supply voltage, live components and power connection must not be touched immediately, since capacitors could be charged. Please observe the corresponding notes on the controller.
• Please close all protective covers and doors prior to and during operation.
• Do not cycle input power to the controller more than once every two minutes.
5
Technical data
2 Technical data
2.1 Standards and application conditions
Conformity
CE Low Voltage Directive (73/23/EEC)
Approvals
UL 508C
Underwriters Laboratories - Power Conversion Equipment
Input voltage phase imbalance
< 2%
Humidity
< 95% non-condensing
Temperature range
Transport -25 … +70°C
Storage -20 … +70°C
Operation -
10 … +55°C (with 2.5%/°C current derating above +40°C)
Installation height
0 … 4000m a.m.s.l.
(with 5%/1000 m current derating above 1000m a.m.s.l.)
Vibration resistance
acceleration resistant up to 1.0g
Earth leakage current
> 3.5 mA to PE
Enclosure
IP 2
1 / IP 31 / NEMA 1
Protection measures against
short circuit, earth fault, phase loss, over voltage, under voltage, motor stalling, over temperature, motor overload
ESV251N01SXB
ESV371N01SXB
ESV751N01SXB
ESV251N02SXB
ESV371N02YXB
ESV751N02YXB
ESV112N02YXB
ESV152N02YXB
ESV222N02YXB
ESV
112N02TXB
ESV152N02TXB
ESV222N02TXB
ESV402N02TXB
ESV552N02TXB
ESV752N02TXB
6
Technical data
2.2 Ratings
120VAC Doubler / 240VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
(120V) Iin (240V) I
n
CLim
max
(2)
0.33 / 0.25
120 V Single-phase (1/N/PE)
(90 …
132 V)
OR
240 V Single-phase (2/PE)
(170 … 264 V)
6.8 3.4 1.7 200 24
0.5 / 0.
37 9.2 4.
6 2.4 200 32
1 / 0.75 16.6 8.3 4.2 200 52
240VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
1~ (2/PE) Iin 3~ (3/PE) I
n
CLim
max
(2)
0.33 / 0.25
240 V Single Phase (2/PE)
3
.4
- 1
.7 200 20
0.5 / 0.37
240 V Single-phase (2/PE)
OR
240 V Three-phase (3/PE)
(170 … 264 V)
5.1 2.9 2.4 200 27
1
/ 0.75 8.8 5.0 4.2 200 4
1
1.5 / 1.1 12.0 6.9 6.0 200 6
4
2 / 1.5 13.3 8.1 7.0 200 75
3
/ 2.2 17.1 10.8 9.6 200 1
03
1.5 / 1.1
240 V Three-phase (3/PE)
(
170 V … 264 V)
- 6
.9 6.0 200 64
2 / 1.5 - 8.
1 7.0 200 75
3 / 2.2 - 1
0.8 9.6 200 103
5 / 4.0 - 1
8.6 16.5 200 154
7.5 / 5.5 - 2
6 23 200 225
10 / 7.5 - 33 29 200 274
(1) Frequency Range: 48 Hz … 62 Hz (2) Current Limit (CLim) is a percentage of the output current, In. CLim
max
is the maximum setting for P171.
ESV371N04TXB
ESV751N04TXB
ESV112N04TXB
ESV152N04TXB
ESV222N04TXB
ESV402N04TXB
ESV552N04TXB
ESV752N04TXB
ESV75
1N06TXB
ESV152N06TXB
ESV222N06TXB
ESV402N06TXB
ESV552N06TXB
ESV752N06TXB
The SMVector drive is designed to operate at the Nominal Output Current (In) shown in the Ratings tables for most standard applications and industrial environments. The drive output current or operating temperature may need to be limited as described
below:
For combinations of the above, please consult Lenze / AC Tech applications support for proper derating.
7
Technical data
480VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
I
n
CLim
max
(2)
400V 480V 400V 480V 400V 480V
0.5 / 0.37
400 V Three-phase (3/PE)
(
340 … 440 V)
OR
480 V Three-phase (3/PE)
(340 … 528 V)
1.7 1.5 1.3 1.1 175 200 2
3
1 / 0.75 2.9 2.5 2.4 2.
1 175 200 37
1.5 / 1.1 4.2 3
.6 3.5 3.0 175 200 48
2 / 1.5 4.7 4.
1 4.0 3.5 175 200 57
3 / 2.2 6.1 5.4 5.5 4.8 1
75 200 87
5 / 4.0 1
0.6 9.3 9.4 8.2 175 200 128
7.5 / 5.5 1
4.2 12.4 12.6 11.0 175 200 178
10 / 7.5 18.1 15.8 16.1 14.0 175 200 208
600VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
I
n
CLim
max
(2)
1 / 0.75
600 V Three-phase (3/PE)
(425 …
660 V)
2.0 1
.7 200
37
2 / 1.5 3.2 2.7 200 51
3 / 2.2 4.4 3
.9 200 68
5 / 4.0 6
.8 6.1 200 101
7.5 / 5.5 1
0.2 9 200 148
10 / 7.5 12.4 11 200 1
72
(1) Frequency Range: 48 Hz … 62 Hz (2) Current Limit (CLim) is a percentage of the output current, In. CLim
max
is the maximum setting for P171.
For 480VAC models, the CLim
max
value in the 480V column of the table is used when P107 is set to 1.
The CLim
max
value in the 400V column is used when P107 is set to 0.
STOP!
Drive Derating
For installations above 1000m a.m.s.l., derate I
n
by 5% per 1000m, do not exceed
4000m a.m.s.l.
Operation above 40°C, derate In by 2.5% per °C, do not exceed 55°C.
• Carrier Frequency (P166):
- If P166=2 (8 kHz), derate In to 92% of drive rating or do not exceed 33°C ambient
- If P166=3 (10 kHz), derate In to 84% of drive rating or do not exceed 27°C ambient
ESV251…XB ESV371…XB ESV751…XB
ESV112…XB ESV152…XB ESV222…XB
ESV402…XB
ESV552…XB ESV752…XB
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive vibration or excessive temperatures. Contact Lenze / AC Tech for more information.
8
Installation
3 Installation
3.1 Dimensions and mounting
b1
a1
a
b
c
b2
4 X #10
18 lb-in
4 X M5
20 Nm
( )
s1 s1
s2
s2
V0102
Type
a
in (mm)
a1
in (mm)b in (mm)
b1
in (mm)
b2
in (mm)c in (mm)
s1
in (mm)
s2
in (mm)m lb (kg)
3.90 (99)
3.
10
(79)
7.50
(190)
7.00
(178)
0.25 (6)
4.35
(110)
0.6
(15)
2.0
(50)
2.0
(0.9)
3.90 (99)
3.
10
(79)
7.50
(190)
7.00
(178)
0.25 (6)
5.45
(138)
0.6
(15)
2.0
(50)
2.8
(1.3)
3.90 (99)
3.
10
(79)
7.50
(190)
7.00
(178)
0.25 (6)
5.80
(147)
0.6
(15)
2.0
(50)
3.2
(1.5)
5.12
(130)
4.25
(1
08)
9.83
(250)
9.30
(236)
0.25 (6)
6.25
(159)
0.6
(15)
2.0
(50)
6.0
(2.0)
Warning!
ESV…N01S…
ESV…N01S… ESV…N01S…
ESV…N02Y… (2/PE AC)
ESV…N02Y… (
1/N/PE AC)
ESV…N02S… (2/PE AC)
ESV…N02S… (
1/N/PE AC)
9
Installation
3.2 Electrical installation
3.2.1 Power Connections
DANGER!
Hazard of electrical shock! Circuit potentials are up to 600 VAC above earth ground. Capacitors retain charge after power is removed. Disconnect power and wait at least three minutes before servicing the drive.
STOP!
• Verify mains voltage before connecting to drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.
• Do not cycle mains power more than once every two minutes. Damage to the drive will result.
3.2.1.1 Mains connection to 120VAC Single-Phase Supply
PE L1 L2 N
PE L1 N
3.2.1.2 Mains connection to 240VAC Single-Phase Supply
PE L1 L2 N
PE L1 L2
PE L1 L2 N
PE L1 N
PE L1 L2 L3
PE L1 L2
PE L1 L2 L3
PE L1 N
PE L1 L2
PE L1 L2
PE L1 L2
PE L1 N
ESV…N02Y… ESV…N02T… ESV…N04T… ESV…N06T… (3/PE AC)
10
Installation
3.2.1.3 Mains connection to Three-Phase Supply
PE L1 L2 L3
PE L1 L2 L3
3.2.1.4 Motor Connection
U/
T1
V/T2 W/T3 PE
PES
PES
M
3~
PE
PES
PES
PES
PE
PES = Protective Earth Shielding
Mains and Motor Terminations
12 lb-in (1.3 Nm)
0.25 in (6mm)
WARNING!
Leakage current may exceed 3.5 mA AC. Minimum size of the protective earth conductor shall comply with local safety regulations for high leakage current equipment.
ESV251N01SXB
ESV371N01SXB
ESV751N01SXB
ESV251N01SXB, ESV251N02SXB, ESV371N01SXB, ESV371N02YXB
ESV751N01SXB, ESV751N02YXB
ESV112N02YXB
ESV152N02YXB
ESV222N02YXB
ESV
371N02YXB, ESV751N02YXB
ESV112N02YXB, ESV152N02YXB, ESV112N02TXB, ESV152N02TXB
ESV222N02YXB, ESV222N02TXB
ESV402N02TXB
ESV552N02TXB
ESV752N02TXB
ESV
371N04TXB...ESV222N04TXB
ESV552N04TXB
ESV752N04TXB
ESV402N04TXB
ESV75
1N06TXB...ESV222N06TXB
ESV402N06TXB
ESV552N06TXB
ESV752N06TXB
11
Installation
3.2.2 Fuses/cable cross-sections
Note
Observe local regulations. Local codes may supersede these recommendations
Type
Recommendations
Fuse
Miniature
circuit
breaker
(1)
Fuse
(2)
or
Breaker
(3)
(N. America)
Input Power Wiring
(L1, L2, L3, PE)
[mm²] [AWG]
120V
1~
(1/N/PE)
M10 A C10 A 10 A 1.5 14
M16 A C16 A 15 A 2.5 1
4
M25 A C25 A 25 A 4 1
0
240V
1
~
(2/PE)
M10 A C10 A 10 A 1.5 14
M16 A C16 A 15 A 2.5 1
4
M20 A C20 A 20 A 2.5 1
2
M25 A C25 A 25 A 2.5 1
2
M32 A C32A 32 A 4 1
0
240V
3
~
(3/PE)
M10 A C10 A 10 A 1.5 14
M12 A C12 A 12 A 1.5 14
M20 A C20 A 20 A 2.5 1
2
M32 A C32 A 32 A 4.0 1
0
M35 A C35 A 35 A 6.0 8
M45 A C45 A 45 A 1
0 8
400V
or 480V
3~(3/PE)
M10 A C10 A 10 A 1.5 14
M16 A C16 A 20 A 2.5 1
4
M20 A C20 A 20 A 2.5 1
4
M25 A C25 A 25 A 4.0 1
0
600V
3~(3/PE)
M10 A C10 A 10 A 1.5 14
M12 A C12 A 12 A 1.5 14
M16 A C16 A 15 A 2.5 1
4
M20 A C20 A 20 A 2.5 1
2
(1) Installations with high fault current due to large supply mains may require a type D circuit breaker. (2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.
(3) Thermomagnetic type breakers preferred.
Observe the following when using Ground Fault Circuit Interrupters (GFCIs):
• Installation of GFCI only between supplying mains and controller.
• The GFCI can be activated by:
- capacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)
- connecting several controllers to the mains at the same time
- RFI filters
12
Installation
3.2.3 Control terminals
Terminal Data for control connections
1
Digital Input: Start/Stop input resistance = 4.
3
k
2
Analog Common
5
Analog Input: 0...
1
0 VDC input resistance: >50 k
6
Internal DC supply for speed pot +
1
0 VDC, max. 10 mA
25
Analog Input: 4...20 mA input resistance: 250
4
Digital Reference/Common +1
5 VDC / 0 VDC, depending on assertion level
11
Internal DC supply for external devices +
1
2 VDC, max. 50 mA
13A
Digital Input: Configurable with P1
21
input resistance = 4.3k
13B
Digital Input: Configurable with P
1
22
13C
Digital Input: Configurable with P1
23
14
Digital Output: Configurable with P1
42 DC 24 V / 50 mA; NPN
30
Analog Output: Configurable with P1
50…P155 0…10 VDC, max. 20 mA
16
Relay output: Configurable with P1
40
AC 250 V / 3 A DC 24 V / 2 A … 240 V / 0.22 A, non-inductive
17
6 25 4 11
13A
13B
13C
17
51 2
14 30
16
AOUT
DIGOUT
2k … 10k
+10 V
AIN
AIN
COM
COM
ALsw
252
4 … 20 mA
52
0 … 10 V 0 … 5 V
1 2 4
13A 13B 13C
+12 VDC - 0 %
+30 VDC + 0 %
ALsw
+15V
1 2 4
13A 13B 13C
ALsw
COM
PNP NPN
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
V0109
Assertion level of digital inputs
The digital inputs can be configured for active-high or active-low by setting the Assertion Level Switch (ALsw) and P120. If wiring to the drive inputs with dry contacts or with PNP solid state switches, set the switch and P120 to “High” (+). If using NPN devices for inputs, set both to “Low” (-). Active-high (+) is the default setting.
HIGH = +12 … +30 V LOW = 0 … +3
V
Note
An fault will occur if the Assertion Level switch (ALsw) position does not match the parameter P120 setting and P100 or any of the digital inputs (P121...P123) is set to a value other than 0.
13
Commissioning
4 Commissioning
4.1 Local Keypad & Display
FWDAUTO
REV
STOP
RUN
V0105
RUN
START BUTTON: In Local Mode (P100 = 0, 4), this button will start the drive.
STOP
STOP BUTTON: stops the drive, regardless of which mode the drive is in.
WARNING!
When JOG is active, the STOP button will not stop the drive!
ROTATION: In Local Mode (P100 = 0, 4), this selects the motor rotation direction:
- The LED for the present rotation direction (FWD or REV) will be on
- Press R/F; the LED for the opposite rotation direction will blink
- Press M within 4 seconds to confirm the change
- The blinking direction LED will turn on, and the other LED will turn off
When rotation direction is changed while the drive is running, the commanded direction LED will blink until the drive is controlling the motor in the selected direction.
MODE: Used to enter/exit the Parameter Menu when programming the drive and to enter a changed
parameter value.
UP AND DOWN BUTTONS: Used for programming and can also be used as a reference for speed, PID setpoint, or
torque setpoint. When the s and t buttons are the active reference, the middle LED on the left side of the display will be on.
INDICATING LEDs
FWD/REV LEDs: Indicate the present rotation direction. See ROTATION above.
AUTO LED: Indicates that the drive has been put into Auto mode from one of the TB
13
inputs (P121…P123 set to 1…7). Also indicates that PID mode is active (if enabled).
RUN LED: Indicates that the drive is running
s t LED: Indicates that the s t are the active reference.
Note
If the keypad is selected as the auto reference (P121…P123 is 6) and the corresponding TB-13 input is closed, the AUTO LED and s t LEDs will both be on
14
Commissioning
4.2 Drive Displays and Modes of Operation
Speed Mode Display
In the standard mode of operation, the drive frequency output is set directly by the selected reference (keypad, analog reference, etc.). In this mode, the drive display will show the drive’s output frequency.
PID Mode Display
When the PID mode is enabled and active, the normal run display shows the actual PID setpoint. When PID mode is not active, the display returns to showing the drive’s output frequency.
Torque Mode Display
When the drive is operating in Vector Torque mode, the normal run display shows the drive’s output frequency.
4.3 Parameter setting
Status/fault messages Change Parameters
StoP
60.0
F.AF F.UF
CL
Err
p100
p104
p541
60 s
P194=0000
PASS
0225
M
M
15 s
M
M
20.0
12.0
V0106
4.4 Electronic programming module (EPM)
Tmd007
The EPM contains the drives operational memory. Parameter settings are stored in the EPM and setting changes are made to the “User settings” in the EPM.
An optional EPM Programmer (model EEPM1RA) is available that allows:
• An EPM to be copied directly to another EPM.
• An EPM to be copied to the memory of the EPM Programmer.
• Stored files can be modified in the EPM Programmer.
• Stored files can be copied to another EPM. As the EPM Programmer is battery operated, parameter settings can be copied to an EPM and inserted into a drive without power being applied to the drive. This means that the drive will be fully operational with the new settings on the next application of power.
Additionally, when the drives parameter settings are burned into an EPM with the EPM Programmer, the settings are saved in two distinct locations; the “User settings” and the “OEM default settings”. While the User settings can be modified in the drive, the OEM settings cannot. Thus, the drive can be reset not only to the “factory” drive default settings (shown in this manual), but can be set to the Original Machine settings as programmed by the OEM.
While the EPM can be removed for copying or to use in another drive, it must be installed for the drive to operate (a missing EPM will trigger an
fault).
15
Commissioning
4.5 Parameter menu
4.5.1 Basic Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Start Control Source
0 0 Local Keypad Use RUN button on front of drive to start
1 Terminal Strip Use start/stop circuit wired into the
terminal strip. See Section 3
.2.3
2 Remote Keypad Only Use RUN button on optional Remote
Keypad to start
3 Network Only • Start command must come from
network (Modbus, CANopen, etc)
• Requires optional communication module (refer to the network module documentation).
• Must also set one of the TB-
13 inputs to 9 (Network Enable); see P121...P123
4 Terminal Strip or Local
Keypad
Allows start control to be switched between terminal strip and local keypad using one of the TB-13
inputs.
See note below.
5 Terminal Strip or Remote
Keypad
Allows start control to be switched between terminal strip and optional remote keypad using one of the TB-13 inputs. See note below.
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled if parameters are reset back to defaults (see P199)
Note
• P100 = 4, 5: To switch between control sources, one of the TB-13 inputs (P121...P123) must be set to 08 (Control Select); TB-13x OPEN (or not configured): Terminal strip control TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4: Network can take control if P121...P123 = 9 and the corresponding TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in JOG mode.
An fault will occur if the Assertion Level switch (ALsw) position does not match the P120 setting and P100 is set to a value other than 0.
Standard Reference Source
0 0 Keypad (Local or Remote) Selects the default speed or torque
reference when no Auto Reference is selected using the TB-13 inputs
1 0-10 VDC
2 4-20 mA
3 Preset #1
4 Preset #2
5 Preset #3
6 Network
motor current rating
P1
08 =
SMV output rating
x 1
00
Example: motor = 3 amps; SMV = 4 amps; P108 = 75%
Note
Do not set above the rated motor current as listed on the motor dataplate. The motor thermal overload function of the SMV is UL approved as a motor protection device. If line power is cycled, the motor thermal state is reset to cold state. Cycling power after an overload fault could result in significantly reducing the motor life.
16
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Minimum Frequency
0.0 0.0 {Hz} P103 • P102, P103 are active for all speed references
• When using an analog speed reference, also see P160, P161
Maximum Frequency
60.0 7.5 {Hz} 500
Note
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows
(flashing).
- Release s button and wait one second
- Press s button again to continue increasing P1
03
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the motor/machine may cause damage to equipment and injury to personnel!
Acceleration Time 1
20.0 0.0 {s} 3600 • P104 = time of frequency change from 0 Hz to P167 (base frequency)
• P105 = time of frequency change from P167 to 0 Hz
• For S-ramp accel/decel, adjust P106
Deceleration Time 1
20.0 0.0 {s} 3600
Example: if P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz;
rate of frequency change from 0 Hz to 120 Hz = 40.0 s
S-Ramp Integration Time
0.0 0.0 {s} 50.0 • P106 = 0.0: Linear accel/decel ramp
• P106 > 0.0: Adjusts S-ramp curve for smoother ramp
(1)
Line Voltage Selection
1* 0 Low (120, 200, 400, 480VAC) * The default setting is 1 for all
drives except when using “reset 50” (Parameter P199, selection 4) with 480V models. In this case, the default setting is 0.
1 High (120, 240, 480, 600VAC)
Motor Overload 100 30 {%} 100
Motor Overload Type
0 0 Speed Compensation
Ir
100%
60%
30 f
1
0
V0108
1 No Speed Compensation
(1) Any changes to this parameter will not take effect until the drive is stopped
17
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Start Method 0 0 Normal
1 Start on Power-up Drive will automatically start when
power is applied.
2 Start with DC Brake When start command is applied, drive
will apply DC braking according to P1
74, P175 prior to starting the motor
3 Auto Restart Drive will automatically restart after
faults, or when power is applied.
4 Auto Restart with DC Brake
Combines settings 2 and 3
5 Flying Start/Restart #1 • Drive will automatically restart after
faults, or when power is applied.
• After
3 failed attempts, drive will
Auto Restart with DC brake.
• P110 = 5: Performs speed search, starting at Max Frequency (P103)
• P110 = 6: Performs speed search, starting at the last output frequency prior to faulting or power loss
• If P111 = 0, a flying START is performed when a start command is applied.
6 Flying Start/Restart #2
Note
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up;
fault will occur if start command is applied too soon.
• P110 = 1, 3…6: For automatic start/restart, the start source must be the terminal strip and the start command must be present.
• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays
(fault lockout) and requires manual reset.
• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into
. fault.
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/restarting should only be used on equipment that is inaccessible to personnel.
Stop Method 0 0 Coast Drive’s output will shut off immediately
upon a stop command, allowing the motor to coast to a stop
1 Coast with DC Brake The drive’s output will shut off and then
the DC Brake will activate (see P1
74,
P175)
2 Ramp The drive will ramp the motor to a stop
according to P1
05 or P126.
3 Ramp with DC Brake The drive will ramp the motor to 0 Hz
and then the DC Brake will activate (see P1
74, P175)
Rotation 0 0 Forward Only If PID mode is enabled, reverse
direction is disabled (except for Jog).
1 Forward and Reverse
18
Commissioning
4.5.2 I/O Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Assertion Level 2
1 Low
P120 and the Assertion Level switch must both match the desired assertion level unless P100, P121…P123 are all set to 0. Otherwise an F.AL fault will occur.
2 High
TB-13A Input Function
TB-13B Input Function
TB-13
C Input
Function
0 0
None Disables input
1 AUTO Reference: 0-1
0 VDC For frequency mode, see P160...P161,
For PID mode, see P204…P205, For vector torque mode, see P33
0
2 AUTO Reference: 4-20 mA
3 AUTO Reference: Preset For frequency mode see P131...P137,
For PID mode, see P231
…P233,
For torque mode see, P331…P333
4 AUTO Reference: MOP Up • Normally open: Close input to
increase or decrease speed, PID setpoint or torque setpoint.
• MOP Up is not active while in STOP
5
AUTO Reference: MOP Down
6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control Select Use when P100 = 4, 5 to switch
between terminal strip control and local or remote keypad control.
9 Network Enable Required to start the drive through the
network.
10
Reverse Rotation Open = Forward Closed = Reverse
11 Start Forward
See note for typical circuit
12
Start Reverse
13 Run Forward
See note for typical circuit
14
Run Reverse
15 Jog Forward Jog Forward speed = P134
16 Jog Reverse Jog Reverse speed = P135
Active even if P112 = 0
17 Accel/Decel #2 See P125, P126
18 DC Brake See P174; close input to override P175
19 Auxiliary Ramp to Stop
Normally closed: Opening input will ramp drive to STOP according to P1
27,
even if P111 is set to Coast (0 or 1).
20 Clear Fault Close to reset fault
21 External Fault
.
Normally closed circuit; open to trip
22 Inverse External Fault
.
Normally open circuit; close to trip
WARNING!
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a fault condition induced.
19
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Note
• When input is activated, settings 1...7 override P101
• When TB-13A...TB-13C are configured for Auto References other than MOP, TB-13C overrides TB-13B, and TB-13B overrides TB-13A. Any other Auto Reference will have priority over MOP.
• Settings 10...14 are only valid in Terminal Strip mode (P100 = 1, 4, 5)
• If Start/Run/Jog Forward and Start/Run/Jog Reverse are both activated, drive will STOP
• If Jog input is activated while the drive is running, the drive will enter Jog mode; when Jog input is deactivated, drive will STOP
An fault will occur if the Assertion Level switch (ALsw) position does not match the P120 setting and any of the digital inputs (P121...P123) are set to a value other than 0.
• An fault will occur under the following conditions:
- TB-13A...TB-13C settings are duplicated (each setting, except 0 and 3, can only be used once)
- One input is set to “MOP Up” and another is not set to “MOP Down”, or vice-versa.
- One input is set to 10 and another input is set to 11…14.
- One input is set to 11 or 12 and another input is set for 13 or 14.
• Typical control circuits are shown below:
- If any input is set to 10, 12 or 14, P112 must be set to 1 for Reverse action to function.
Run / Stop
with Direction
P1
21 = 10
Start Forward /
Start Reverse
P121 = 11, P122 = 12
Run Forward /
Run Reverse
P121 = 13, P122 = 14
1 4
13A
FWD
REV
STOP
RUN
1 4
13A 13B
RUN REV
RUN FWD
FWD
REVSTOP
1 4
13A 13B
Acceleration Time 2
20.0 0.0 {s} 3600 • Selected using TB-13A...TB-13C (P121...P123 = 17)
• For S-ramp accel/decel, adjust P106
Deceleration Time 2
20.0 0.0 {s} 3600
Deceleration Time for Auxiliary Ramp to Stop
20.0 0.0 {s} 3600 • Selected using TB-13A...TB-13C (P121...P123 = 19).
• For S-ramp accel/decel, adjust P106
• Once executed, this ramp time has priority over P105 and P126.
Preset Speed #1 0.0 0.0 {Hz} 500
PRESET
SPEED
13A 13B 13C
1 X -- -­2 -- X -­3 -- -- X 4 X X -­5 X -- X 6 -- X X 7 X X X
Preset Speed #2 0.0 0.0 {Hz} 500
Preset Speed #3 0.0 0.0 {Hz} 500
Preset Speed #4 0.0 0.0 {Hz} 500
Preset Speed #5 0.0 0.0 {Hz} 500
Preset Speed #6 0.0 0.0 {Hz} 500
Preset Speed #7 0.0 0.0 {Hz} 500
20
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Relay Output TB-16, 17
0 0 None Disables the output
1 Run Energizes when the drive is running
2 Reverse E
nergizes when reverse rotation is active
3 Fault De-energizes when the drive trips, or
power is removed
4 Inverse Fault Energizes when the drive trips
5 Fault Lockout P
110 = 3...6: De-energizes if all restart
attempts fail
6 At Speed Energizes when output frequency =
commanded frequency
7 Above Preset Speed #
6 Energizes when output freq. > P136
8 Current Limit Energizes when motor current = P171
9 Follower Loss (4-20 mA) Energizes when 4-20 mA signal falls
below 2 mA
10
Loss of Load Energizes when motor load drops
below P1
45; see also P146
11 Local Keypad Control Active
Energizes when the selected source is active for start control
12
Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference Active Energizes when P101 reference is active
16 Auto Reference Active
Energizes when Auto Reference is activated using TB-13
input; see
P121...P123
17 Sleep Mode Active See P240...P242
18
PID Feedback < Min. Alarm Energizes when PID feedback signal
< P21
4
19 Inverse PID Feedback < Min.
Alarm
De-energizes when PID feedback signal < P21
4
20 PID Feedback > Max Alarm Energizes when PID feedback
signal > P21
5
21 Inverse PID Feedback > Max
Alarm
De-energizes when PID feedback signal > P21
5
22 PID Feedback within
Min/Max Alarm range
Energizes when PID feedback signal is within the Min/Max Alarm range; see P21
4, P215
23 PID Feedback outside
Min/Max Alarm range
Energizes when PID feedback signal is outside the Min/Max Alarm range; see P21
4, P215
24 Reserved
25 Network Activated Requires optional communication
module (refer to the network module documentation).
21
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
TB-14 Output 0 0...23 (same as P140)
24 Dynamic Braking For use with Dynamic Braking option
25 Network Activated Requires optional communication
module (refer to the network module documentation).
Loss of Load Threshold
0 0 {%} 200 P140, P142 = 10: Output will energize
if motor load falls below P145 value longer than P146 time
Loss of Load Delay
0.0 0.0 {s} 240.0
TB-30 Output 0 0 None 2-10 VDC signal can be converted to
4-20 mA with a total circuit impedance of 500 W
1 0-10 VDC Output Frequency
2 2-10 VDC Output Frequency
3 0-10 VDC Load
4 2-10 VDC Load
5 0-10 VDC Torque
6 2-10 VDC Torque
7 0-10 VDC Power (kW)
8 2-10 VDC Power (kW)
9 Network Controlled
Requires optional communication module (refer to the network module documentation).
TB-30 Scaling: Frequency
60.0 3.0 {Hz} 2000 If P150 = 1 or 2, sets the frequency at which output equals 10 VDC
TB-30 Scaling: Load
200 10 {%} 500 If P150 = 3 or 4, sets the Load (as a
percent of drive current rating) at which output equals 1
0 VDC.
TB-30 Scaling: Torque
100 10 {%} 1000 If P150 = 5 or 6, sets the Torque (as a
percent of motor rated torque) at which output equals 10 VDC
TB-30 Scaling: Power (kW)
1.0 0.1 {kW} 200.0 If P150 = 7 or 8, sets the power at which output equals 10 VDC
22
Commissioning
4.5.3 Advanced Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Speed at Minimum Signal
0.0 -999.0 {Hz} 1000
f
P161
P160
ref
10V
(20mA)
0V
(4mA)
V0111
Speed at Maximum Signal
60.0
-999.0 {Hz} 1000
Note
• P160 sets the output frequency at 0% analog input
• P161 sets the output frequency at 100% analog input
• P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate opposite direction!
• P
160 > P161: Drive will react inversely to analog input signal
Analog Input Filter
0.01 0.00 {s} 10.00 Adjusts the filter on the analog inputs (TB-5 and TB-25) to reduce the effect of signal noise
TB-25 Loss Action
0 0 No Action • Selects the reaction to a loss of the
4-20 mA signal at TB-25.
• Signal is considered lost if it falls
below 2 mA
• Digital outputs can also indicate a
loss of 4-20 mA signal; see P140, P142
1 Fault
2 Go to Preset when TB-25 is: Speed reference: P137 PID feedback source: P137 PID setpoint reference: P233 Torque reference: P333
Carrier Frequency
1 0 4 kHz • As carrier frequency is increased,
motor noise is decreased
• Observe derating in Section 2.2
• Automatic shift to 4 kHz at 120%
load
1 6
kHz
2 8 kHz
3 10 kHz
(1)
Base Frequency 60.0 10.0 {Hz} 1500
V0112
Fixed Boost 0.0 {%} 30.0
Note
• P167 = rated motor frequency for standard applications
• P168 default setting depends on drive rating
Accel Boost 0.0 0.0 {%} 20.0 Accel Boost is only active during
acceleration
(1) Any changes to this parameter will not take effect until the drive is stopped
23
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Slip Compensation
0.0 0.0 {%} 10.0 Increase P170 until the motor speed no longer changes between no load and full load conditions.
(1)
Current Limit 200 30 {%} CLim
max
• When the limit is reached, the
drive displays
, and either the acceleration time increases or the output frequency decreases.
• Digital outputs can also indicate when the limit is reached; see P140, P142.
• Refer to section 2.2 for CLim
max
DC Brake Voltage
0.0 0.0 {%} 30.0 Setting is a percent of the nominal DC bus voltage.
DC Brake Time 0.0 0.0 {s} 999.9
Note
CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P1
74) is applied for the time specified by P175 with the
following exceptions:
• If P
111=1, 3 and P175=999.9 the brake voltage will be applied
continuously until a run or fault condition occurs.
• If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s
• If P121…P123=18 and the corresponding TB-13 input is CLOSED, brake voltage will be applied until the TB-13 input is OPENED or a fault condition occurs.
Display Frequency Multiplier
0.00 0.00 650.00 • Allows frequency display to be scaled
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual Frequency X P178
Example: If P178 = 29.17 and actual frequency = 60 Hz,
Drive displays 1750 (rpm)
Run Screen Display
0 0 {Parameter Number} 599 • 0 = Normal Run Screen, this display
depends on mode of operation. See Section 4.2.
• Other selections choose a diagnostic parameter to display (P501…P599).
Skip frequency 1 0.0 0.0 {Hz} 500 • Drive will not run in the defined skip
range; used to skip over frequencies that cause mechanical vibration
• P181 and P182 define the start of the skip ranges
• P
184 > 0 defines the bandwidth of
both ranges.
Skip frequency 2 0.0 0.0 {Hz} 500
Skip frequency bandwidth
0.0 0.0 {Hz} 10.0
Note
Bandwidth (Hz) = fs (Hz) + P184 (Hz) fs = P181 or P182 Example: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz
(1) Any changes to this parameter will not take effect until the drive is stopped
24
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Password 225 0000 9999 • Must enter password to access
parameters
• P194 = 0000: Disables password
Clear Fault History
0 0 No Action
1 Clear Fault History
Program Selection
0 Operate from User settings
1 Operate from OEM settings See Notes 1, 2 and 3
2 Reset to OEM default settings See Note 1
3 Reset to 60 Hz default settings • See Note 4
• Parameters are reset to the defaults listed in this manual.
• For
P199=4, the following exceptions
apply:
- P103, P152, P161, P167 = 50.0 Hz
- P304 = 50 Hz;
- P305 = 1450 RPM
- P107 = 0 (480 V drives only)
4 Reset to 50 Hz default settings
5 Translate See Note 5
WARNING!
Modification of P199 can affect drive functionality! STOP and EXTERNAL FAULT circuitry may be disabled! Check P100 and P121...P123
Note 1
If the EPM does not contain valid OEM settings, a flashing GF will be displayed when P199 is set to 1 or 2.
Note 2
When P199 is set to 1, the drive operates from the OEM settings stored in the EPM Module and no other parameters can be changed (
will be
displayed if attempted).
Note 3
Auto Calibration is not possible when operating from OEM Settings.
Note 4
Reset 60 and Reset 50 will set the Assertion Level (P120) to “2” (High). P120 may need to be reset for the digital input devices being used. An fault may occur if P120 and the Assertion switch are not set identically.
Note 5
If an EPM that contains data from a previous compatible software version is installed:
• The drive will operate according to the previous data, but parameters cannot be changed (
will be displayed if attempted)
• To update the EPM to the current software version, set P199 = 5. The parameters can now be changed but the EPM is incompatible with previous software revisions.
25
Commissioning
4.5.4 PID Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
PID Mode 0 0 Disabled • Normal-acting: As feedback
increases, motor speed decreases
• Reverse-acting: As feedback increases, motor speed increases
• PID mode is disabled in Vector Torque mode (P300 = 5)
1 Normal-acting
2 Reverse-acting
Note
To activate PID mode, one of the TB-13 inputs (P121...P123) must be used to select the Auto Reference that matches the desired PID setpoint reference. If the selected PID setpoint reference uses the same analog signal as the PID feedback (P201), an
fault will occur. Example: The desired PID setpoint reference is the keypad (s and t). Set TB-13x = 6 (Auto Reference: Keypad):
• TB-13x = closed: PID mode is active
• TB-13x = open: PID mode is disabled and the drive speed will be
controlled by the reference selected in P101.
PID Feedback Source
0 0 4-20 mA (TB-25) Must be set to match the PID feedback
signal
1 0-10 VDC (TB-5)
PID Decimal Point
1 0 PID Display = XXXX Applies to P204, P205, P214, P215,
P231...P233, P242, P522, P523
1 PID Display = XXX.X
2 PID Display = XX.XX
3 PID Display = X.XXX
4 PID Display = .XXXX
Feedback at Minimum Signal
0.0 -99.9 3100.0 Set to match the range of the feedback signal being used Example: Feedback signal is 0 - 300 PSI; P204 = 0.0, P205 = 300.0
Feedback at Maximum Signal
100.0 -99.9 3100.0
Proportional Gain 5.0 0.0 {%} 100.0 Used to tune the PID loop:
• Increase P207 until system becomes
unstable, then decrease P207 by 10-15%
• Next, increase P208 until feedback
matches setpoint
• If required, increase P209 to
compensate for sudden changes in feedback
Integral Gain 0.0 0.0 {s} 20.0
Derivative Gain 0.0 0.0 {s} 20.0
Note
• Derivative Gain is very sensitive to noise on the feedback signal and must be used with care
• Derivative Gain is not normally required in pump and fan applications
PID Setpoint Ramp
20.0 0.0 {s} 100.0 • time of setpoint change from P204 to P205 or vice versa.
• Used to smooth the transition from one PID setpoint to another, such as when using the Preset PID Setpoints (P231...P233)
26
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Minimum Alarm 0.0 P204 P205 Use with P140, P142 = 18...23
Maximum Alarm 0.0 P204 P205
Preset PID Setpoint #1
0.0 P204 P205 TB-13A activated; P121 = 3 and P200 = 1 or 2
Preset PID Setpoint #2
0.0 P204 P205 TB-13B activated; P122 = 3 and P200 = 1 or 2
Preset PID Setpoint #3
0.0 P204 P205 TB-13C activated; P123 = 3 and P200 = 1 or 2
Sleep Threshold 0.0 0.0 {Hz} 500.0 • If drive speed < P240 for longer than
P241, output frequency = 0.0 Hz; drive display =
• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again
when speed command is above P240
• P242 > 0.0: Drive will restart when
the PID feedback differs from the setpoint by more than the value of P242
or when the PID loop
requires a speed above P240.
Sleep Delay 30.0 0.0 {s} 300.0
Sleep Bandwidth 0.0 0.0 B
max
Where: B
max
= |(P205 - P204)|
27
Commissioning
4.5.5 Vector Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
(1)
Drive Mode 0 0 Constant V/Hz Constant torque V/Hz control for
general applications
1 Variable V/Hz Variable torque V/Hz control for
centrifugal pump and fan applications
2 Enhanced Constant V/Hz For single or multiple motor
applications that require better performance than settings 0 or 1
, but
cannot use Vector mode, due to:
• Missing required motor data
• Vector mode causing unstable motor operation
3 Enhanced Variable V/Hz
4 Vector Speed For single-motor applications requiring
higher starting torque and speed regulation
5 Vector Torque For single-motor applications requiring
torque control independent of speed
Note
To configure the drive for either Vector mode or Enhanced V/Hz mode:
• P300 = 4, 5:
- Set P302...P306 according to motor nameplate
- Set P399 = 1
- Make sure motor is cold (20° - 25° C) and apply a Start command
- Display will indicate
for about 40 seconds
- Once the calibration is complete, the display will indicate
; apply
another Start command to actually start the motor
- If an attempt is made to start the drive in Vector or Enhanced V/Hz mode before performing the Motor Calibration, the drive will display
and will not operate
• P300 = 2, 3: Same as above but only need to set P302…P304
(1)
Motor Rated Voltage
0 {V} 600
• Default setting = drive rating
• Set to motor nameplate data
(1)
Motor Rated Current
0.0 {A} 500.0
(1)
Motor Rated Frequency
60 0 {Hz} 1000
Set to motor nameplate data
(1)
Motor Rated Speed
1750 300 {RPM} 65000
(1)
Motor Cosine Phi 0.80 0.40 0.99
Note
If motor cosine phi is not known, use one of the following formulas: cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732) cos phi = cos [ sin1 (magnetizing current / motor current) ]
(1) Any changes to this parameter will not take effect until the drive is stopped
28
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
(1)
Motor Stator Resistance
0.00 0.00 {W}
64.00 • Will be automatically programmed by P399
• Changing these settings can adversely affect performance. Contact factory technical support prior to changing
(1)
Motor Stator Inductance
0.0 0.0 {mH} 2000
Torque Limit 100 0 {%} 400 When P300 = 5, sets the maximum
output torque.
Preset Torque Setpoint #1
100 0 {%} 400 TB-13A activated; P121 = 3 and
P300 = 5
Preset Torque Setpoint #2
100 0 {%} 400 TB-13B activated; P122 = 3 and
P300 = 5
Preset Torque Setpoint #3
100 0 {%} 400 TB-13C activated; P123 = 3 and
P300 = 5
(1)
Current Loop P Gain
0.25 0.00 16.0
Changing these settings can adversely affect performance. Contact factory technical support prior to changing.
(1)
Current Loop I Gain
65 12 {ms} 9990
(1)
Speed Loop Adjustment
0.0 0.0 {%} 20.0
Motor Auto­calibration
0 0 Calibration Not Done • If P300 = 2...5, motor calibration
must be performed, but motor data must be programmed first
• An alternating
/ will occur if:
- motor calibration is attempted with
P300 = 0 or 1
- motor calibration is attempted
before programming motor data
1 Calibration Enabled
2 Calibration Complete
Note
To run the Auto Calibration:
- Set P302...P306 according to motor nameplate
- Set P399 = 1
- Make sure motor is cold (20° - 25° C)
- Apply a Start command
- Display will indicate
for about 40 seconds
- Once the calibration is complete, the display will indicate
; apply
another Start command to actually start the motor
- Parameter P399 will now be set to 2.
(1) Any changes to this parameter will not take effect until the drive is stopped
29
Commissioning
4.5.6 Network Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Network Protocol 0 Not Active
This parameter will only display the selection for the module that is installed.
1 Remote Keypad
2 Modbus RTU
3 CANopen
4
DeviceNet
5 Ethernet
6 Profibus
Module Specific Parameters
Refer to the Reference Guide specific to the module installed.
4.5.7 Diagnostic Parameters
Code
Display Range
(READ ONLY)
IMPORTANT
No. Name
Fault History • Displays the last 8 faults
• Format: n.xxx where: n = 1
..8; 1 is the newest fault xxx = fault message (without the
.)
• see Section 5.3
Software version Format: x.yz
Drive ID A flashing display indicates that the Drive ID
stored in the EPM does not match the drive model it is plugged into.
Internal Code Alternating Display: xxx-; -yy
DC Bus Voltage 0 {VDC} 1500
Motor Voltage 0 {VAC} 1000
Load 0 {%} 255 Motor load as % of drive’s output current rating.
See section 2.2.
Motor Current 0.0 {A} 1000 Actual motor current
Torque 0 {%} 500 Torque as % of motor rated torque
(vector mode only)
kW 0.00 {kW} 650.0
kWh 0.0 {kWh} 9999999 Alternating display: xxx-; yyyy when value
exceeds 9999
Heatsink Temp 0 {°C} 150 Heatsink temperature
0-10 VDC Input 0.0 {VDC} 10.0 Actual value of signal at TB-5
4-20 mA Input 0.0 {mA} 20.0 Actual value of signal at TB-25
TB-5 Feedback P204 P205 TB-5 signal value scaled to PID feedback units
TB-25 Feedback P204 P205 TB-25 signal value scaled to PID feedback units
30
Commissioning
Code
Display Range
(READ ONLY)
IMPORTANT
No. Name
Analog Output 0 {VDC} 10.0 See P150…P155
Actual Output Frequency
0 {Hz} 500.0
Network Speed Command
0 {Hz} 500.0 Command speed if (Auto: Network) is selected
as the speed source
Terminal and Protection Status
Indicates terminal status using segments of the LED display. (See section 4.5.7.1)
Keypad Status Indicates keypad button status using segments
of the LED display. (See section 4.5.7.2)
Total Run Time 0 {h} 9999999 Alternating display: xxx-; yyyy when value
exceeds 9999
Total Power On Time
0 {h} 9999999
4.5.7.1 Terminal and Protection Status Display
Parameter P530 allows monitoring of the control terminal points and common drive conditions: An illuminated LED segment indicates:
• the protective circuit is active (LED 1)
• the Logic Assertion Switch is set to High (+)
• input terminal is asserted (LED 2)
• output terminal is energized (LED 4)
• the Charge Relay is not a terminal, this segment will be illuminated when the Charge Relay is energized (LED 4).
Charge Relay Input (13C) Input (13A) Protection Diagnostic
Current Limit Diagnostic Logic Assertion Switch Input (1) Input (13B) Relay Output (14)
4.5.7.2 Keypad Status Display
Parameter P531 allows monitoring of the keypad pushbuttons: An illuminated LED segment indicates when the button is depressed.
31
Troubleshooting and Diagnostics
5 Troubleshooting and Diagnostics
5.1 Status/Warning Messages
Status / Warning Cause Remedy
DC-injection brake active DC-injection brake activated
• activation of digital input (P121...P123 = 18)
• automatically (P110 = 2, 4...6)
• automatically (P111 = 1, 3)
Deactivate DC-injection brake
• deactivate digital input
• automatically after P175 time has expired
Drive ID warning The Drive ID (P502) stored on
the EPM does not match the drive model.
• Verify motor data (P302…P306) and perform Auto Calibration.
• Set drive mode (P300) to 0 or 1
• Reset the drive (P199 to 3 or 4) and reprogram.
Motor Auto-calibration is being performed
See P300, P399
An EPM that contains valid data from a previous software version has been installed
An attempt was made to change parameter settings
Parameter settings can only be changed after the EPM data is converted to the current version (P199 = 5)
Current Limit (P171) reached Motor overload • Increase P171
• Verify drive/motor are proper size for application
Decel Override The drive has stopped
decelerating to avoid tripping into
fault, due to excessive motor
regen (2 sec max).
If drive trips into
fault:
• Increase P105, P126
• Install Dynamic Braking option
Error Invalid data was entered, or an
invalid command was attempted
Fast Current Limit Overload Verify drive/motor are proper size
for application
Flying Restart Attempt after Fault P110 = 5,6
OEM Settings Operation warning An attempt was made to change
parameter settings while the drive is operating in OEM Settings mode (P199 = 1)
In OEM Settings mode, making changes to parameters is not permitted
OEM Defaults data warning An attempt was made to use
(or reset to) the OEM default settings (P199 = 1 or 2) using an EPM without valid OEM data.
Install an EPM containing valid OEM Defaults data
Fault Lockout The drive attempted 5 restarts
after a fault but all attempts were unsuccessful (P110 = 3...6)
• Drive requires manual reset
• Check Fault History (P500) and correct fault condition
PID Deceleration Status PID setpoint has finished
its ramp but the drive is still decelerating to a stop.
32
Troubleshooting and Diagnostics
Status / Warning Cause Remedy
PID Mode Active Drive has been put into PID
Mode. See P200.
Sleep Mode is active See P240...P242
Start Pending The drive has tripped into a fault
and will automatically restart (P110 = 3...6)
To disable Auto-Restart, set P110 = 0...2
PID Mode disabled. Drive has been taken out of PID
Mode. See P200.
Output frequency = 0 Hz (outputs U, V, W inhibited)
Stop has been commanded from the keypad, terminal strip, or network
Apply Start command (Start Control source depends on P100)
5.2 Drive Conguration Messages
When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that indicates how the drive is configured. If the drive is in a Stop state when this is done, the display will also indicate which control source commanded the drive to Stop (the two displays will alternate every second).
Conguration Display
Format = x.y.zz x = Control Source:
= Local Keypad = Terminal Strip = Remote Keypad = Network
y = Mode:
= Speed mode = PID mode = Vector Torque mode
zz = Reference:
= Keypad s t = 0-10 VDC (TB-5) = 4-20 mA (TB-25) = Jog = Network = MOP
= Preset 1...7
Example:
= Local Keypad Start control, Speed mode, Keypad speed reference
= Terminal Strip Start control, PID mode, 0-10 VDC setpoint reference
= Network Start control, Vector Torque mode, Preset Torque #2 reference
Stop Source Display
Format = x
= Stop command came from Local Keypad = Stop command came from Terminal Strip = Stop command came from Remote Keypad = Stop command came from Network
33
Troubleshooting and Diagnostics
5.3 Fault Messages
The messages below show how they will appear on the display when the drive trips. When looking at the Fault History (P500), the . will not appear in the fault message.
Fault Cause Remedy
(1)
High Temperature fault Drive is too hot inside • Reduce drive load
• Improve cooling
Assertion Level fault • Assertion Level switch is
changed during operation
• P120 is changed during operation
P100 or P121...P123 are set to a value other than 0 and P120 does not match the Assertion Level Switch.
• Make sure the Assertion Level switch and P120 are both set for the type of input devices being used, prior to setting P100 or P121...P123. See 3.2.3 and P120.
Personality fault Drive Hardware • Cycle Power
• Power down and install EPM with valid data
• Reset the drive back to defaults (P
199 = 3, 4) and then re-
program
• If problem persists, contact factory technical support
Control fault An EPM has been installed that is
either blank or corrupted
Incompatible EPM fault An EPM has been installed that
contains data from an incompatible parameter version
Dynamic Braking fault Dynamic braking resistors are
overheating
• Increase active decel time (P105, P126, P127).
• Check mains voltage and P107
External fault • P121…P123 = 21 and that digital
input has been opened.
• P121…P123 = 22 and that digital input has been closed.
• Correct the external fault condition
• Make sure digital input is set properly for NC or NO circuit
EPM fault EPM missing or defective Power down and replace EPM
Internal faults Contact factory technical support
Invalid message received • A network message was
received while in Remote Keypad mode
• A remote keypad message was received while in Network mode
Only the remote keypad or the network can be connected at one time; see P100
Loss of 4-20 mA signal fault
4-20 mA signal (at TB-25) is below 2 mA (P163 = 1)
Check signal/signal wire
OEM Defaults data fault Drive is powered up with
P199 =1 and OEM settings in the EPM are not valid.
Install an EPM containing valid OEM Defaults data or change P199 to 0.
High DC Bus Voltage fault
Mains voltage is too high Check mains voltage and P107
Decel time is too short, or too much regen from motor
Increase active decel time (P1
05, P126, P127) or install
Dynamic Braking option
(1) The drive can only be restarted if the error message has been reset
34
Troubleshooting and Diagnostics
Fault Cause Remedy
(1)
Digital Input Configuration fault (P121...P123)
More than one digital input set for the same function
Each setting can only be used once (except settings 0 and 3)
Only one digital input configured for MOP function (Up, Down)
One input must be set to MOP Up, another must be set to MOP Down
PID mode is entered with setpoint reference and feedback source set to the same analog signal
Change PID setpoint reference (P1
21…P123) or feedback source
(P201).
One of the digital inputs (P121… P123) is set to 10 and another is set to 11…14.
Reconfigure digital inputs
One of the digital inputs (P1
21… P123) is set to 11 or 12 and another is set to 13 or 14.
PID enabled in Vector Torque mode (P200 = 1
or 2 and P300 = 5)
PID cannot be used in Vector Torque mode
Remote keypad fault Remote keypad disconnected Check remote keypad connections
Low DC Bus Voltage fault Mains voltage too low Check mains voltage
No Motor ID fault An attempt was made to start the
drive in Vector or Enhanced V/Hz mode prior to performing the Motor Auto-calibration
See P300…P399 for Drive Mode setup and calibration.
Module communication fault
Communication failure between drive and Network Module.
Check module connections
Network Faults Refer to the module documentation.
for Causes and Remedies.
Output fault: Transistor fault
Output short circuit Check motor/motor cable
Acceleration time too short Increase P1
04, P125
Severe motor overload, due to:
• Mechanical problem
Drive/motor too small for
application
• Check machine / system
• Verify drive/motor are proper size for application
Boost values too high Decrease P16
8, P169
Excessive capacitive charging current of the motor cable
• Use shorter motor cables with lower charging current
• Use low capacitance motor cables
• Install reactor between motor and drive.
Failed output transistor Contact factory technical support
Output fault: Ground fault Grounded motor phase Check motor and motor cable
Excessive capacitive charging current of the motor cable
Use shorter motor cables with lower charging current
(1) The drive can only be restarted if the error message has been reset
35
Troubleshooting and Diagnostics
Fault Cause Remedy
(1)
Motor Overload fault Excessive motor load for too long • Verify proper setting of P108
• Verify drive and motor are proper size for application
Flying Restart fault Controller was unable to
synchronize with the motor during restart attempt; (P110 = 5 or 6)
Check motor / load
Single-Phase fault A mains phase has been lost Check mains voltage
Start fault Start command was present when
power was applied (P110 = 0 or 2).
• Must wait at least 2 seconds after power-up to apply Start command
• Consider alternate starting method (see P110).
(1) The drive can only be restarted if the error message has been reset
Notes
AC Technology Corporation • 630 Douglas Street • Uxbridge, MA 01569 • USA
+1 (508) 278-9100
(SV01B)
Loading...