Important !
Always Place Varistor
Across Lock Terminals
DS100e Door Station Installation
OP2 = Aux Relay
OP3 = OP3
OP4 = OP2
IP1 = Aux Input
IP2 = Door Contact
IP3 = Push Button
Door
Contact
Door
Release
Button
Network cable is single
shielded twisted pair,
Belden 9501 or similar
To next door
NETWORK
A
B
0V
0V
ACT 2000
A
B
Shield
A
B
DTR
DOORS
Power
Supply Unit
+12V
0V
Note:
If the Mains Present or Door
Contact inputs are not used,
they should be linked to 0V
This illustration shows wiring
for a normally energised
lock. If a normally de-energised
lock is required, use the
N/O relay contacts.
OP3 OP4 0V IP1 IP2 IP3
NC
C
OP2
NO
NC
C
OP1
NO
TAMPER
MAINS
PRESENT
+
12V DC
-
4 5 6 7 8
On
To set the door number,
set address switches
4-8 as shown
LED Functionality:
Red LED indicates the status of communications with the Controller.
While online to the controller the Red LED will flash rapidly.
If there is a problem it will flash slowly (about once a second).
Green LED will flash if an event occurs on the DS100e.
5A 250VAC
5A 30VDC
5A 250VAC
5A 30VDC
Required
Address
5
4
03 OFF OFF OFF ON ON
04 OFF OFF ON OFF OFF
05 OFF OFF ON OFF ON
06 OFF OFF ON ON OFF
07 OFF OFF ON ON ON
08 OFF ON OFF OFF OFF
09 OFF ON OFF OFF ON
1 2 3 4 5 6 7 8
On
N ADDRESS
6
7
8
Downloaded from: http://www.guardianalarms.net
SERIAL NETWORK
DTR RX TX 0V B A
SENSE
CLOCK
DATA
+5V0VRED
Entry/Exit Reader
Required
Address
5
4
10 OFF ON OFF ON OFF
11 OFF ON OFF ON ON
12 OFF ON ON OFF OFF
13 OFF ON ON OFF ON
14 OFF ON ON ON OFF
15 OFF ON ON ON ON
16 ON OFF OFF OFF OFF
6
8
7
www.accesscontrol.ie
Total Length max 1.4km
Wiring for Clock and Data / Wiegand Reader
Entry Reader
GREEN
Max len 30M
Cable: 8 Core Screened
Belden 9504 or equiv
FACTORY DEFAULT
This unit should be reset to its
factory default condition before
installation. To do this, power
the unit up with ALL switches in
the OFF position. The two LED's
will illuminate for about 2 sec.
The correct switch settings may
then be set.
White
Green
Blue
Red
Black
Brown
Yellow
Orange
SENSE
CLOCK / DATA 1
DATA / DATA 0
+5v
0v
RED
GREEN
(Buzzer Ctrl)
For Clock & Data
Readers, wire exit
reader in parallel
but leave it's
sense line
unconnected.
For Wiegand
Readers, wire the
DATA 0 of the exit
reader to SENSE
on the DS100e
18-00037