ACT ACTPRO200 Installation

ACTpro200 Installation
2 Door Controller and Monitored Power Supply
Mains Present
Fuse OP2 Blown
Fuse OP1 Blown
Fuse OP1
Fuse OP2
Press to connect batteries
MAINS VOLTAGE
DISCONNECT BEFORE MAINTENANCE
LED Functionality: Red LED indicates the status of communications with the controller. While online to the controller the Red LED will flash rapidly. If there is a problem it will flash slowly (about once a second). Green LED will flash if an event occurs on the ACTpro200.
Secondary AC Fuse
12V 0V
OUTPUT 1
AC AC
12V 0V
OUTPUT 2
5A 250VAC
5A 30VDC
BATTERY 1
Battery OK LEDs
5A 250VAC 5A 30VDC
BATTERY 2
TAMPER
1 2 3 4 5 6 7 8
On
WARNING:
NO C NC NO C NC
5A 250VAC 5A 30VDC
5A 250VAC
5A 30VDC
NC C NO NC C NO
5A 250VAC
5A 30VDC
5A 250VAC 5A 30VDC
Entry/Exit Reader
DOOR 1 Connections
+12V
GREEN
RED0V+5V
SENSE
CLOCK
DATA
+5V0VRED
NETWORK
A
B
0V
0V
Total Length max 1.4km Belden 9502 or equiv.
DATA
CLOCK
SENSE
OP3
OP2
0V
AUX INPUT
DC2
PB2
A
B
0V
OP3
OP2
0V
AUX INPUT
DC2
PB2
GREEN
+12V
Cable: 8 Core Screened Belden 9504 or equiv
ACT 2000
A B
Shield
DOORS
A B
DOORS NETWORK
DOOR 2 Connections
Entry Reader
Battery 1 - Backup for Output 1 and PCB
*Always connect Battery 1.
Important! Do not reverse battery leads.
red lead connects to + terminal of battery black lead connects to - terminal of battery.
5
Door Address
Example: When the dipswitch is set to 3, Door 1 is set to Address 3 and Door 2 is set to Address 4. When the dipswitch is set to 4, Door 1 is set to Address 4 and Door 2 is set to Address 5.
4
03 OFF OFF OFF ON ON
04 OFF OFF ON OFF OFF
05 OFF OFF ON OFF ON
06 OFF OFF ON ON OFF
07 OFF OFF ON ON ON
08 OFF ON OFF OFF OFF
09 OFF ON OFF OFF ON
10 OFF ON OFF ON OFF
11 OFF ON OFF ON ON
12 OFF ON ON OFF OFF
13 OFF ON ON OFF ON
14 OFF ON ON ON OFF
15 OFF ON ON ON ON
16 ON OFF OFF OFF OFF
6
8
7
FACTORY DEFAULT This unit should be reset to its factory default condition before installation. To do this, power the unit up with ALL switches in the OFF position. The two LED's will illuminate for about 2 sec. The correct switch settings may then be set.
Battery 2 - Backup for Output 2 Monitoring for battery 2 can be disabled by setting dipswitch 3 to ON
www.accesscontrol.ie
Important ! Always Place Varistor Across Lock Terminals
This illustration shows wiring for a normally energised lock. If a normally de-energised lock is required, use the N/O relay contacts.
Technical Specifications
Mains Voltage 230Vac +10% -15%
Frequency  47-63 Hz
Mains Fuse 630mAmp
Secondary AC Fuse 3.15Amps
Fuse OP1  1.25 Amps Quick
Fuse OP2  1.25 Amps Quick
Ripple Voltage <200mV
ACTWinPro users must tick Mains
Fault Reporting in the door view
Access Control Technology, Ireland. Tel: + 353 466 2570
Max length: 30m from +5V 100m from +12V
White Green Blue Red Black Brown Yellow Orange
For Clock and Data Readers, wire exit reader in parallel but do not connect to SENSE.
For Wiegand Readers, wire DATA0 of the exit reader to SENSE.
SENSE CLOCK / DATA 1 DATA / DATA 0 +5V or +12V 0V RED GREEN (Buzzer Control)