Acme PP-32 User Manual

KOOLMASTER
PP-32
CONTROLLER
ENVIRONMENTAL
MANAGEMENT
SYSTEM
SERIAL NUMBER: DATE:
Read this guide carefully before using the controller.
NOTICE
Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice due to further developments.

T ABLE OF CONTENTS

Page
1. PRECAUTIONS............................................................ 6
2. FEATURES ................................................................. 7
3. LOCATION OF THE CONTROLS .................................... 9
4. MOUNTING INSTRUCTIONS ....................................... 11
4.1 CONNECTION ..................................................................11
4.2 SETTING THE DIP SWITCHES ............................................. 14
5. CONTROLLER SETUP ................................................ 15
5.1 CURRENT CONDITIONS ..................................................... 15
5.2 CONTROLLER PROGRAMS ................................................16
5.2.1 Selecting a Program ........................................................ 16
5.2.2 Selecting a Season.......................................................... 16
5.3 ADJUSTING THE ROOM SET POINT ....................................18
5.4 MINIMUM VENTILATION................................................... 19
5.4.1 Adjusting Minimum Ventilation's On-Time.......................... 19
5.4.2 Adjusting Minimum Ventilation's Cycle Time ...................... 20
5.5 INLET / VENT DOOR SETTINGS...........................................21
5.5.1 Inlet Settings (Potentiometer Feedback from Inlets)............... 21
5.5.1.1 Setting DWR-F-1A's ID numbers ......................................... 21
5.5.1.2 Adjusting the Air Inlet Compensation .................................. 22
5.5.2 Vent Door Settings ......................................................... 23
5.5.2.1 Adjusting Static Pressure Set Points ................................... 2 6
5.5.2.2 Adjusting Vent Doors Open / Close / Off Times ................... 26
5.5.2.3 Adjusting Stage Level for the Closing of Vent Doors ............. 2 8
5.5.2.4 2nd Group of Pressure Set Points: at Stage X ...................... 2 8
5.5.2.5 2nd Group of Pressure Set Points: at Outside T° X ............... 29
5.6 TUNNEL CURTAIN ............................................................ 31
5.6.1 Adjusting Minimum Age for Tunnel Ventilation .................. 34
5.6.2 Selecting the First Tunnel Stage........................................ 34
5.6.3 Adjusting Curtain's Operating Times.................................. 35
5.6.4 Adjusting Static Pressure Hi and Lo Set Points .................... 36
5.6.5 Adjusting Curtain's Timer Cycle ....................................... 36
5.7 FAN STAGES SETTINGS.................................................... 38
5.7.1 Adjusting Fan Stages' Start/Stop Temperatures................... 39
5.7.2 Adjusting Fans Stages' Timer ........................................... 39
5.8 HEATER SETTINGS ........................................................... 41
KOOLMASTER PP-32 REV.01
3
PP-32
5.9 AUXILIARY OUTPUTS....................................................... 42
5.10 ANIMAL AGE ................................................................ 44
5.11 CLOCK OUTPUTS........................................................... 45
5.11.1 Adjusting Clock Output Start and Stop Times ................... 46
5.11.2 Adjusting Starting Day of Clock Programs ........................ 47
5.12 HISTORY ......................................................................48
5.12.1 Resetting Histories........................................................ 48
5.12.2 Average Temperature History ......................................... 48
5.12.3 Individual Temperature Sensors History ........................... 49
5.12.4 Outside Temperature Sensor History................................ 49
5.12.5 Relative Humidity History .............................................. 49
5.12.6 Water Consumption History ........................................... 50
5.12.7 Heater Run Time History................................................ 50
5.13 ALARM SETTINGS..........................................................52
5.13.1 Alarm Log.................................................................... 52
5.13.2 Setting Alarm Limits...................................................... 53
5.13.2.1 Adjusting Hi/ Lo Temperature Alarms ................................. 54
5.13.2.2 Adjusting Critical Temperature ......................................... 55
5.13.2.3 Adjusting the Outside Temperature Influence ..................... 55
5.13.2.4 Adjusting Static Pressure Alarms ...................................... 5 6
5.13.3 Resetting the Alam Log.................................................. 58
5.14 INSTALLATION .............................................................. 59
5.14.1 Step-by-Step Installation Guide ...................................... 59
5.14.2 Password Settings ........................................................ 61
5.14.3 Installation Setup .......................................................... 63
5.14.4 Sensor Assignment ....................................................... 66
5.14.4.1 Assigning Sensors to the Room T° and Fan Stages.............. 66
5.14.4.2 Assigning Sensors to Heater Stages .................................. 6 7
5.14.4.3 Assigning Sensors to Air Inlets.......................................... 67
5.14.4.4 Assigning Sensors to Auxiliary Outputs ............................... 68
5.14.5 Setting Time and Date................................................... 70
5.14.6 Relay Assignment ......................................................... 70
5.14.6.1 Assigning Fan Stages' Relays ............................................. 72
5.14.6.2 Assigning Heater Stages' Relays ........................................ 73
5.14.6.3 Assigning Relays to Vent Doors ......................................... 7 3
5.14.6.4 Assigning Relays to the Tunnel Curtain ............................... 7 4
5.14.6.5 Assigning Relays to Clock Outputs ..................................... 7 5
5.14.6.6 Assigning Relays to Auxiliary Outputs ................................. 7 5
5.14.6.7 Assigning Relays for the Lo Static Pressure Alarm ............... 7 6
5.14.7 Calibrating the Water Counter ......................................... 77
4
KOOLMASTER PP-32 REV.01
PP-32
5.15 ADVANCED SETTINGS .................................................... 78
5.15.1 Setting the Temperature Curve........................................ 78
5.15.2 Setting the Minimum Ventilation Curve ............................ 80
5.15.3 Humidity Control ......................................................... 82
5.15.3.1 Adjusting Relative Humidity Set Point ................................ 82
5.15.3.2 RH Compensation on Minimum Ventilation ......................... 83
5.15.3.3 Adjusting Mist or Kool-Cel Shutoff ..................................... 8 4
5.15.3.4 Adjusting Heater Timer Cycle ............................................ 84
5.15.4 Calibrating Sensors ....................................................... 86
5.15.4.1 Calibrating Room and Outside T° Sensors ......................... 86
5.15.4.2 Calibrating the Relative Humidity Sensor ........................... 86
5.15.4.3 Calibrating the Static Pressure Level ................................. 8 7
6. TECHNICAL SPECIFICATIONS .................................... 89
7. FACTORY SETTINGS ................................................. 90
8. USING THE CONFIGURATION MODULE ...................... 91
8.1 LOADING A CONFIGURATION ...........................................91
8.2 SAVING A CONFIGURATION ............................................. 92
9. INSTALLATION REPORT ............................................ 93
10. INDEX .................................................................... 98
KOOLMASTER PP-32 REV.01
5

1. PRECAUTIONS

We strongly recommend installing supplementary natural ventila­tion as well as a backup thermostat on at least one cooling stage
(refer to the wiring diagram enclosed with this user's manual to
connect the thermostat).
Although fuses at the input and outputs of the controller protect
its circuits in case of an overload or overvoltage, we recommend
installing an additional protection device on the controller's
supply circuit.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO 40°C).
To avoid exposing the controller to harmful gases or excessive
humidity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE CONTROLLER
6
KOOLMASTER PP-32 REV.01
FOR CUSTOMER USE
Enter the serial number located on the side of the controller below for future reference.
Model number: Serial number:
PP-32

2. FEATURES

The PP-32 is an electronic device used for environmental control in livestock buildings. It allows the user to maintain a specified target temperature by controlling the operation of ventilation and heating equipment. Eight heater stages, 16 fan stages, a tunnel curtain, 2 auxiliary outputs, vent doors and 4 clock outputs can be controlled. Fan stages can be configured to activate cooling systems in timer mode. In all, the PP-32 provides up to 32 relay outputs. In addition, up to 12 DWR-F-1A air inlet controllers can be con­nected to the PP-32.
The main features of the PP-32 are as follows:
LCD DISPLAY
An LCD display provides an efficient interface for displaying, monitoring and adjusting parameter values.
MINIMUM VENTILATION CYCLE
When ventilation is not required for reducing room temperature, on-off fan outputs can be operated either continuously or intermittently to reduce the level of humidity and supply oxygen to the room.
TEMPERATURE AND MINIMUM VENTILATION CURVES
The controller can automatically change the temperature set point and the minimum ventilation's On-Time over a given period of time in accordance with the user's requirements.
AVERAGE TEMPERATURE READINGS RECORDED FOR THE PAST 60 DAYS
The average temperature readings are logged into the controller's history for the past 60 days.
INDIVIDUAL SENSOR READINGS RECORDED FOR THE PAST 10 DAYS
The minimum and maximum readings of each sensor (temperature & humidity sensors) are logged into the controller's history for the past 10 days.
WATER AND HEATER MONITORING
A pulse input is provided to monitor the water consumption. Heater run times are also logged into an history. These values are recorded for the current day and for the previous 60 days.
ALARM MANAGEMENT
Alarms are provided for high-low temperatures, defective sensors and other system failures. The controller keeps in memory the 10 most recent alarms.
KOOLMASTER PP-32 REV.01
7
PP-32
EIGHT INDEPENDENT TEMPERATURE SENSOR INPUTS
Up to eight temperature sensors can be connected to the controller in order to obtain a more accurate reading of the average room temperature and a faster reaction time. Sensors may be assigned to each heater output or to auxiliary outputs. Auxiliary outputs can be used to operate various devices such as heating units or stir fans for instance.
OUTSIDE TEMPERATURE SENSOR
HUMIDITY COMPENSATION
Three mechanisms can be used to compensate for a high humidity level:
1. Fans' On-Time, in minimum vent. cycles, can automatically be increased.
2. Kool-Cel or mist units can be shutoff.
3. Heaters can be activated in timer mode.
STATIC PRESSURE & VENT DOORS & TUNNEL CURTAIN CONTROL
A static pressure input is provided to control static pressure by opening and closing the vent doors and/or tunnel curtain.
CONTROL OF AIR INLET MOVEMENT
If the PP-32 is used in combination with one or more DWR-F-1A controllers, the movement of air inlets can be coordinated with the operation of the fans using a potentiometer located on the panel drive. This allows the air inlets to be adjusted correctly, without the influence of uncontrollable factors such as wind or air from adjoining rooms.
PASSWORD PROTECTION
A password can be enabled to restrict access to the controller setup functions.
BACKUP BATTERY
A backup battery allows the unit to keep time in case of a power failure.
OVERLOAD AND OVERVOLTAGE PROTECTION
Resettable fuses are provided at low-voltage inputs and outputs of the controller to protect its circuitry in the case of an overload or overvoltage.
COMPUTER CONTROL
The controller can be connected to a computer, thus making it possible to centralize the management of information and diversify control strategies.
TEST MODE
A test mode allows you to simulate temperature changes and verify controller performance, as well as manually activate each output sequentially.
8
KOOLMASTER PP-32 REV.01

3. LOCATION OF THE CONTROLS

Front Panel
LED
DISPLAY
LCD DISPLAY
MAIN MENUS
32 ON/OFF RELAYS
NAVIGATION
BUTTONS
ADJUSTMENT
BUTTONS
ALARM STATUS LED
SHORTCUT
KEYS
KOOLMASTER PP-32 REV.01
9
PP-32
LCD Display: The LCD display gives the current readings and param­eters to be adjusted when you select a function. When the parameters for a given function cannot all be presented at once on the display, arrows are displayed on the right handside to indicate that additional parameters can be displayed using the arrow keys.
After 5 minutes of inactivity, the display returns to the CURRENT
CONDITIONS display. Led Display: This display shows the current average room temperature. Navigation buttons (Arrow Keys): The up and down-arrow keys are used
to scroll within a function menu. The right-arrow key is used to select a menu option. The left arrow key is used to return to the previous menu display.
Adjustment Buttons: These two push-buttons allow the user to adjust the value of a parameter that is shown on the display.
Adjusting a Parameter: A parameter can be adjusted when it is flashing on the LCD display. Use the adjustment buttons to change the value of a parameter. Pressing increases the value, pressing decreases the value.
Shortcut Keys: These 6 buttons allow the user to step quickly to the special predefined functions on the display.
syeKtuctrohSnoitanitseD
goLmralA
snoitidnoCtnerruC
remiTnoitalitneVmuminiM
sgnitteSerusserPcitatS/srooDtneV
sgnitteSniatruClennuT
sgnitteSerutarepmeT
)segatSgnilooC/snaF(
10
KOOLMASTER PP-32 REV.01

4. MOUNTING INSTRUCTIONS

Fasten the four metal brackets on the mounting holes located behind the controller using the four screws included with the controller. Mount the enclosure on the wall using four other screws. Make sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from entering the control­ler. The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall. Push on the locking devices to open
LOCKING DEVICE
the enclosure as illustrated.

4.1 CONNECTION

To connect the controller, refer to the wiring diagram enclosed with this user's manual. Use the electrical knockouts provided at the bottom of the enclosure. Do not make additional holes in the enclosure, particularly on the side of the enclosure when using a computer communications module.
1. SENSOR INPUTS
!
WARNING
ROOM TEMPERATURE SENSORS
WATER METER
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRICIAN AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND REGULATIONS. BE SURE POWER IS OFF BEFORE DOING ANY WIRING TO AVOID ELECTRICAL SHOCKS AND EQUIPMENT DAMAGE.
HUMIDITY SENSOR (Refer to the main wiring diagram)
STATIC PRESSUR E SENSOR (Refer to the main wiring diagram)
OUTSIDE T° SENSOR
KOOLMASTER PP-32 REV.01
11
PP-32
Sensors operate at low voltage and are isolated from the supply. Be sure that sensor cables remain isolated from all high voltage sources. In particular, do not route the sensor cables through the same electrical knockout as other cables. Do not connect the shield from the sensor cable to a terminal or a ground.
Extending a sensor: Each sensor can be extended up to 500 feet (150 meters). To extend a sensor:
Use a shielded cable of outside diameter between 0.245 and
0.260 in (6.22 and 6.60 mm) (the cable dimensions should not be under 18 AWG) to ensure the cable entry is liquid tight. Do
not ground the shielding.
It is preferable to solder the cable joint to ensure a proper contact between the two cables.
CAUTION: Do not run sensor cables next to other power cables. When crossing over other cables, cross at 90°.
Defective temperature sensors: An alarm is generated when a defective sensor is detected. The defective temperature sensors are identified in the "15. Alarm Log" menu. Press the key to directly access this menu.
2. ALARMS
ALARM
There are two types of alarms on the market. One type activates when current is cut off at its input, whereas the other activates when current is supplied at its input. For an alarm of the first type, use the NC
12
KOOLMASTER PP-32 REV.01
PP-32
terminal as shown on the wiring diagram. For an alarm of the second type, use the NO terminal.
3. DWR-F-1A COMMUNICATION HOOKUP
If DWR-F-1A air inlet controllers are connected to the PP-32, use id numbers within the range 4-15. Id numbers 1,2 and 3 are reserved for another purpose. Refer to section 5.5.1.1 to set the proper ID numbers.
KOOLMASTER PP-32 REV.01
13
PP-32

4.2 SETTING THE DIP SWITCHES

The PP-32 has 12 DIP switches (only the first 7 are used) which deter­mine how the controller works. These switches are located on the board inside the top cover.
ON
ON
OFF
123456789101112
To change the position of a DIP switch, use a small screwdriver or similar object to move the switch to the desired position.
Pay attention when setting DIP switches. Since they are very close to each other, it is easy to switch 2 switches at the same time.
When the controller is shipped, all DIP switches are set
!
to the OFF position.
WARNING
14
KOOLMASTER PP-32 REV.01
ALWAYS close the controller before applying power to it.
1 SEERGEDTIEHNERHAF SEERGEDSUISLEC 2 EDOMMP/MA EDOMSRUOH42 3 SNOLLAG SRETIL
4 RETAWFOSEHCNI SLACSAP
5
6
7
8 DESUTON 9 DESUTON
#hctiwS FFO NO
TSIMROLLECLOOK NOITASNEPMOCHR
ELBASID
HRRETAEH
NOITASNEPMOC
ELBASID
NOITALITNEVMUMINIM
NOITASNEPMOCHR
ELBASID
01 DESUTON 11 DESUTON 21 DESUTON
ELBATHCTIWSPID
TSIMROLLECLOOK
NOITASNEPMOCHR
ELBANE
HRRETAEH
ELBANENOITASNEPMOC
HRNOITALITNEVMUMINIM ELBANENOITASNEPMOC

5. CONTROLLER SETUP

5.1 CURRENT CONDITIONS

The current conditions menu gives a quick view of the actual conditions in the barn. Press to step directly to this menu.
Room Set Point: this is the target temperature in the barn.
Average Temperature: shows the average temperature in the barn.
Static Pressure: current static pressure in the barn.
Fan Stage: shows which fan stage is currently active.
Program: shows the selected program.
Fan On-Time sec: fans' on-time in minimum ventilation.
Sensor 1-8: actual reading of each temperature sensor.
Outside: actual outside temperature reading.
RH Sensor: current humidity level in the room.
Room Set Point 80.0 Average Temp 79.2 Static Pressure 0.01 Fan Stage: Min.V Program: (a) Fan On Time sec 30 Sensor 1: 79.3 Sensor 2: 79.1 Outside: 65.9 R. Humidity 74
KOOLMASTER PP-32 REV.01
15
PP-32

5.2 CONTROLLER PROGRAMS

The controller allows to use up to 4 separate programs to control the room temperature. It then becomes possible to activate a specific program, that uses particular fan settings, in accordance with the animal age for instance.
Relays that are activated on fan stages 1-4 vary depending on the chosen program: the first 4 fan stages use separate relay assignment settings for each program. This allows to activate a greater number of fans as the occupied space in the barn increases. Fan stage's sensor assignment must also be set separately for each program in use.

5.2.1 Selecting a Program

Use the navigation buttons to select "5. Program Select" from the main menu then press the right-arrow key. The program that is currently in use is flashes on the display.
Use the adjustment buttons to select the proper program (a, b, c or d). Only the programs that have been enabled during the installation can be selected (see sec. 5.14.3). Press the left-arrow key to exit this menu.
5. Program Select.
Fan / Sensor Program Selection: (a) Temp Settings: Summr
Main Menu

5.2.2 Selecting a Season

The start and stop temperatures of heating and ventilation stages can be set separately for summer and winter seasons. The season change is signalled by the user as follows:
Use the navigation buttons to select "5. Program Select" from the main menu then press the right-arrow key. The program that is currently in use is flashes on the display.
Press the down-arrow key to select the " Temp Settings" display.
16
KOOLMASTER PP-32 REV.01
PP-32
Use the adjustment buttons to select the proper season (winter/ summer). The start and stop temperatures of heating and ventilation stages that are associ­ated with this seasons will be used.
Press the left-arrow key to exit this menu.
Fan / Sensor Program Selection: (a) Temp Settings: Summr
KOOLMASTER PP-32 REV.01
17
PP-32

5.3 ADJUSTING THE ROOM SET POINT

The room set point is the target room temperature. It can be adjusted between 32°F and 120°F (0°C and 48.9°C). Note that the temperature curve must be turned off to adjust this value.
The set point can quickly be accessed by pressing the shortcut key (note that the set point will not be accessible this way if the temperature curve is turned on, see below to deactivate the temperature curve).
Select the "6.Room Set Point" function from the main menu using the navigation buttons then press the right-arrow key. The current set point is displayed, as well as the on/ off state of the temperature curve.
6. Room Set Point
Main Menu
If the temperature curve is OFF, the set point flashes on the display. Use the adjustment buttons to adjust the room set point to the desired value.
If the temperature curve is ON, the set point, as determined by the temperature curve, is displayed. Press the down-arrow key and scroll the menu until "Curve stat" status flashes on the display. Press
to turn off the temperature
curve then follow the procedure above to adjust the set point.
18
KOOLMASTER PP-32 REV.01
Room Temperature
Set Point: 80.0°F Curve stat Off Day: 1 Temp: 60.0°F Day: 10 Temp: 75.0°F
(...)
Curve stat Off
PP-32

5.4 MINIMUM VENTILATION

PRINCIPLE OF OPERATION When the room temperature is below the set point, fans can operate
according to a timer. The minimum ventilation cycles runs stage 1 fans according to a timer as shown below. Running fans even though ventila­tion is not required for reducing the room temperature is useful to reduce the humidity level and supply oxygen to the room. It also prevents the fans from freezing in winter.
MINIMUM VENTILATION TIMER
ON
OFF
In addition, fans' On-Time, in minimum ventilation, can automatically be adjusted over time by using a curve. Refer to section 5.15.2 for further information on the minimum ventilation curve.
Note that the minimum ventilation curve must be TURNED OFF in order to adjust minimum ventilation settings.
ON-TIME
CYCLE-TIME

5.4.1 Adjusting Minimum Ventilation's On-Time

Fans' On-Time, in the minimum ventilation cycle, can be adjusted from 0 to 900 seconds (15 minutes), in increments of 5 seconds. Note that the On-Time cannot be greater than the cycle time. If vent doors are used, the On-Time is limited by the vent doors' pre-opening delay (see sec. 5.14.3).
Select "7.Min. Ventilation" from the main menu using the naviga­tion buttons then press the right­arrow key.
Min ventilation
On Time: 30sec Curve stat Off
KOOLMASTER PP-32 REV.01
19
PP-32
Use the arrow keys to select the "1. On Time/Curve" function. Press the right-arrow key. The fans' On- Time, in minimum ventilation, is displayed, as well as the status of the minimum ventilation curve.
If the curve is OFF, the On-Time value flashes on the display. Use the adjustment buttons to adjust minimum ventilation's On- Time to the desired value then press the left-arrow key to exit this menu.
If the curve is ON, press the down-arrow key to scroll all ten points of the curve. The curve status flashes on the display. Press to turn off the minimum ventilation curve then follow the procedure
above to adjust the set point.

5.4.2 Adjusting Minimum Ventilation's Cycle Time

Fans' Cycle-Time, in minimum ventilation, can be adjusted from 0 to 900 seconds (15 minutes), in increments of 5 seconds. If vent doors are used, the Cycle-Time is limited by the vent doors' pre-opening delay : it must be set at a greater value than twice the pre-opening delay (see sec. 5.14.3).
Min ventilation
Curve stat Off
Select "7.Min. Ventilation" from the main menu using the navigation buttons then press the right-arrow key.
Use the arrow keys to select the "2. Cycle Time" function. Press the right-arrow key. The current cycle time flashes on the display.
Use the adjustment buttons to adjust the Cycle-Time to the desired value then press the left-arrow key to exit this menu.
20
KOOLMASTER PP-32 REV.01
Min Ventilation Cycle Time 300sec
PP-32

5.5 INLET / VENT DOOR SETTINGS

The PP-32 controller can operate the air inlets / vent doors in two different ways:
1. Inlets' positions can be determined by using a potentiometer feedback controller (DWR-F-1A). Refer to the installation setup section to enable DWR-F-1A modules. Note that the static pressure sensor must be deactivated in order to activate the air inlets (see sec. 5.15.3).
2. Inlets' positions can be determined by the static pressure level in the barn. In this case, a static pressure sensor is required and must be activated during the installation setup (see sec. 5.15.3). The term "Vent Door" is used to refer to an air inlet that is controlled by the static pressure.

5.5.1 Inlet Settings (Potentiometer Feedback from Inlets)

If air inlets operate according to potentiometer feedback modules (DWR­F-1A), the PP-32 controller adjusts the air inlets opening according to ventilation stages. As the temperature increases and new stages are activated, the inlet is opened or closed accordingly. The air inlet position is directly related to these ventilation stages. Refer to the DWR-F-1A instruction manual to program inlet openings.
In addition, a compensation can be activated to ensure the uniformity in room temperature: air inlet positions are automatically adjusted when the reading of the sensors that are associated with the air inlet differs from the average room temperature.
5.5.1.1 Setting DWR-F-1A's ID numbers
ID numbers must be assigned to each DWR-F-1A modules. This allows to establish the communication with the PP-32 control and the external modules. The following table gives the proper ID numbers for each
DWR-F-1A module.
KOOLMASTER PP-32 REV.01
21
PP-32
Note that the reference numbers that are used by the PP-32 DO NOT correspond to the ID numbers that used by the DWR-F-1A modules because #1, 2 and 3 are reserved for other purpose.
23-PP
#ecnerefeR
14
25
......
2151
#diA1-F-RWD
5.5.1.2 Adjusting the Air Inlet Compensation
The compensation is expressed as a percentage per degree difference between the average controller's temperature and the average tempera­ture of sensors that are assigned to the inlet. It determines by how much the inlet must open or close to help reduce the temperature differences in the building. For each degree above or below the average tempera­ture, the inlet will open or close using the compensation value assigned by the user. For example, if the compensation value is set to 5%/°F and the inlet's sensors read 3°F above the average controller temperature, the inlet will open of 15% to help decrease the temperature in that zone.
The compensation can be adjusted from 0 to 10% of inlets' opening or to "Off" to deactivate this function.
Select "8.Inlet Settings" from the main menu using the navigation buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor is disabled and if inlets have been activated (see sec. 5.15.3).
Press the right-arrow key once again to select "1.Inlet Comp" menu. The compensation value of each air inlet is displayed.
Use the up or down-arrow key to select the desired inlet.
Use the adjustment buttons to set the compensation to the proper value. Press the left-arrow key to exit this menu.
22
KOOLMASTER PP-32 REV.01
Inlet Settings
1. Inlet Comp
Inlet Compensation Inlet 1 5%/°F Inlet 2 5%/°F Inlet 3 5%/°F
PP-32

5.5.2 Vent Door Settings

If a static pressure sensor is used, the PP-32 can control the static pressure in the room by opening and closing vent doors. When the pressure drops below the low pressure set point, the vent doors close according to a timer. Likewise, when the static pressure increases above the high pressure set point, the vent doors open according to a timer. It is also possible to define a stage level above which the vent doors will always remain closed. Refer to sec. 5.15.3 to activate the static pressure sensor.
VENT DOORS OPERATION
STATIC
PRESSURE
VENT DOORS STOP
OPENING
HIGH SET POINT
(OPEN AT)
LOW SET POINT
(CLOSE AT)
STATIC PRESSURE
EXCEEDS
CLOSING
HI SET POINT:
VENT DOORS OPEN IN
TIMER CYCLE
(OPEN TI ME/ OFF TIME)
OPEN
VENT DOORS
STAY STILL
VENT DOORS
CLOSE
VENT DOORS
STATIC PRESSURE
DROPS BELOW LO SET POI N T:
VENT DOORS CL OSE IN
TIMER C YCLE
(CLOSE TIME/ OFF TI ME)
VENT DOORS STOP
TIME
In minimum ventilation, the vent doors open during the pre-opening delay before fans start running. The same delay is used to close the vent doors when the stage 1 fans return to a stop.
Static Pressure Alarm: alarms can be set off if the static pressure remains below or exceeds a certain level for a too long period of time. In this case, a delay is set in order to activate the alarm: the alarm condition must maintained during this delay before the alarm is set off. Refer to section 5.13.2 to set the static pressure alarm settings.
KOOLMASTER PP-32 REV.01
23
PP-32
GROUPS OF STATIC PRESSURE SET POINTS :
Two groups of static pressure set points can be defined. HI and LO static pressure set points #2 start being used either when a certain ventilation stage is reached or when the outside temperature decreases below a user-define value. The following graphs sum both cases:
1. Static pressure set points' transition according to ventilation stages:
Example: when the start temperature of stage 5 is reached, the vent
doors start operating according to the second group of static pressure set points. The first group of set points is being used once again when the room temperature drops below the stage 5 stop temperature.
STATIC PRESSURE SET POINTS
INFLUENCED BY VENTILATION STAGES
STATIC
PRESSURE
SET POINTS
HI SET POINT 2
(OPEN AT)
HI SET POINT 1
(OPEN A T )
LO SET POINT 2
(CLOSE AT)
LO SET POINT 1
(CLOSE AT)
FAN STAGE 5
STOP T°
FAN STAGE 5
START T°
TEMPERATURE
ROOM
Refer to the installation setup section to activate the second group of static pressure set points (see sec. 5.14.3).
24
KOOLMASTER PP-32 REV.01
PP-32
2. Static pressure set points' transition according to the outside T°:
Example: When the outside temperature drops below the "outside
temperature influence" value, a transition between the two set point groups starts. When the outside temperature decreases 5°F further than the user-defined value, the second group of set points is used.
STATIC PRESSURE SET POINTS
INFLUENCED BY THE OUTSIDE TEMPERATURE
STATIC
PRESSURE
SET POINTS
HI SET POINT 1
(OPEN AT)
HI SET POINT 2
(OPEN AT)
LO SET POINT 1
(CLOSE AT)
LO SET POINT 2
(CLOSE AT)
50°F
(27.8°C)
5°F
(2.8°C)
55°F
(30.6°C)
(outside t° influence)
OUTSIDE
TEMPERATURE
Refer to the installation setup section to activate the second group of static pressure set points (see sec. 5.14.3).
KOOLMASTER PP-32 REV.01
25
PP-32
5.5.2.1 Adjusting Static Pressure Set Points
When the high pressure set point is reached opens the vent doors according to a timer cycle. When the low pressure set point is reached according to the another timer. The pressure set points can be adjusted from 0 to 0.2 inches of water (0 to 50Pa).
Select "8.Vents/Static P" from the main menu using the navigation buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor has been enabled during the installation setup (see sec 5.14.3).
Press the right-arrow key to select the "1.Set Points" menu.
Press the down-arrow key once, the LO static pressure set point is selected
Use the adjustment buttons to adjust the low static pressure set point value then press the down-arrow key. The hi static pressure set point
Use the adjustment buttons to adjust the hi static pressure set point
(Close At)
(Open At)
(Open At)
(Close at)
is selected.
to the desired value.
, the controller closes the vent doors
.
(Open at)
Vents/Static Press Cal. SP .000WC Close At: .070WC Open At: .090WC
(Close At)
, the controller
to the desired
5.5.2.2 Adjusting Vent Doors Open / Close / Off Times
When the static pressure level in the room exceeds the hi or low set points, the vent doors start opening or closing according to a cycle, as explained below:
Open Time: when the static pressure exceeds the Hi pressure set point, the vent doors open during this delay. The open time ranges from 0 to 900 seconds.
Close Time: when the static pressure drops below the Lo pressure set point, the vent doors close during this delay. The close time ranges from 0 to 900 seconds.
26
KOOLMASTER PP-32 REV.01
PP-32
Off Time: once the vent doors have opened or closed (depending on the situation), they then stop operating during the Off time delay. The Off Time delay ranges from 0 to 900 seconds.
VENT DOORS TIMER
OPEN / CLOSE
ON
TIMES
OFF
OFF TIME
If the pressure has not reached the desired value after the Off Time, the cycle starts again, up until the pressure goes back into the normal range.
Select "8.Vents/Static P" from the main menu using the navigation buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor has been enabled during the installation setup (see sec 5.14.3).
Press the right-arrow key to select the "1.Set Points" menu.
Press the down-arrow key in order to select the Open Time then use the adjustment buttons to set the
Open Time 30sec Close Time 30sec Off Time 60sec
opening time to the desired value.
Press the down-arrow key. The Close Time flashes on the display. Use the adjustment buttons to set the Close Time to the desired value.
Press the down-arrow key once again. The Off Time flashes on the display. Use the adjustment buttons to set the Off Time to the desired value.
KOOLMASTER PP-32 REV.01
27
PP-32
5.5.2.3 Adjusting Stage Level for the Closing of Vent Doors
When the stage defined by this parameter is reached, the vent doors start to close continuously until they are completely closed, no matter what the static pressure is. This feature is usefull for closing vent doors when a tunnel ventilation stage starts. Select "None" to deactivate this function.
Select "8.Vents/Static P" from the main menu using the navigation buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor has been enabled during the installation setup (see sec 5.14.3).
Press the right-arrow key to select the "1.Set Points" menu.
Press the down-arrow key in order to select "Close Vent Door At Stage" menu on the display.
Use the adjustment buttons to select the fan stage above which the vent doors will be closed.
Close Time 30sec Off Time 60sec Close Vent Door At Stage 5
5.5.2.4 2nd Group of Pressure Set Points: at Stage X
The following procedure shows how to select the fan stage above which the second group of static pressure set points starts being used. It also explains how to adjust Hi and Lo static pressure set points #2
and Close At)
Select the "8.Vents/Static P" from the main menu using the naviga­tion buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor has been enabled during the installation setup (see sec 5.14.3).
Press the right-arrow key to select the "1.Set Points" menu. Press the down-arrow key in order to
select "Static Settings 2 At Stage" display. This menu is only displayed if the 2nd group of static pressure set points has been enabled during the installation (see sec. 5.14.3).
. Refer to sec.5.14.3 to activate this function.
Static Settings 2 At Stage 10 Close At: .050WC Open At: .080WC
(Open At
28
KOOLMASTER PP-32 REV.01
PP-32
Use the adjustment buttons to select the fan stage above which the second group of static pressure set points starts being used.
Press the down-arrow key once, the LO static pressure set point #2 is selected
Use the adjustment buttons to adjust the 2nd low static pressure set point The HI static pressure set point #2
Use the adjustment buttons to adjust the 2nd HI static pressure set point
Press the left-arrow key to exit this menu.
5.5.2.5 2nd Group of Pressure Set Points: at Outside T° X
The following procedure shows how to select the outside temperature below which the second group of static pressure set points starts being used. It also explains how to adjust the second group of Hi and Lo static pressure set points activate this function.
(Close At)
(Close At)
(Open At)
.
to the desired value then press the down-arrow key.
(Open At)
to the desired value.
(Open At and Close At)
. Refer to sec.5.14.3 to
is selected.
Select "8.Vents/Static P" from the main menu using the navigation buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor has been enabled during the installation setup (see sec 5.14.3).
Press the right-arrow key to select the "1.Set Points" menu.
Press the down-arrow key in order to the select "Outside Temperature Influence" display. Note that this menu only appears if the outside temperature has been enabled during the installation setup and if the 2nd Group of static pressure set points has been enabled (see sec
5.14.3).
Static Settings 2 Outside Temperature Influence: 50.0°F Close At: .070WC Open At: .090WC
KOOLMASTER PP-32 REV.01
29
PP-32
Use the adjustment buttons to set the outside temperature below which the second group of static pressure set points start to be used.
Press the down-arrow key once, the LO static pressure set point #2
(Close At)
Use the adjustment buttons to adjust the 2nd low static pressure set point The HI static pressure set point #2
Use the adjustment buttons to adjust the 2nd HI static pressure set point
Press the left-arrow key to exit this menu.
is selected .
(Close At)
(Open At)
to the desired value then press the down-arrow key.
(Open At)
to the desired value.
is selected.
30
KOOLMASTER PP-32 REV.01
Loading...
+ 70 hidden pages