ATxBlock
Universal Temperature Transmitter
User Manual

WARNING
This manual should be passed on to the end user.
The contents of this manual are subject to change without prior notice.
All rights reserved.
ABUS gives no warranty of any kind with regard to this manual, including, but not limited to, fitness
for a particular purpose.
If any question arises or errors are found, or if any information is missing from this manual, please
ATxBlock
inform your supplier or inform at info@abustek.com
.
The specifications mentioned in this manual are limited to those for the standard type under the
specified model number break-down and do not necessarily apply for customized instruments.
Please note that changes in the specifications, construction, or component parts of the instrument
may not immediately be reflected in this manual at the time of change.
If the customer or any third party is harmed by the use of this product, ABUS assumes no
responsibility for any such harm owing to any defects in the product which were not predictable, or
for any indirect damages.
Although Warning hazards are related to personal injury, and Caution hazards are associated
with equipment or property damage, it must be understood that operation of damaged equipment could,
under certain operational conditions, result in degraded process system performance leading to
personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of
our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are
not to be reproduced in full or part without prior approval of Technical Communications Department,
ABUS Technologies
HEALTH AND SAFETY
To ensure that our products are safe and without risk to health, the following points must be
noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained
personnel and in accordance with the information given. Any deviation from these instructions will
transfer the complete liability to the user.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when
operating in conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept
dry. Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant
hazard data sheets (where applicable) may be obtained from the Company address on the back cover,
together with servicing and spares information.
ABUS TECHNOLOGIES INC.
2

.
ATxBlock
CATALOGUE
Contents Page No.
1. Introduction 4
2. Presentation
Technical Parameters
3. Dimensions 5
4. Ordering Details 5
5. Connections
1. Connector Specification
2.
Wiring
6. Installation
1. Recommendation
2. Input Sensors
7. Configuration 7
8. Maintenance
Calibration of Instruments
9. Safety Precautions 11
10. Warranty 11
4
4
5
5
6
6
6
7
10
10
ABUS TECHNOLOGIES INC.
3

1. INTRODUCTION
The ATxBlock is a 2-wire in-head temperature transmitter, microprocessor
based designed for the flexibility of accepting mV, Pt100 and a variety of
thermocouples as the input sensor. The ATxBlock delivers a scalable linear 4-20mA or
0-10V output signal proportional to the sensor temperature. User-friendly configuration
software is provided for parameter setup, including sensor type, temperature range,
filter, etc.
2. PRESENTATION
Technical Parameters
Sensor input: User defined. The supported sensors are listed in table 6.2 ATxBlock
ATxBlock
Input Sensors, along with their maximum ranges and minimum span.
Thermocouples: Types J, K, R, S, T, N, B and E, according to IEC 60584 (ITS-90).
Impedance >> 1 M
Pt100: Excitation: 180 A.
2 or 3-wire connection (for 2-wire sensors, tie terminals 2 and 3
together).
= 0.00385, according to IEC 60751(ITS-90).
Voltage: 0 ~ 50mV dc.
Impedance: 1 M
Total accuracy: Better than 0.25% of the maximum range for thermocouples and 0,15%
for Pt100 and voltage;
Response Time: < 100 ms;
Output: 2-wire 4-20 mA, linear with respect to the measured temperature.
Resolution: 0.004 mA (12 bits).
Power supply: 12 to 35 Vdc, across the transmitter;
Maximum load (RL): RL (max.)= (Vdc – 12) / 0,02 []
Where: Vdc= Power supply voltage
Operating Temperature: -40 to 85 °C
Humidity: 0 to 90% RH
Electromagnetic compatibility: EN 50081-2, EN 50082-2
Polarity inversion protection: Internal
No isolation
Cold junction compensation for thermocouples.
between the sensor and the 4-20mA loop.