VR8105, VR8205, and VR8305
Direct Ignition Combination
Gas Controls
INSTALLATION INSTRUCTIONS
APPLICATION
These direct ignition gas controls are used in gas-fired
appliances with up to 415 ft
pressure drop (8.5 m
They include a manual valve, two automatic operators
and a pressure regulator.
Model
VR81051/2 x 1/2852.3
VR82051504.2
VR8305
VR8305
VR8305
a
Capacity based on 1000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas
at 0.25 kPa pressure drop).
b
Capacity is reduced by 5 percent when using an outlet screen.
c
Valves are guaranteed at only 77 percent of the rating.
d
Minimum regulation for LP gas is 15,000 Btuh.
e
Minimum regulation for LP gas is 40,000 Btuh.
f
Minimum regulation for LP gas is 50,000 Btuh.
Table 2. Gas Capacity Conversion Factor.Table 3. Model Number Suffix Letter Designation.
Manufactured0.600.516
Mixed0.700.765
Propane1.531.62
Size Inlet-
Outlet (in.)
b,c
b,c
1/2 x 3/42707.637010.5
b,c
3/4 x 3/43008.541511.8
GasSpecific Gravity
3
/hr capacity at 1 in. wc
3
/hr at 0.24 kPa) on natural gas.
Table 1. Valve Capacity.
AGA Certified
Capacity for
Natural Gas
3
/hrm3/hrft3/hrm3/hrft3/hrm3/hr
ft
2406.8
Multiply Listed
Capacity By
These gas controls are available in a range of valve
capacities; see Table 1. (Table 2 provides gas capacity
conversion factors.) The suffix letter indicates
temperature range and regulator type; see Table 3.
a
AGA Certified Minimum
Regulation for
Natural Gas
d
10
e
20
f
30
Model No.
Suffix
Letter
A0°F t0 175° F
CStep-opening
HSlow-opening
K-40°F to +175°F
MStandard
PStep-opening
QTwo-stage
RConvertible
0.41203.4
0.62005.7
0.83409.6
Ambient
Temperature Range
(-18°C to +79°C)
(-40°C to +79°C)
AGA Certified Maximum
Regulation for Natural
Gas
Pressure
Regulator Type
Standard
69-1226—3
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
SPECIFICATIONS
Body Pattern: Straight through; See Table 1 for inlet and
outlet size.
Electrical Ratings:
Voltage and Frequency: 24 Vac, 60 Hz.
Current Draw: 0.5A with both operators energized.
Capacity: See Table 1.
Conversion:
Use conversion factors in Table 2 to convert capacities for
other gases.
Regulation Range: See Table 1.
Natural-LP Gas Conversion Kits: See Table 4.
Pipe Adapters:
Angle and straight adapters available for 3/8-, 1/2- and
3/4-in. pipe. See Table 5. Flange kits include one
flange with attached O-ring, four mounting screws, a
9/64 in. hex wrench and instructions.
Approvals:
American Gas Association Design Certificate: L2025006.
Canadian Gas Association Design Certificate: L2025006.
Australian Gas Association Design Certificate: 4214.
Approved for Delta C applications.
European Community (CE) Certificate: Pending.
PLANNING THE INSTALLATION
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow these warnings exactly:
1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in
the Maintenance section.
Heavy demands are made on the controls when direct
ignition systems are used on central heating equipment in
barns, greenhouses, and commercial properties and on
heating appliances such as commercial cookers,
agricultural equipment, industrial heating equipment and
pool heaters.
Special steps may be required to prevent nuisance
shutdowns and control failures due to frequent cycling,
severe environmental conditions related to moisture,
corrosive chemicals, dust or excessive heat. These
applications require Honeywell Engineering review;
contact your Honeywell Sales Representative for
assistance.
Review the following conditions that can apply to your
specific installation and follow the precautions suggested.
Frequent Cycling
this control is designed for use on appliances that typically
cycle three to four times an hour only during the heating
season. In year-around applications with greater cycling
rates, the control can wear out more quickly. Perform a
monthly check.
Table 4. Natural-LP Gas Conversion Kits.
Model No. Suffix LetterKit to Convert Natural Gas to LPKit to Convert LP to Natural Gas
Equipment Damage Hazard.
Improper use can damage equipment.
Read the instructions before use. This control
must be installed in accordance with the rules in
force.
Water or Steam Cleaning
If a control gets wet, replace it. If the appliance is likely to
be cleaned with water or steam, protect (cover) the
control and wiring from water or steam flow. Mount the
control high enough above the bottom of the cabinet so it
does not get wet during normal cleaning procedures.
High Humidity or Dripping Water
Dripping water can cause the control to fail. Never install
an appliance where water can drip on the control. In
addition, high ambient humidity can cause the control to
corrode and fail. If the appliance is in a humid
atmosphere, make sure air circulation around the control
is adequate to prevent condensation. Also, regularly
check out the system.
Corrosive Chemicals
Corrosive chemicals can attack the control, eventually
causing a failure. If chemicals are used for routine
cleaning, avoid contact with the control. Where chemicals
are suspended in air, as in some industrial or agricultural
applications, protect the control with an enclosure.
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause the
control to malfunction. Where dust or grease can be a
problem, provide covers for the control to limit
contamination.
Heat
Excessively high temperatures can damage the control.
Make sure the maximum ambient temperature at the
control does not exceed the rating of the control. If the
appliance operates at very high temperatures, use
insulation, shielding, and air circulation, as necessary, to
protect the control. Proper insulation or shielding should
be provided by the appliance manufacturer; verify proper
air circulation is maintained when the appliance is
installed.
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after installation is complete.
3. Always install a sediment trap in gas supply line
to prevent contamination of gas control.
4. Do not force the gas control knob. Never use
any tools. If the gas control knob does not
operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
CAUTION
Equipment Damage.
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
Follow the appliance manufacturer instructions, if
available. Otherwise, use these instructions as a guide.
IMPORTANT
These gas controls are shipped with protective
seals over the inlet and outlet tappings. Do not
remove the seals until ready to install adapters
or connect the piping.
369-1226—3
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
Converting Gas Control from Natural GAs
to LP Gas (or LP Gas to Natural Gas)
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
1. Do not attempt to convert step-opening models
(suffix letter P).
2. Always change the main and pilot burner
orifices when converting from natural to LP gas
or from LP to natural gas. Carefully follow
appliance manufacturer specification and
instructions to assure proper appliance
conversion.
3. Gas controls are factory-set for natural (and
manufactured) gas or LP gas. Do not attempt to
use a gas control set for natural (manufactured)
gas on LP gas or a gas control set for LP gas
on natural (manufactured) gas.
Controls with standard, slow-opening, and two-stage
regulators (model numbers with suffix letters H, K, M, or
Q) can be converted from one gas to the other with a
conversion kit (ordered separately). See Table 4 for the
correct conversion kit.
Convertible Pressure Regulators
Controls with suffix letter R are convertible pressure
regulator models. They can be converted from natural gas
to LP gas or from LP gas to natural gas without a
conversion kit.
Before converting the control from one gas to the other,
check the control label and the appliance manufacturer
rating plate to determine of the pressure regulator setting
(factory-set) will meet the appliance manifold
requirements after conversion.
letter R) do not have field-adjustable regulators.
If the factory pressure regulator setting meets the
appliance manifold requirement, convert the control as
follows:
1. Remove the pressure regulator cap, Fig. 1.
2. Invert the cap so that the letters appear that
represent the gas type appropriate for the
appliance; NAT for natural (manufactured) gas, LP
for liquid petroleum gas.
3. Replace the cap and tighten firmly.
PRESSURE
REGULATOR
CAP
T
N
A
A
N
T
T
N
A
A
N
T
P
OR
L
OTHER SIDE
OF CAP
M11678
L
P
Fig. 1. Top view of convertible pressure regulator cap.
Install Adapters to Control
If adapters are being installed on the control, mount them
as follows:
Flanges
1. Choose the appropriate flange for your application.
Remove the seal over the ignition system control inlet or
outlet.
2. Make sure the O-ring is fitted in the groove of the
flange. If the O-ring is not attached or is missing, do
not use the flange.
3. With the O-ring facing the gas control, align the
screw holes on the control with the holes in the
flange.
4. Insert and tighten the screws provided with the
flange. See Fig. 2. Tighten the screws to 25 inchpounds of torque to provide a gas-tight seal.
VALVE OUTLET
FLANGE
9/64 INCH HEX SCREWS (4)
DO NOT OVERTIGHTEN SCREWS. TIGHTEN TO
1
25 INCH-POUNDS.
Fig. 2. Firmly fasten flange to valve,
but do not overtighten screws.
1
M9046
69-1226—34
Bushings
1. Remove the seal over the control inlet or outlet.
2. Apply a moderate amount of good quality pipe
compound to the bushing, leaving two end threads
bare. On an LP installation, use compound that is
resistant to LP gas. Do not use Teflon® tape.
3. Insert the bushing in the control and carefully thread
the pipe into the bushing until tight.
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
Complete the instructions below for installing the piping,
installing the control, connecting the pilot gas tubing and
the wiring. Make sure the leak test you perform on the
control after completing the installation includes leak
testing the adapters and screws. If you use a wrench on
the valve after the flanges are installed, use the wrench
only on the flange, not on the control. See Fig. 5.
Location
The gas controls are mounted in the appliance vestibule
on the gas manifold. If this is a replacement application,
mount the gas control in the same location as the old
control.
Locate the combination gas control where it cannot be
affected by steam cleaning, high humidity, or dripping
water, corrosive chemicals, dust or grease accumulation
or excessive heat. To assure proper operation, follow
these guidelines:
• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom
to avoid exposure to flooding or splashing water.
• Assure the ambient temperature does not exceed the
ambient temperature rating for each component.
• Cover gas control if appliance is cleaned with water,
steam or chemicals or to avoid dust and grease
accumulation.
• Avoid locating gas control where exposure to corrosive
chemical fumes or dripping water is likely.
Install Piping to Control
All piping must comply with local codes and ordinances or
with the National Fuel Gas Code (ANSI Z223.1, NPFA No.
54), whichever applies. Tubing installation must comply
with approved standards and practices.
1. Use new, properly reamed pipe that is free from
chips. If tubing is used, make sure the ends are
square, deburred and clean. All tubing bends must
be smooth and without deformation.
2. Run pipe or tubing to the control. If tubing is used,
obtain a tube-to-pipe coupling to connect the tubing
to the control.
3. Install a sediment trap in the supply line to the
control. See Fig. 3.
Install Control
1. Mounted 0 to 90 degrees in any direction, including
vertically, from the upright position of the gas control
knob.
2. Mount so the gas flow is in the direction of the arrow
on the bottom of the control.
3. Thread the pipe the amount shown in Table 7 for
insertion into control or adapters. Do not thread
pipe too far. Valve distortion or malfunction can
result if the pipe is inserted too deeply.
Table 7. NPT Pipe Thread Length (in.).
Pipe
Size
Thread Pipe
this Amount
Maximum Depth Pipe can be
inserted into Control
3/89/163/8
1/23/41/2
3/413/163/4
DROP
3 IN.
PIPED
GAS
SUPPLY
GAS
CONTROL
2
DROP
TUBING
1
GAS
SUPPLY
2
GAS
CONTROL
2
HORIZONTAL
3 IN.
(76 MM)
MINIMUM
HORIZONTAL
RISER
(76 MM)
MINIMUM
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
1
2
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
RISER
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
GAS
CONTROL
M3077
Fig. 3. Sediment trap installation.
4. Apply a moderate amount of good quality pipe com-
pound (do not use Teflon® tape) only to the pipe,
leaving two end threads bare. On LP installations,
use a compound resistant to LP gas. See Fig. 4.
5. Remove the seals over the control inlet and outlet if
necessary.
6. Connect the pipe to the control inlet and outlet. use
a wrench on the square ends of the control. If a
flange is used, place the wrench on the flange
rather than on the control. Refer to Fig. 5 and 6.
TWO IMPERFECT
THREADS
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
GAS CONTROL
PIPE
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
M3075B
Fig. 4. Use moderate amount of pipe compound.
569-1226—3
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
APPLY WRENCH
FROM TOP OR
BOTTOM OF GAS
CONTROL TO
EITHER SHADED AREA
HI-LO
ADJUSTMENT SCREWS
(UNDER CAP)
REGULATOR
VENT COVER
WHEN FLANGE IS NOT USED
WHEN FLANGE IS USED
APPLY WRENCH
TO FLANGE ONLY
Fig. 5. Proper use of wrench on gas control with and without flanges.
INLET
PRESSURE REGULATOR
ADJUSTMENT (UNDER
CAP SCREW)
INLET
LO
HI
TWO-STAGE
PRESSURE
REGULATOR
MODEL
PRESSURE TAP
INLET
WIRING
TERMINALS (2)
GAS CONTROL KNOB
Fig. 6. Top view of gas control.
OUTLET
PRESSURE
TAP
OUTLET
M3084A
M10967A
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before making wiring
connections. More than one disconnect may be
involved.
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the general instructions
provided below. When these instructions differ from the
appliance manufacturer, follow the appliance
manufacturer instructions.
69-1226—36
All wiring must comply with applicable electrical codes
and ordinances.
1. Disconnect power supply before making wiring
connections to prevent electrical shock or
equipment damage.
2. Check the power supply rating on the gas control
and make sure it matches the available supply.
Install a transformer and other controls as required.
3. Connect the control circuit to the gas control
terminals. See Fig. 7 and 8.
4. Adjust thermostat heat anticipator to 0.50A rating
stamped on valve operator.
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
A
L1
MV
MV
BURNER
HOT
SURFACE
IGNITERSENSOR
Q354 FLAME
SENSOR
LIMIT
CONTROLLER
(HOT)
M9043
(HOT)
M9047
L2
1
L1
L2
1
2
S87B CONTROL MODULE
24V (GND)
24V
TEMPERATURE
CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
2
3
MAXIMUM IGNITER-SENSOR CABLE LENGTH: 3 ft. (0.9 m) OR LESS.
4
3A REPLACEABLE FUSE.
ALARM TERMINAL PROVIDED ON SOME MODELS.
5
Fig. 7. Typical wiring connections for 24 volt control
DUAL VALVE
COMBINATION
GAS CONTROL
THERMOSTAT
OR CONTROLLER
in S87 Direct Ignition System.
MV
MV
BURNER
GROUND
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED. MAKE SURE L1 AND L2 ARE NOT
REVERSED; THIS WOULD PREVENT FLAME DETECTION.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.
3
Fig. 8. typical wiring connections with 24 volt
control in S89 Direct Ignition System.
5
ALARM
VALVE
VALVE
GND
4
IGNITER-SENSOR AND
BURNER GROUND
3
S89C,G,J/S890C,G,J
HOT SURFACE
IGNITION CONTROL
VALVE
VALVE (GND)
24V
TH-W
24V (GND)
GND (BURNER)
VENT
DAMPER PLUG
2
SEN
3
L2
HSI
L1
HSI
ALARM, IF USED
DUAL VALVE
COMBINATION
GAS CONTROL
Q347 IGNITER-SENSOR
WHITE
BLUE
BLACK
BLUE
STARTUP AND CHECKOUT
WARNING
Fire or Explosion Hazard,
Can cause severe injury, death or property
damage.
1. Do not force the gas control knob on the
appliance. Use only your hand to turn the gas
control knob. Never use any tools.
2. If the knob does not operate by hand, the
control should be replaced by a qualified
service technician.
Gas Control Knob Settings
Gas control knob settings are as follows:
• OFF: Prevents pilot and main gas flow through the
control.
• ON: Permits gas to flow into the control body. Under
control of the thermostat and direct ignition module,
gas can flow to the main burner.
NOTE: Controls are shipped with the gas control knob in
the ON position.
Perform Gas Leak Test
WARNING
Fire or Explosion Hazard,
Can cause severe injury, death or property
damage.
Perform Gas Leak Test every time work is done on
a gas system to prevent gas leaks and possible
explosion or fire.
Gas Leak Test
1. Paint pipe connections upstream of the gas control
with rich soap and water solution. Bubbles indicate
a gas leak.
2. If a leak is detected, tighten the pipe connections.
3. Light the main burner. Stand clear of the main
burner while lighting to prevent injury caused from
hidden leaks that could cause flashback in the
appliance vestibule.
4. With the main burner in operation, paint the pipe
joints (including adapters) and the control inlet and
outlet with rich soap and water solution.
5. If another leak is detected, tighten the adapter
screws, joints, and pipe connections.
6. Replace the part if the leak cannot be stopped.
Turn On System
Rotate the gas control knob counterclockwise to
ON.
Turn On Main Burner.
Follow appliance manufacturer instructions or turn
thermostat up to call for heat.
769-1226—3
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
Check and Adjust Gas Input and Burner
Ignition
IMPORTANT
1. Do not exceed input rating stamped on
appliance nameplate, or manufacturer
recommended burner orifice pressure for size
orifice(s) used. Make certain primary air supply
to main burner is properly adjusted for complete
combustion. Follow appliance manufacturer
instructions.
2. IF CHECKING GAS INPUT BY CLOCKING GAS
METER: Make certain there is no gas flow
through the meter other than to the appliance
being checked. Other appliances must remain
off with the pilots extinguished (or deduct their
consumption from the meter reading). Convert
flow rate to Btuh as described in form 70-2602,
Gas Controls Handbook, and compare to Btuh
input rating on appliance nameplate.
3. IF CHECKING GAS INPUT WITH
MANOMETER: Make sure the gas control is in
the OFF position before removing outlet
pressure tap plug to connect manometer
(pressure gauge). Also, move the gas control
knob back to the OFF position when removing
the gauge and replacing the plug. Before
removing inlet pressure tap plug, shut off gas
supply at the manual valve in the gas piping to
the appliance or, for LP, at the tank. Also, shut off
gas supply before disconnecting manometer and
replacing plug. Repeat Gas Leak Test at plug
with main burner operating.
NOTE: Check the inlet pressure before adjusting the
pressure regulator.
Standard and Slow-Opening (H,K and M) Models
1. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lighted.
2. Check the full rate manifold pressure listed on the
appliance nameplate. Gas control full rate outlet
pressure should match this rating.
3. With the main burner operating, check the control
flow rate using the meter clocking method or check
pressure using a manometer connected to the outlet pressure tap on the control. See Fig. 6.
4. If necessary, adjust the pressure regulator to match
the appliance rating. See Tables 7A and 7B for
factory-set nominal outlet pressure and adjustment
range.
a. Remove the pressure regulator adjustment cap
screw.
b. Using a screwdriver, turn the inner adjustment
screw (Fig. 6) clockwise to increase or
counterclockwise to decrease the gas
pressure to the burner.
c. Always replace the cap screw and tighten firmly
to prevent gas leakage.
5. If the desired outlet pressure or flow rate cannot be
achieved by adjusting the gas control, check the
gas control inlet pressure using a manometer at the
inlet pressure tap of the gas control. If the inlet
pressure is in the nominal range (see Tables 7A and
7B), replace the gas control. Otherwise, take the
necessary steps to provide proper gas pressure to
the control.
NOTE: If the burner firing rate is above 150,000 Btuh on
VR8305 models (see Table 1 for VR8305
capacities), it may not be possible to deliver the
desired outlet pressure. This is an application
issue, not a control failure. Take whatever steps
are required to correct the situation.
Step-Opening (P) Models
Step-opening models require that you check and adjust
the full-rate pressure first and then check the step
pressure. The step pressure is not field-adjustable.
1. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lighted.
2. Check the full rate manifold pressure listed on the
appliance nameplate. Gas control full rate outlet
pressure should match this rating.
3. With main burner operating, check the gas control
flow rate using the meter clocking method or check
pressure using a manometer connected to the
outlet pressure tap on the gas control. See Fig. 6.
4. If necessary, adjust the pressure regulator to match
the appliance rating. See Tables 8 and 9 for factoryset nominal outlet pressure and adjustment range.
a. Remove the pressure regulator adjustment cap
screw.
b. Using a screwdriver, turn the inner adjustment
screw (Fig. 6) clockwise to increase or
counterclockwise to decrease the gas
pressure to the burner.
c. Always replace the cap screw and tighten firmly
to prevent gas leakage.
5. If the desired outlet pressure or flow rate cannot be
achieved by adjusting the gas control, check the
gas control inlet pressure using a manometer at the
inlet pressure tap of the control. If the inlet pressure
is in the nominal range (see Tables 8 and 9),
replace the control. Otherwise, take the necessary
steps to provide proper gas pressure to the control.
6. Carefully check the burner lightoff at step pressure.
Make sure the burner lights smoothly and without
flashback to the orifice. Make sure all ports remain
lighted. Cycle the burner several times, allowing at
least 60 seconds between cycles for the regulator
to resume the step function. Repeat after allowing
the burner to cool. Readjust the full rate outlet
pressure, if necessary, to improve lightoff
characteristics.
Two-Stage (Q) Models
Two-stage models require that you check and adjust both
high and low pressure regulator settings. Two-stage
appliances operating sequences vary. Consult the
appliance manufacturer instructions for the specific
operating sequence and regulator adjustment procedure
for the appliance in which the control was installed.
1. Set appliance to operate on high.
2. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lighted.
3. Check the full rate (high) manifold pressure listed
on the appliance nameplate for high pressure. The
gas control full rate outlet pressure should match
this rating.
4. With main burner operating, check the gas control
flow rate using the meter clocking method or check
pressure using a manometer connected to the
outlet pressure tap on the gas control. See Fig. 6.
69-1226—38
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
5. If necessary, adjust the high pressure regulator to
match the appliance rating. See Tables 8 and 9 for
factory-set nominal outlet pressure and adjustment
range.
a. Remove the pressure regulator adjustment cap
(Fig. 6).
b. Using a screwdriver, turn the inner adjustment
screw for HI pressure clockwise to
increase or counterclockwise to decrease
the gas pressure to the burner.
6. After high pressure has been checked, check low
pressure regulation. Two-stage appliance operating
sequences vary. Consult the appliance
manufacturer instructions for the specific operating
sequence and regulator adjustment procedure for
the appliance in which the control is installed and
for instructions on how to prevent the control from
moving to high stage while checking the low
pressure regulator setting.
7. check the low rate manifold pressure listed on the
appliance nameplate. Gas control low rate outlet
pressure should match this rating.
8. With main burner operating, check the gas control
flow rate as before (using the meter clocking
method or check pressure using a manometer
connected to the outlet pressure tap on the control).
9. If necessary, adjust the low pressure regulator to
match the appliance rating. See Tables 8 and 9 for
factory-set nominal outlet pressure and adjustment
range.
a. Remove the pressure regulator adjustment cap
(Fig. 6).
b. Using a screwdriver, turn the inner adjustment
screw for LO pressure clockwise to
increase or counterclockwise to
decrease the gas pressure to the burner.
and adjusted, replace pressure regulator
adjustment cap. If the desired outlet pressure or
flow rate cannot be achieved by adjusting the gas
control, check the control inlet pressure using a
manometer at the inlet pressure tap of the control. If
the inlet pressure is in the nominal range (see
Tables 8 and 9), replace the gas control. Otherwise,
take the necessary steps to provide proper gas
pressure to the control.
Check Safety Lockout (Slow-Opening
Controls Only)
1. With the system power off and the thermostat set to
call for heat, manually shut off the gas supply.
2. Energize ignition control and start timing safety
lockout time. When spark ignition terminates, stop
timing.
NOTE: When using the VR8105H, VR8205H, and
VR8305H step-opening control, the specified
ignition control safety lockout time must exceed
8.5 seconds for the system to function properly.
3. After spark cutoff, manually reopen the gas control
knob. No gas should flow to the main burner.
4. Reset the system by adjusting the thermostat below
room temperature, wait 30 seconds, and then move
the thermostat setting up to call for heat. Normal
ignition should occur.
Factory-Set Nominal Outlet
PressureSetting Range
StepFull RateStepFull Rate
3.5 High
10.0 High
PressureSetting Range
StepFull RateStepFull Rate
0.90 High
2.5 High
—
—2.5 - 7.0 Low
—
—0.6 - 1.8 Low
0.9 - 3.0 Low
3.0 - 5.0 High
8.0 - 11.0 High
0.22 - 0.75 Low
0.75 - 1.2 High
2.0 - 2.5 High
a
a
969-1226—3
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
Check Safety Shutdown Performance
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Perform the safety shutdown test any time work is
done on a gas system.
NOTE: Read steps 1 through 7 before starting, and
compare to the safety shutdown or safety
lockout tests recommended for the direct ignition
(DI) module. When different, use the procedures
recommended for the module.
1. Turn off the gas supply.
2. Set thermostat or controller above room tempera-
ture to call for heat.
3. Watch for ignition spark or glow at hot surface
igniter either immediately or following prepurge.
See DI module specifications.
4. Time the length of spark operation. See the DI
module specifications.
5. After the module locks out, open the manual gas
cock and make sure no gas is flowing to the main
burner.
6. Set the thermostat below room temperature and
wait one minute.
7. Operate system through one complete cycle to
make sure all controls operate properly.
MAINTENANCE
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Do not disassemble the gas control; it contains no
replaceable components. Attempted disassembly,
repair, or cleaning can damage the control,
resulting in gas leakage.
Regular preventive maintenance is important in
applications in the commercial cooking and agricultural
and industrial industries that place a heavy load on
system controls, because:
• In many such applications, particularly commercial
cooking, the equipment operates 100,000 to 200,000
cycles per year. Such heavy cycling can wear out the
gas control in one to two years.
• Exposure to water, dirt, chemicals and heat can
damage the gas control and shut down the control
system.
The maintenance program should include regular
checkout of the control as outlined in the Startup and
Checkout section, and the control system as described in
the appliance manufacturer literature.
Maintenance frequency must be determined individually
for each application. Some considerations are:
• Cycling frequency. Appliances that cycle 20,000 times
annually should be checked monthly.
• Intermittent use. Appliances that are used seasonally
should be checked before shutdown and again before
the next use.
• Consequence of unexpected shutdown. Where the
cost of an unexpected shutdown would be high, the
system should be checked more often.
• Dusty, wet or corrosive environments. Since these
environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.
The system should be replaced if:
• It does not perform properly on checkout or
troubleshooting.
• The gas control is likely to have operated for more than
200,000 cycles.
• The control is wet or looks as if it has been wet.
SERVICE
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Do not disassemble the gas control; it contains no
replaceable components. Attempted disassembly,
repair, or cleaning can damage the control,
resulting in gas leakage.
CAUTION
Equipment Damage.
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
After servicing, verify proper system operation.
If Main Burner Does Not Come On With
Call For Heat
1. Confirm the gas control knob is in the ON position.
2. Adjust thermostat several degrees above room
temperature.
3. Using ac voltmeter, measure across MV terminals
at gas control.
4. If voltage is incorrect or not present, check control
circuit for proper operation.
5. If proper voltage is present, replace gas control.
69-1226—310
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
INSTRUCTIONS TO THE
HOMEOWNER
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow these warnings exactly:
1. Before lighting, smell around the appliance for
gas. Be sure to smell next to floor because LP
gas is heavier than air. If you smell gas:
(a) Turn off the gas supply at the appliance
service valve. On LP gas systems, turn off
the gas supply at the gas tank.
(b) Do not light any appliance in the house.
(c) Do not touch electrical switches or use the
telephone.
(d) Leave the building and use a neighbor’s
phone to call your gas supplier.
(e) If you cannot reach your gas supplier, call
the fire department.
2. Replace the gas control in the event of any
physical damage, tampering, bent terminals,
missing or broken parts, stripped threads, or
evidence of exposure to heat.
IMPORTANT:
Follow the operating instructions provided by the
heating appliance manufacturer. The information
below describes a typical control application, but
the specific controls used and the procedures
outlined in your appliance manufacturer
instructions can differ, requiring special
instructions.
To Turn ON Appliance
STOP: Read the Warnings Above Before
Proceeding
1. The lighting sequence on this appliance is
automatic; do not attempt to manually light the main
burner.
2. If the furnace does not come on when the
thermostat is set several degrees above room
temperature, set the thermostat to its lowest setting
to reset the safety control.
3. Remove the burner access panel, if provided, on
your appliance.
4. Turn the gas control knob clockwise to OFF.
5. Wait five minutes to allow any gas in the
combustion chamber to vent. Then, if you smell
gas, STOP! Follow Step 1 in the Warning above. If
you do not smell gas, continue with the next step.
6. If you do not smell gas, turn the knob on the gas
control counterclockwise to ON.
7. Replace the burner access panel.
8. Reset the thermostat to the desired temperature.
9. If the appliance does not turn on, turn the gas
control knob to OFF and contact a qualified service
technician for assistance.
Turning Off the Appliance
Vacation Shutdown
Set the thermostat to the desired room temperature while
you are away.
Complete Shutdown
1. Turn off the power to the appliance.
2. Turn off the gas supply to the appliance.
3. Turn gas control knob clockwise to OFF.
Appliance will completely shut off.
Follow the procedures in the Instructions to the Homeowner section above to resume normal operation.
1169-1226—3
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North35 Dynamic Drive
Golden Valley, MN 55422Scarborough, Ontario M1V 4Z9