AbsolutAire MS-221 Installation Manual

DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. Box 373 • Michigan City, IN 46361-0373, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
The Series MS Magnesense®Differential Pressure Transmitter is an extremely versatile transmitter for monitoring
pressure and air velocity. This compact package is loaded with features such as: field selectable English or metric ranges, field upgradeable LCD display, adjustable dampening of output sig­nal (with optional display) and the ability to select a square root output for use with Pitot tubes and other similar flow sensors. Along with these features, magnetic sensing technology pro­vides exceptional long term performance and enables the Magnesense
®
to be the solution for a myriad of pressure and
air flow applications.
INSTALLATION Mounting:
The transmitter should be mounted on a vertical surface with the connections directed down to prevent moisture fr om enter­ing either the pressure ports or the electrical cable entry. The diaphragm must be vertical to minimize gravity effects on the diaphragm. Mount the transmitter using #8 x 1/2˝ pan head sheet metal screws in the mounting flanges. Do not over tighten.
Duct Mount:
The transmitter should be mounted away from fans, corners, heating and cooling coils and other equipment that will effect the measurement of the pressure.
1. To mount the transmitter, drill a .562 (12.70) diameter hold into the duct.
2. Insert transmitter probe into the duct.
3. Mark location of three mounting holes on duct using mount­ing flange as template. Drill holes.
4. Attach mounting flange to duct with (3) #8 x 1/2 pan head sheet metal screws. Do not overtighten screws.
Electrical Connection: 2-Wire Operation:
CAUTION: DO NOT EXCEED SPECIFIED SUPPL Y VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT. 2-WIRE UNITS ARE NOT DESIGNED FOR AC VOLTAGE OPERATION.
Series MS Magnesense®Differential Pressure Transmitter
Specifications - Installation and Operating Instructions
Bulletin A-26
SPECIFICATIONS
Service: Air and non-combustible, compatible gases. Wetted Materials: Consult Factory. Accuracy: ±1% for 0.25” (50 Pa), 0.5” (100 Pa), 2” (500 Pa), 5”
(1250 Pa), ±2% for 0.1” (25 Pa), 1” (250 Pa) and all bi-directional ranges.
Stability: ±1% F.S./ year. Temperature Limits: 0 to 150°F (-18 to 66°C). Pressure Limits: 1 psi maximum, operation; 10 psi, burst. Power Requirements: 2-wire, 10 to 35 VDC; 3-wire, 17 to
36 VDC or isolated 21.6 to 33 VAC.
Output Signals: 2-wire, 4 to 20 mA or 3-wire, 0 to 10 V. Response Time: Adjustable 0.5 to 15 sec. time constant.
Provides a 95% response time of 1.5 to 45 seconds.
Zero & Span Adjustments: Digital push button. Loop Resistance: Current Output: 0-1250 Ohm max. Voltage
Output: min. load resistance 1 k OhmΩ.
Current Consumption: 40 mA max. Display (optional): 4 digit LCD. Electrical Connections: 4-20 mA Units: 2-Wire: European Style
Terminal Block for 16 to 26 AWG; 0-10 V Units: 3-Wire: European Style Terminal Block 16 to 22 AWG. Electrical Entry: 1/2˝ NPS Thread.
Accessory: Cable Gland for 5 to 10 mm diameter cable. Process Connections: 3/16˝ (5 mm) ID tubing. Maximum OD 9 mm.
Enclosure Rating: NEMA 4X (IP65). Mounting Orientation: Diaphragm in vertical position. Weight: 8.0 oz (230 g). Agency Approvals: CE.
The following standards were used for CE approval:
CENELEC EN 61000-4-2: 2001 CENELEC EN 61000-4-3: 2002 CENELEC EN 61000-4-4: 1995 CENELEC EN 61000-4-5: 2001 CENELEC EN 61000-4-6: 2003 CENELEC EN 61000-4-8: 2001 CENELEC EN 55011: 2003 CENELEC EN 61326: 2002 89/336/EED EMC Directive
2-41/64 (67.07)
2-11/64 (55.17)
2-9/16
(65.09)
21/32
(16/67)
8-1/8
(206.38)
21/32
(16/67)
29/32
(12.70)
(23.02)
57/64
(22.62)
(3) 3/16 (4.76) HOLES EQUALLY SPACED ON A
4.115 (104.52) BC
Ø35/84 (13.87)
1/2
Ø3-7/16
(Ø87.31)
1/2 NPT
Electrical Connection: 2-Wire Operation, continued:
The connections to the transmitter are made through a two circuit European style terminal block TB1 located at the bottom left of the main PB board. Polarity is indicated by + and – signs on the P.C. board.
Figure 1
An external power supply delivering 10 to 35 VDC with a minimum current capability of 40 milliamps must be used to power the con­trol loop in which the Magnesense
®
transmitter is connected. Refer to Fig. 1 for connection of the power supply , transmitter and receiv­er. The range of appropriate receiver load resistances (R
L
) for the
power supply voltage available is given by the formula and graph in Fig. 2. Shielded two wire cable is recommended for control loop wiring and the negative side of the loop may be grounded if desired. Note also that the receiver may be connected in either the negative or positive side of the loop, whichever is most convenient. Should polarity of the transmitter or receiver be inadvertently reversed, the loop will not function properly but no damage will be done to the transmitter
.Figure 2
The maximum length of connecting wire between the transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 feet), it is desirable to select receivers with higher resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 feet, connecting lead wire as small as No. 22 Ga. can be used.
3-Wire Operation:
CAUTION: DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.
The connections to the transmitter are made through a three cir­cuit European style terminal block. Connect the power and signal leads to the corresponding terminals as shown in Fig. 3. When using a DC supply, the positive of the supply should be connected
to V+ and the negative connected to Com. Connecting the leads in reverse will not damage the device but it will not operate. The DC supply should be capable of providing 20 mA or more of current per Magnesense
®
transmitter.
When using an isolated AC supply, either leads of the supply may be connected to Com and V+. The input diode of the device half wave rectifies and filters the applied AC voltage. A small DC cur­rent of less than 20 mA is thus drawn through the transformer. The transformer used for the AC supply must be capable of handling this small DC current. Use a UL 1584 Class 2 rated transformer rated between 24 V and 30 VAC, 40 VA or larger, 50/60 Hz. UL 1584 Class 2 rated transformers are limited to 30 VAC maximum under any conditions at nominal line. The AC input voltage to the device is thus limited to a minimum of 21.6 at low line (24 V-10%) and 33 V at high line (30 V+10%).
Figure 3
The output of Vo is 0 to 10 VDC. As much as 10 mA may be drawn from Vo without affecting accuracy. This limits the minimum load
RL connected to Vo to 1 KΩ or higher. Remember to keep the wiring resistance between the output and the receiver R
L
low com­pared to value of RL. While the voltage at the terminals remains unchanged with a 10 mA current flow, resistive losses in the wiring
do cause errors in the voltage delivered to RL. For a 1% accurate gauge, a good rule of thumb would be to keep the resistance of
the leads less than 0.1% of the value of RL. This will keep the error caused by current flow below 0.1%.
To minimize noise in the signal use shielded cable. The common line may also be grounded.
Pressure Connections
Two integral tubing connectors are provided. They are designed to fit 3/16˝ (5 mm) ID tubing. Connect the high pressure to the High side as shown in Fig. 4. Be sure the pressure ratings of the tubing exceed that of the operating ranges.
Figure 4
Select Operation Mode and Range:
The operating modes and ranges are controlled by two shorting jumpers on a pair of jumper blocks, PJ3 and PJ5. These two jumper blocks are shown in Fig. 5.
Bulletin A-26
Page 2
TOTAL RECEIVER RESISTANCE ( )
– +
1500 1400 1300 1200 1100 1000
900 800 700 600 500 400 300 200 100
50
TB1
5101315
0
+
POWER SUPPLY 10-35V
RL MAX =
RECEIVER
L
R
MAXIMUM VALUE (1250 )
V
ps - 10.0
20mA DC
OPERATING
REGION
20 25 30 35 40
POWER SUPPLY VOLTAGE
TB1
V+ Vo
COM
RECEIVER
L
R
POWER SUPPLY
17 TO 36 VDC
OR
21.6 TO 33 VAC
PJ1 PJ2
PJ1
PJ2
LOW
SW1 SW2
TB1
HIGH
Loading...
+ 2 hidden pages