AbsolutAire MEP304 Installation Manual

®
MP-5301
OCTOBER 2003
MEP300, MEP304 and MEP397
PROGRAMMER MODULES
DESCRIPTION
U
C
LISTED
The Fireye MEP300, MEP304, and MEP397 Programmer Modules are used with the Fireye Modular MicroM control. The MEP300 series programmers provide additional enhancements such as early spark termination, pilot proving and interrupted or intermittent pilot operation. These programmers must be used with the MEC320 and MEC480 series chassis. The programmer module incorporates a plug-in design for easy installation.
Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module. Test jacks are also provided on the flame amplifier module to permit flame signal measurement during operation. For proper and safe application of this product, you must refer to Fireye bulletin MC-5000 for a detailed description of the various programmer modules, including installation instructions, amplifier selection, operating sequences for each programmer module, etc.
WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government agency. Inappropriate application of this product could result in an unsafe condition hazardous to life and pr operty . Installation should not be considered complete until pilot turndown and other appropriate performance tests have been successfully completed.
US
L
£
APPROVED
FOR USE WITH THE FIREYE® MODULAR
MicroM™ CONTROL TO BE USED
PROGRAMMER MODULE SELECTION
MicroM Programmer Models (For use with MEC320 and MEC480 Chassis)
MEP300 Relight operation, 10 sec. fixed PTFI, 5 second pilot proving period, 5 second MTFI. lockout on flame fail during
PTFI, pilot proving and MTFI. Recycle on air flow open. No post purge. Reset on line voltage.
MEP304 Non-recycle on flame fail, 5 second purge, 10 second fixed PTFI, 5 second pilot proving, 10 second MTFI, inter-
rupted pilot, early spark termination.
MEP397 Recycle on main flame fail, 15 second purge, 7 second fixed PTFI, 5 second pilot proving 5 second MTFI, early spark
termination and interrupted pilot. Recycle on air flow failure. No post purge, run/check switch. Reset on line voltage.
1
INSTALLATION
LOCKOUT CODES
£
WARNING: Remove power from the control and remove the control from its wiring base before proceeding.
The Programmer Modules are used with the Fireye modular MicroM Chassis (P/N MEC320, MEC320RC, MEC320R, MEC320D and MEC320C for 120VAC and
The programmer mod­ules are designed to fit into the proper slot only.
MEC480 for 230 VAC). They are installed in the chassis by grabbing hold of the program­mer module by the ridged finger grips on the side on the module, aligning the module with the guide slots on the opening farthest from the transformer, and inserting the module into the pin connectors.
MSGN DESCRIPTION OP CTRL
DEC HEX
6 6 Lockout Line Frequency Noise Detected ●❍❍●✱
7 7 Lockout Flame Fail - PTFI ❍● ●●✱
15 0F Lockout Fault Unknown ●●●●✱
16 10 Lockout Amplifier High Count Fail ❍❍❍❍✱
19 13 Lockout Flame Fail - MTFI ❍❍●●✱
20 14 Lockout False Flame - STANDBY ❍●❍❍✱
21 15 Lockout Intrlck Open ●●●❍✱
22 16 Lockout Intrlck Closed ❍● ●❍✱
24 18 Lockout Chassis Opto ●●❍●✱
37 25 Lockout Flame Fail - AUTO ❍●❍●✱
39 27 Lockout Fuel Valve State Change ❍❍❍●✱
54 36 Lockout Check Chassis ❍❍❍●✱
55 37 Lockout Check Programmer ❍❍ ●❍✱
56 38 Lockout Check Amplifier ●❍❍❍✱
58 3A Lockout Amplifier Auto Check Fail ●❍●❍✱
59 3B Lockout Check BLOWN FUSE ●❍ ●●✱
76 4C Lockout Check Scanner ●●❍❍✱
= NOT LIGHTED
= LIGHTED= FLASHING
All MicroM chassis are shipped with a convenient peel off label that can be applied to any surface (inside cover) for future reference.
AIRFLOW
INTLCK
PTFI FLAME ALARM
FIREYE MP-5301
£