Air Handling Systems
Description
inacoustic RC is a flexible duct liner insulation made from
L
strong, glass fibers bonded with a thermosetting resin. The
airstream surface is protected with JM’s exclusive Reinforced
oating System, which combines our state-of-the-art
C
Permacote
®
acrylic coating with a flexible glass cloth
reinforcement.
Factory-Applied Edge Coating
Edge coating is factory applied to the edges of the liner core,
assuring coverage of the leading edges per NAIMA/SMACNA
requirements. Shop fabrication cuts may be coated with the
SuperSeal
®
Duct Butter and Edge Treatment products (refer to
publication AHS-202).
Uses
Linacoustic RC is specifically designed for lining sheet metal
ducts in air conditioning, heating and ventilating systems,
providing superior acoustical and thermal performance.
Advantages
Improves Indoor Building Environment.
Linacoustic RC improves
indoor environmental quality by helping to control both
temperature and sound.
Resistant to Dust and Dirt. The tough, acrylic polymer Permacote
coating helps guard against the incursion of dust or dirt into the
substrate, minimizing the potential for biological growth.
Will Not Support Microbial Growth. Permacote coating is
formulated with an immobilized, EPA-registered, protective
agent to protect the coating from potential growth of fungus
and bacteria.
Linacoustic RC duct liner meets all requirements of ASTM C 1071
for fungi and bacterial resistance. Tests were conducted in
accordance with ASTM C 1338 and ASTM G 21 (fungi testing)
and ASTM G 22 (bacteria resistance testing). Detailed
information is available in Johns Manville fact sheet HSE-103FS.
Note: As with any type of surface, microbial growth may occur in
accumulated duct system dirt, given certain conditions. This risk
is minimized with proper design, filtration, maintenance and
operation of the HVAC system.
GREENGUARD®. This certification is proof that the product meets
the Environmental Institute’s indoor air quality standards for
VOCs.
Cleanability. If HVAC system cleaning is required,
the Reinforced Coating airstream surface may be
cleaned with industry-recognized dry methods. See the North
American Insulation Manufacturers Association (NAIMA)
“Cleaning Fibrous Glass Insulated Air Duct Systems.”
Minimizes Pre-Installation Damage. Linacoustic RC’s
Reinforced Coating System is highly resistant to damage that
can occur during in-shop handling, fabrication, jobsite shipping,
and installation.
Linacoustic RC
™
Fiber Glass Duct Liner With Reinforced Coating System
Highly Resistant to Water. The Reinforced Coating surface
provides superior resistance to penetration of incidental water
into the fiber glass wool core.
Easy to Fabricate. Linacoustic RC is light in weight and easy to
handle. Clean, even edges can be accurately cut with regular
shop tools.
Available Forms
Thickness (in) (mm)
Roll Width* (in) (mm)
Roll Length**
*Available in1⁄4" (6.4 mm) increments. **Check with plant for availability.
Performance Limits
Maximum Air Velocity
Maximum Operating Temperature 250°F (121°C)
Water Repellency
Per Cent Mass Gain (JM 436-1006) 6.2% (avg.)
INDA IST 80.6-92 ≥ 6
Installation
Linacoustic RC installation must be performed in accordance
with the requirements of the NAIMA Fibrous Glass Duct Liner
Standard, or SMACNA HVAC Duct Construction Standard. All
transverse edges, or any edges exposed to airflow, must be
coated with an approved duct liner coating material, such as
Johns Manville SuperSeal
1
2
/
125
1
2
/
1
13
38
251
34 to 36 8864 to 8914
44 to 48 1118 to 1219
56 to 60 1422 to 1524
66 to 72 1676 to 1829
(lineal feet) (lineal meters)
50
15
100 31
150 46
200 61
6,000 fpm (30.5 m/sec).
®
products.
AHS-329 6-05 (Replaces 2-05)
Specification Data
Linacoustic RC Fiber Glass Duct Liner With Reinforced Coating System
Thermal Performance
Thickness R-Value Conductance
(in) (mm) (hr•ft2•°F)/Btu m2•°C/W Btu/(hr•ft2•°F) W/m2•°C
1
/213 2.2 0.38 .46 2.61
25 4.2 0.74 .24 1.36
1
1
1
/238 6.3 1.11 .16 0.91
2 51 8.0 1.41 .13 0.74
R-Value and Conductance are calculated from the material thermal conductivity tested in
accordance with ASTM C 518 at 75°F (24°C) mean temperature.
Sound Absorption Coefficients (Type “A” Mounting)
Sound Absorption Coefficient at Frequency
Thickness (Cycles per Second) of
(in) (mm) 125 250 500 1000 2000 4000 NRC
1
/213 0.07 0.20 0.44 0.66 0.84 0.93 0.55
1 25 0.08 0.31 0.64 0.84 0.97 1.03 0.70
1
1
/238 0.10 0.47 0.85 1.01 1.02 0.99 0.85
2 51 0.25 0.66 1.00 1.05 1.02 1.01 0.95
Coefficients were tested in accordance with Test Method ASTM C 423-90 and ASTM E 795.
ISO 9000 Certification
Johns Manville mechanical insulation products are designed,
manufactured and tested in our own facilities, which are certified and
registered to stringent ISO 9000 (ANSI/ASQC 90) series quality standards.
This certification, along with regular, independent third-party auditing for
compliance, is your assurance that Johns Manville products deliver
consistent high quality.
Surface Burning Characteristics
Flame Spread not over 25
Smoke Developed not over 50
Per UL 723, ASTM E 84 and CAN/ULC S102-M88 test methods.
If UL labels are required, they may be requested at time of order.
Specification Compliance
• ASTM C 1071, Type I, Flexible (Replaced
HH-I-545B and NAIMA AHC 101)
• ASTM G 21 and G 22
• ICC Compliant
• California Title 24
• SMACNA Application Standards for
Duct Liners
• NAIMA Fibrous Glass Duct Liner
Installation Standard
• NFPA 90A and 90B, FHC 25/50 and
Limited Combustibility
• Conforms to ASHRAE 62-2001
• Canada: CGSB 51-GP-11M
CAN/ULC S102-M88
Performance Materials Division
.O. Box 5108
P
Denver, CO 80217-5108
Product Information: (800) 654-3103
www.jm.com/ahs
AHS-329 6-05 (Replaces 2-05)
North American Sales Offices, Performance Materials Division
Eastern Region Western Region Outside
P.O. Box 158 and Canada North America
Defiance, OH 43512
P.O. Box 5108 (303) 978-2939
(800) 334-2399 Denver, CO 80217 Fax: (303) 978-2627
Fax: (419) 784-7866 (800) 368-4431
Fax: (303) 978-4661
The physical and chemical properties of Linacoustic RC™Fiber Glass Duct Liner with Reinforced
Coating System represent typical, average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. They are supplied as a technical
service and are subject to change without notice. Numerical flame spread and smoke
developed ratings are not intended to reflect hazards presented by these or any other materials
under actual fire conditions. Check with the Regional Sales Office nearest you to assure current
information. All Johns Manville products are sold subject to Johns Manville’s Limited Warranty
and Limitation of Remedy
Remedy, call the 800 number below. For information on other Johns Manville thermal insulations
and systems and a copy of the Spec-Line®CSI formatted specifications, call (800) 654-3103.
. For a copy of the Johns Manville Limited Warranty and Limitation of
Copyright © 2005 Johns Manville
Printed in USA