Product Description
Pressure Switch, Auto Reset
The L02-04-0107 series differential pressure switch is a general
purpose proving switch designed to require a manual operator reset following actuation. This pressure switch can be used to sense
positive, negative, or differential air pressure in HVAC and Energy
Management applications which require operator interface.
.
The L02-04-0107
12.0" w.c. The
of 0.05" +/- 0.02" to 12" w.c. with a field adjustable release range
of 0.04" to 11.2" of w.c.. Each unit contains a diaghram, calibration spring, and a snap-acting SPDT switch.
The sampling connections are located on each side of the
diaghram. The
tubing via the integral compression ferrule and nut. The enclosure
cover guards against accidental contact with the live switch terminal screws and the set point adjusting screw. The
contains a 1/2" conduit knockout in the cover of the enclosure.
has a field adjustable operating range of 0.05" to
L02-04-0107
L02-04-0107
has a field adjustable set point range
will accept a 0.25" O.D. rigid metallic
L02-04-0107
also
Features and Application Highlights
The L02-04-0107 differential pressure switch may be used in many different applications including:
Monitoring non-critical equipment for alerts to maintenance
•
Clogged filter switch
•
Technical Data
Input Pressure Range
Electrical Rating
Output
Maximum Pressure
Switch Differential
Set Point
Measured Media
Operating Temperature
Mounting Direction
Field Wiring
Approval
Shipping Weight
Lynxspring, Inc. 8900 State Line Road, Suite 220, Leawood, KS 66206 877-649-5969
• 0.05” +/- 0.02” to 12” w.c.
• 300VA pilot duty @ 115 to 277 VAC
15 amps non-inductive to 277 VAC, 60 Hz
• 1 set SPDT contacts (Auto Reset)
• 0.5 PSI
• increasing from 0.01” w.c. at minimum
• +0.08” w.c. @ maximum set point
• Air or combustion by-products that will not degrade silicon
• -40˚F to 180˚F (-40˚C to 82.2˚C)
• Any vertical plane
• Wire to be rated to 90˚C; user copper conductors only
• UL, CSA, FM, CE
• 1.2 lbs
Please contact Lynxspring for more information about this product
Device Detail
Pressure Switch, Auto Reset
Ordering Information
Model # Description
L02-04-0107 .05 to 12” Differential Pressure Switch (Auto Reset)
Accessory Items Description
VPT Total Pressure Pitot Tube
SPT Static Pressure Pitot Tube
Lynxspring, Inc. 8900 State Line Road, Suite 220, Leawood, KS 66206 877-649-5969