AbsolutAire L02-04-0107 User Manual

L02
-04-
010
7 – Differential
Product Description
Pressure Switch, Auto Reset
The L02-04-0107 series differential pressure switch is a general purpose proving switch designed to require a manual operator re­set following actuation. This pressure switch can be used to sense positive, negative, or differential air pressure in HVAC and Energy Management applications which require operator interface. .
The L02-04-0107
12.0" w.c. The of 0.05" +/- 0.02" to 12" w.c. with a field adjustable release range of 0.04" to 11.2" of w.c.. Each unit contains a diaghram, calibra­tion spring, and a snap-acting SPDT switch.
The sampling connections are located on each side of the diaghram. The tubing via the integral compression ferrule and nut. The enclosure cover guards against accidental contact with the live switch termi­nal screws and the set point adjusting screw. The contains a 1/2" conduit knockout in the cover of the enclosure.
has a field adjustable operating range of 0.05" to
L02-04-0107
L02-04-0107
has a field adjustable set point range
will accept a 0.25" O.D. rigid metallic
L02-04-0107
also
Features and Application Highlights
The L02-04-0107 differential pressure switch may be used in many different applications including:
Monitoring non-critical equipment for alerts to maintenance
Clogged filter switch
Technical Data
Input Pressure Range Electrical Rating
Output Maximum Pressure Switch Differential Set Point Measured Media Operating Temperature Mounting Direction Field Wiring Approval Shipping Weight
Lynxspring, Inc. 8900 State Line Road, Suite 220, Leawood, KS 66206 877-649-5969
0.05” +/- 0.02” to 12” w.c.
300VA pilot duty @ 115 to 277 VAC
15 amps non-inductive to 277 VAC, 60 Hz
1 set SPDT contacts (Auto Reset)
0.5 PSI
increasing from 0.01” w.c. at minimum
+0.08” w.c. @ maximum set point
Air or combustion by-products that will not degrade silicon
-40˚F to 180˚F (-40˚C to 82.2˚C)
Any vertical plane
Wire to be rated to 90˚C; user copper conductors only
UL, CSA, FM, CE
1.2 lbs
Please contact Lynxspring for more information about this product
L02
-04-
010
7 – Differential
Device Detail
Pressure Switch, Auto Reset
Ordering Information
Model # Description
L02-04-0107 .05 to 12” Differential Pressure Switch (Auto Reset)
Accessory Items Description
VPT Total Pressure Pitot Tube
SPT Static Pressure Pitot Tube
Lynxspring, Inc. 8900 State Line Road, Suite 220, Leawood, KS 66206 877-649-5969
Please contact Lynxspring for more information about this product
Loading...