ABB B6, VB6, VB6A, B7, VB7 Technical Data

...
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Main pole – Utilization characteristics according to IEC
Contactor types
Standards Rated operational voltage U
e max
Rated frequency (without derating) Conventional free-air thermal current l
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C, with conductor cross-sectional area
th
AC-1 Utilization category for air temperature close to contactor θ ≤ 40 °C
I
/ Rated operational current AC-1
e
U
≤ 690 V, 50/60 Hz
e max
AC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current AC-1
e
U
≤ 690 V, 50/60 Hz
e max
AC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C
Ie / Rated operational current AC-3 220 / 230 / 240 V
3-phase motors
M
M
3
3
Rated operational power AC-3
1500 r.p.m. 50 Hz 1800 r.p.m. 60 Hz 3-phase motors
M
M
3
3
DC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current DC-1 110 V
e
DC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current DC-3 110 V
e
DC-5 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current DC-5 110 V
e
Rated making capacity AC-3 Rated breaking capacity AC-3 Short-circuit protection device for contactors
without thermal O/L relay - motor protection excluded Ue ≤ 500 V AC - fuse type gG Type 1: 25 A / Type 2: 25 A
Rated short-time withstand current I
at 40 °C ambient temperature, in free air from a cold state
CW
Maximum breaking capacity cos ϕ = 0.45 Maximum electrical switching frequency
220-230-240 V
380-400 V
440 V
500 V 690 V
220-230-240 V
380-400 V
440 V
500 V 690 V
380 / 400 V
440 V 500 V 690 V
220-230-240 V
380-400 V
440 V 500 V 690 V
220 V
220 V
220 V
10 s
at 400 V
AC-1 AC-3
DC-1, DC-3, DC-5
B6, VB6, VB6A B7, VB7, VB7A BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
IEC/EN 60947-1, IEC/EN 60947-4-1 690 V AC DC or 50 / 60 Hz Screw terminal types: 20 A
Flat pin types: 20 A Soldering pin types: 12 A
Screw terminal types: 20 A Flat pin types: 20 A Soldering pin types: 12 A
Screw terminal types: 20 A Flat pin types: 20 A Soldering pin types: 12 A
Screw terminal types: 20 A Flat pin types: 20 A Soldering pin types: 12 A
12 A 6 A
Screw terminal types: 16 A Flat pin types: 16 A Soldering pin types: 12 A
Screw terminal types: 16 A Flat pin types: 16 A Soldering pin types: 12 A
Screw terminal types: 16 A Flat pin types: 16 A Soldering pin types: 12 A
12 A 6 A
8.9 / 8.5 / 8.1 A 11.8 / 11.3 / 10.8 A
8.9 / 8.5 A 12.1 / 11.5 A
7.4 A 10.1 A
6.8 A 9.2 A
3.8 A 3.8 A
2.2 kW 3 kW 4 kW 5.5 kW 4 kW 5.5 kW 4 kW 5.5 kW 3 kW 3 kW
- 4 A
- 0.6 A
- 1.5 A
- 0.25 A
- 0.4 A
- 0.2 A
10 x Ie AC-3 acc. to IEC 60947-4-1 8 x Ie AC-3 acc. to IEC 60947-4-1
64 A 64 A
96 A 96 A
300 cycles/h 600 cycles/h 600 cycles/h
3
ABB | 3/41
2CDC102043C0201
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Main pole – Utilization characteristics according to UL/NEMA/CSA
Contactor types
3
Standards Maximum operational voltage UL/CSA general use rating UL/CSA maximum 1-phase motor rating
Full load current
Horse power rating
UL/CSA maximum 3-phase motor rating
Full load current
Horse power rating
Resistive Heating Incandescent Lamps Fluorescent Lamps Short-circuit protection device for contactors
without thermal overload relay - motor protection excluded
Fuse rating Fuse type, 600 V
Maximum electrical switching frequency
For resitive loads AC-1 300 cycles/h For motor loads AC-3 600 cycles/h
1)
For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
1)
1)
120 V AC 240 V AC 120 V AC 240 V AC
200 / 208 V AC
220-240 V AC 440-480 V AC 550-600 V AC
200 / 208 V AC
220-240 V AC 440-480 V AC
550-600 V AC 300 V per pole 300 V per pole 300 V per pole
600 V 600 V
B6, VB6, VB6A B7, VB7, VB7A BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
UL 508, CSA C22.2 N°14 600 V 12 A / 300 V 16 A / 600 V
5.8 A 13.8 A
4.9 A 10.0 A
0.25 hp 0.75 hp
0.5 hp 1.5 hp
4.8 / 4.6 A 7.8 / 10.6 A
6.8 A 9.6 A
4.8 A 7.6 A
1.7 A 6.1 A 1 hp 2 / 3 hp 2 hp 3 hp 3 hp 5 hp 1 hp 5 hp
8 A 8 A 6 A 6 A
8.4 A 8.4 A
40 A Class J
General technical data
Contactor types
Rated insulation voltage U
acc. to IEC 60947-4-1 690 V acc. to UL/CSA 600 V
Rated impulse withstand voltage U Ambient air temperature, close to contactor
Operation Fitted with thermal overload relay -25 ... +50 °C
Storage -40 ... +80 °C
Climatic withstand Maximum operating altitude (without derating) Mechanical durability Resistance to shock
acc. IEC 60068-2-27 and EN 60068-2-27 15 g / 11 ms acc. to IEC/EN 60947-1 Annex. Q Category E
Resistance to vibrations
acc. IEC 60068-2-27 and EN 60068-2-27 5 g / 3 ... 150 Hz acc. to IEC/EN 60947-1 Annex. Q Category E
i
imp
Without thermal overload relay -25 ... +55 °C
B6, VB6, VB6A B7, VB7, VB7A BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
6 kV
Acc. to IEC 60947-1 Annex Q 2000 m 107 operating cycles Half-sine
Sinusoidal
3/42 | ABB
2CDC102043C0201
Loading...