B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data
Main pole – Utilization characteristics according to IEC
Contactor types |
AC operated |
B6, VB6, VB6A |
B7, VB7, VB7A |
|||
|
|
|
|
DC operated |
BC6, VBC6, VBC6A |
BC7, TBC7, VBC7, VBC7A |
Standards |
|
IEC/EN 60947-1, IEC/EN 60947-4-1 |
|
|||
Rated operational voltage Ue max |
|
690 V AC |
|
|||
Rated frequency (without derating) |
|
DC or 50 / 60 Hz |
|
|||
Conventional free-air thermal current lth |
|
Screw terminal types: 20 A |
|
|||
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C, |
|
Flat pin types: 20 A |
|
|||
with conductor cross-sectional area |
|
Soldering pin types: 12 A |
|
|||
AC-1 Utilization category for air temperature close to contactor θ ≤ 40 °C |
|
|
|
|||
Ie / Rated operational current AC-1 |
220-230-240 V |
Screw terminal types: 20 A |
|
|||
Ue max ≤ 690 V, 50/60 Hz |
|
Flat pin types: 20 A |
|
|||
|
|
|
|
|
Soldering pin types: 12 A |
|
|
|
|
|
380-400 V |
Screw terminal types: 20 A |
|
|
|
|
|
|
Flat pin types: 20 A |
|
|
|
|
|
|
Soldering pin types: 12 A |
|
|
|
|
|
440 V |
Screw terminal types: 20 A |
|
|
|
|
|
|
Flat pin types: 20 A |
|
|
|
|
|
|
Soldering pin types: 12 A |
|
|
|
|
|
500 V |
12 A |
|
|
|
|
|
690 V |
6 A |
|
AC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C |
|
|
|
|||
Ie / Rated operational current AC-1 |
220-230-240 V |
Screw terminal types: 16 A |
|
|||
Ue max ≤ 690 V, 50/60 Hz |
|
Flat pin types: 16 A |
|
|||
|
|
|
|
|
Soldering pin types: 12 A |
|
|
|
|
|
380-400 V |
Screw terminal types: 16 A |
|
|
|
|
|
|
Flat pin types: 16 A |
|
|
|
|
|
|
Soldering pin types: 12 A |
|
|
|
|
|
440 V |
Screw terminal types: 16 A |
|
|
|
|
|
|
Flat pin types: 16 A |
|
|
|
|
|
|
Soldering pin types: 12 A |
|
|
|
|
|
500 V |
12 A |
|
|
|
|
|
690 V |
6 A |
|
AC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C |
|
|
|
|||
Ie / Rated operational current AC-3 |
220 / 230 / 240 V |
8.9 / 8.5 / 8.1 A |
11.8 / 11.3 / 10.8 A |
|||
3-phase motors |
380 / 400 V |
8.9 / 8.5 A |
12.1 / 11.5 A |
|||
|
|
|
||||
|
|
|
|
440 V |
7.4 A |
10.1 A |
|
M |
|||||
3 |
|
|
500 V |
6.8 A |
9.2 A |
|
|
|
|
|
690 V |
3.8 A |
3.8 A |
Rated operational power AC-3 |
220-230-240 V |
2.2 kW |
3 kW |
|||
1800 r.p.m. 60 Hz |
380-400 V |
4 kW |
5.5 kW |
|||
1500 r.p.m. 50 Hz |
|
|
|
|||
3-phase motors |
440 V |
4 kW |
5.5 kW |
|||
|
|
|
|
|||
|
M |
500 V |
4 kW |
5.5 kW |
||
3 |
|
|
690 V |
3 kW |
3 kW |
|
DC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C |
|
|
|
|||
Ie / Rated operational current DC-1 |
110 V |
- |
4 A |
|||
|
|
|
|
220 V |
- |
0.6 A |
DC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C |
|
|
|
|||
Ie / Rated operational current DC-3 |
110 V |
- |
1.5 A |
|||
|
|
|
|
220 V |
- |
0.25 A |
DC-5 Utilization category for air temperature close to contactor θ ≤ 55 °C |
|
|
|
|||
Ie / Rated operational current DC-5 |
110 V |
- |
0.4 A |
|||
|
|
|
|
220 V |
- |
0.2 A |
Rated making capacity AC-3 |
|
10 x Ie AC-3 acc. to IEC 60947-4-1 |
|
|||
Rated breaking capacity AC-3 |
|
8 x Ie AC-3 acc. to IEC 60947-4-1 |
|
|||
Short-circuit protection device for contactors |
|
|
|
|||
without thermal O/L relay - motor protection excluded |
|
|
|
|||
Ue ≤ 500 V AC - fuse type gG |
|
Type 1: 25 A / Type 2: 25 A |
|
|||
Rated short-time withstand current ICW |
|
|
96 A |
|||
at 40 °C ambient temperature, in free air from a cold state |
10 s |
64 A |
||||
Maximum breaking capacity cos ϕ = 0.45 |
at 400 V |
64 A |
96 A |
|||
Maximum electrical switching frequency |
AC-1 |
300 cycles/h |
|
|||
|
|
|
|
AC-3 |
600 cycles/h |
|
|
|
|
DC-1, DC-3, DC-5 |
600 cycles/h |
|
3
<![if ! IE]><![endif]>2CDC102043C0201
ABB | 3/41
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data
Main pole – Utilization characteristics according to UL/NEMA/CSA
|
|
|
|
|
|
|
|
Contactor types |
AC operated |
B6, VB6, VB6A |
B7, VB7, VB7A |
||
3 |
|
|
DC operated |
BC6, VBC6, VBC6A |
BC7, TBC7, VBC7, VBC7A |
|
|
|
Standards |
|
UL 508, CSA C22.2 N°14 |
|
|
|
Maximum operational voltage |
|
600 V |
|
||
|
UL/CSA general use rating |
|
12 A / 300 V |
16 A / 600 V |
||
|
UL/CSA maximum 1-phase motor rating |
|
|
|
|
|
|
|
Full load current |
120 V AC |
5.8 |
A |
13.8 A |
|
|
|
240 V AC |
4.9 |
A |
10.0 A |
|
|
Horse power rating |
120 V AC |
0.25 hp |
0.75 hp |
|
|
|
|
240 V AC |
0.5 hp |
1.5 hp |
|
|
UL/CSA maximum 3-phase motor rating |
|
|
|
|
|
|
|
Full load current 1) |
200 / 208 V AC |
4.8 |
/ 4.6 A |
7.8 / 10.6 A |
|
|
|
220-240 V AC |
6.8 |
A |
9.6 A |
|
|
|
440-480 V AC |
4.8 |
A |
7.6 A |
|
|
|
550-600 V AC |
1.7 |
A |
6.1 A |
|
|
Horse power rating 1) |
200 / 208 V AC |
1 hp |
2 / 3 hp |
|
|
|
|
220-240 V AC |
2 hp |
3 hp |
|
|
|
|
440-480 V AC |
3 hp |
5 hp |
|
|
|
|
550-600 V AC |
1 hp |
5 hp |
|
|
Resistive Heating |
300 V per pole |
8 A |
|
8 A |
|
|
Incandescent Lamps |
300 V per pole |
6 A |
|
6 A |
|
|
Fluorescent Lamps |
300 V per pole |
8.4 A |
8.4 A |
||
|
Short-circuit protection device for contactors |
|
|
|
|
|
|
without thermal overload relay - motor protection excluded |
|
|
|
|
|
|
|
Fuse rating |
600 V |
40 A |
|
|
|
|
Fuse type, 600 V |
600 V |
Class J |
|
|
|
Maximum electrical switching frequency |
|
|
|
|
|
|
|
For resitive loads AC-1 |
|
300 cycles/h |
|
|
|
|
For motor loads AC-3 |
|
600 cycles/h |
|
1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
General technical data
Contactor types |
AC operated |
B6, VB6, VB6A |
B7, VB7, VB7A |
|
DC operated |
BC6, VBC6, VBC6A |
BC7, TBC7, VBC7, VBC7A |
Rated insulation voltage Ui |
|
|
|
acc. to IEC 60947-4-1 |
690 V |
|
|
acc. to UL/CSA |
|
600 V |
|
Rated impulse withstand voltage Uimp |
6 kV |
|
|
Ambient air temperature, close to contactor |
|
|
|
Operation |
Fitted with thermal overload relay |
-25 ... +50 °C |
|
|
Without thermal overload relay |
-25 ... +55 °C |
|
Storage |
|
-40 ... +80 °C |
|
Climatic withstand |
|
Acc. to IEC 60947-1 Annex Q |
|
Maximum operating altitude (without derating) |
2000 m |
|
|
Mechanical durability |
|
107 operating cycles |
|
Resistance to shock |
|
Half-sine |
|
acc. IEC 60068-2-27 and EN 60068-2-27 |
15 g / 11 ms |
|
|
acc. to IEC/EN 60947-1 Annex. Q |
Category E |
|
|
Resistance to vibrations |
|
Sinusoidal |
|
acc. IEC 60068-2-27 and EN 60068-2-27 |
5 g / 3 ... 150 Hz |
|
|
acc. to IEC/EN 60947-1 Annex. Q |
Category E |
|
<![endif]>2CDC102043C0201
3/42 | ABB