B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Main pole – Utilization characteristics according to IEC
Contactor types
Standards
Rated operational voltage U
e max
Rated frequency (without derating)
Conventional free-air thermal current l
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C,
with conductor cross-sectional area
th
AC-1 Utilization category for air temperature close to contactor θ ≤ 40 °C
I
/ Rated operational current AC-1
e
U
≤ 690 V, 50/60 Hz
e max
AC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current AC-1
e
U
≤ 690 V, 50/60 Hz
e max
AC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C
Ie / Rated operational current AC-3 220 / 230 / 240 V
3-phase motors
M
M
3
3
Rated operational power AC-3
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
M
M
3
3
DC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current DC-1 110 V
e
DC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current DC-3 110 V
e
DC-5 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
/ Rated operational current DC-5 110 V
e
Rated making capacity AC-3
Rated breaking capacity AC-3
Short-circuit protection device for contactors
without thermal O/L relay - motor protection excluded
Ue ≤ 500 V AC - fuse type gG Type 1: 25 A / Type 2: 25 A
Rated short-time withstand current I
at 40 °C ambient temperature, in free air from a cold state
CW
Maximum breaking capacity cos ϕ = 0.45
Maximum electrical switching frequency
AC operated
DC operated
220-230-240 V
380-400 V
440 V
500 V
690 V
220-230-240 V
380-400 V
440 V
500 V
690 V
380 / 400 V
440 V
500 V
690 V
220-230-240 V
380-400 V
440 V
500 V
690 V
220 V
220 V
220 V
10 s
at 400 V
AC-1
AC-3
DC-1, DC-3, DC-5
B6, VB6, VB6A B7, VB7, VB7A
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
IEC/EN 60947-1, IEC/EN 60947-4-1
690 V AC
DC or 50 / 60 Hz
Screw terminal types: 20 A
Flat pin types: 20 A
Soldering pin types: 12 A
Screw terminal types: 20 A
Flat pin types: 20 A
Soldering pin types: 12 A
Screw terminal types: 20 A
Flat pin types: 20 A
Soldering pin types: 12 A
Screw terminal types: 20 A
Flat pin types: 20 A
Soldering pin types: 12 A
12 A
6 A
Screw terminal types: 16 A
Flat pin types: 16 A
Soldering pin types: 12 A
Screw terminal types: 16 A
Flat pin types: 16 A
Soldering pin types: 12 A
Screw terminal types: 16 A
Flat pin types: 16 A
Soldering pin types: 12 A
12 A
6 A
8.9 / 8.5 / 8.1 A 11.8 / 11.3 / 10.8 A
8.9 / 8.5 A 12.1 / 11.5 A
7.4 A 10.1 A
6.8 A 9.2 A
3.8 A 3.8 A
2.2 kW 3 kW
4 kW 5.5 kW
4 kW 5.5 kW
4 kW 5.5 kW
3 kW 3 kW
- 4 A
- 0.6 A
- 1.5 A
- 0.25 A
- 0.4 A
- 0.2 A
10 x Ie AC-3 acc. to IEC 60947-4-1
8 x Ie AC-3 acc. to IEC 60947-4-1
64 A
64 A
96 A
96 A
300 cycles/h
600 cycles/h
600 cycles/h
3
ABB | 3/41
2CDC102043C0201
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Main pole – Utilization characteristics according to UL/NEMA/CSA
Contactor types
3
Standards
Maximum operational voltage
UL/CSA general use rating
UL/CSA maximum 1-phase motor rating
Full load current
Horse power rating
UL/CSA maximum 3-phase motor rating
Full load current
Horse power rating
Resistive Heating
Incandescent Lamps
Fluorescent Lamps
Short-circuit protection device for contactors
without thermal overload relay - motor protection excluded
Fuse rating
Fuse type, 600 V
Maximum electrical switching frequency
For resitive loads AC-1 300 cycles/h
For motor loads AC-3 600 cycles/h
1)
For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
1)
1)
AC operated
DC operated
120 V AC
240 V AC
120 V AC
240 V AC
200 / 208 V AC
220-240 V AC
440-480 V AC
550-600 V AC
200 / 208 V AC
220-240 V AC
440-480 V AC
550-600 V AC
300 V per pole
300 V per pole
300 V per pole
600 V
600 V
B6, VB6, VB6A B7, VB7, VB7A
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
UL 508, CSA C22.2 N°14
600 V
12 A / 300 V 16 A / 600 V
5.8 A 13.8 A
4.9 A 10.0 A
0.25 hp 0.75 hp
0.5 hp 1.5 hp
4.8 / 4.6 A 7.8 / 10.6 A
6.8 A 9.6 A
4.8 A 7.6 A
1.7 A 6.1 A
1 hp 2 / 3 hp
2 hp 3 hp
3 hp 5 hp
1 hp 5 hp
8 A 8 A
6 A 6 A
8.4 A 8.4 A
40 A
Class J
General technical data
Contactor types
Rated insulation voltage U
acc. to IEC 60947-4-1 690 V
acc. to UL/CSA 600 V
Rated impulse withstand voltage U
Ambient air temperature, close to contactor
Operation Fitted with thermal overload relay -25 ... +50 °C
Storage -40 ... +80 °C
Climatic withstand
Maximum operating altitude (without derating)
Mechanical durability
Resistance to shock
acc. IEC 60068-2-27 and EN 60068-2-27 15 g / 11 ms
acc. to IEC/EN 60947-1 Annex. Q Category E
Resistance to vibrations
acc. IEC 60068-2-27 and EN 60068-2-27 5 g / 3 ... 150 Hz
acc. to IEC/EN 60947-1 Annex. Q Category E
i
imp
Without thermal overload relay -25 ... +55 °C
AC operated
DC operated
B6, VB6, VB6A B7, VB7, VB7A
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
6 kV
Acc. to IEC 60947-1 Annex Q
2000 m
107 operating cycles
Half-sine
Sinusoidal
3 /42 | ABB
2CDC102043C0201
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Magnet system characteristics for B6, B7 contactors
Contactor types
Coil operating limits acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage U
Coil consumption Average pull-in value 3.5 VA / 3.5 W
C
Average holding value 3.5 VA / 3.5 W
Drop-out voltage
Magnet system characteristics for BC6, BC7 contactors
AC operated
AC supply
B6, VB6 B7, VB7
0.85 ... 1.1 x U
c
See ordering tables
0.20 ... 0.75 % of U
c
3
Contactor types
DC operated
Coil operating limits acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage U
Coil consumption
1)
C
Average pull-in value 3.5 VA / 3.5 W
Average holding value 3.5 VA / 3.5 W
Drop-out voltage in % of U
1)
Interface mini-contactors: see coil consumption on ordering details pages
C min
Magnet system characteristics for TBC7 contactors
Contactor types
Coil operating limits acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage U
Coil consumption Average pull-in value 5 VA / 5 W
Drop-out voltage in % of U
C min
C
Average holding value 5 VA / 5 W
DC operated
Mounting characteristics and conditions for use
Contactor types
Mounting positions
AC operated
DC operated
DC supply
DC supply
BC6, VBC6 BC7, VBC7
0.85 ... 1.1 x U
c
See ordering tables
0.10 ... 0.75 x U
C
TBC7
Wide range voltage supply see ordering tables, U
Cmin
... U
Cmax
See ordering tables
≤
0.20 % of U
Cmin
B6, VB6, VB6A B7, VB7, VB7A
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
- 30° + 30°
Pos. 4
Pos. 3
Mounting distances
Fixing
On rail acc. to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm
By screws (not supplied) 2 x M4 screws placed diagonally
Pos. 1
Pos. 1 ± 30°
The contactors can be assembled side by side
Pos. 5 Pos. 6
2CDC102043C0201
ABB | 3 /43
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Auxiliary contacts for front mounting, side mounting and built-in according to IEC
Types CA6, CAF6, built-in auxiliary contacts
Standards
3
Rated operational voltage Ue max
Rated frequency (without derating)
Conventional free-air thermal current lth θ ≤ 40 °C
Ie / Rated operational current AC-15
acc. to IEC 60947-5-1
24 V 50/60 Hz
110-120 V 50/60 Hz
220-230-240 V 50/60 Hz
380-400 V 50/60 Hz
440 V 50/60 Hz
Ie / Rated operational current DC-13
acc. to IEC 60947-5-1
24 V DC
110 V DC
220 - 240 V DC
Short-circuit protection device
Minimum switching capacity with failure rate acc. to IEC 60947-5-4
Maximum electrical switching frequency
Auxiliary contacts for front mounting, side mounting and built-in according to UL/CSA
Types CA6, CAF6, built-in auxiliary contacts
Max. operational voltage
Pilot duty
AC thermal rated current 5 A
IEC/EN 60947-1, IEC/EN 60947-4-1
690 V
DC or 50 / 60 Hz
6 A
4 A
4 A
4 A
3 A
3 A
2.5 A
0.7 A
0.4 A
6 A, Type gG
17 V / 5 mA
AC-15
600 cycles/h
DC-13
600 cycles/h
600 V AC
A600
Accessories for mini contactors
MS116
CA6
MS132
MO132
RV-BC6
BEA7
B7
B6
CAF6
RV-BC6
RV-BC6
3/44 | ABB
E16DU
T16
2CDC212018F0011
2CDC102043C0201
B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors
Technical data
Connection characteristics
Contactor types
Main terminals
Connection capacity
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Screw terminals
Screwdriver type
1)
Main conductors (poles)
Rigid: solid
Flexible without ferrule
Connection capacity acc. to UL/CSA
Stripping length
Tightening torques
Connection capacity – auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid: solid
Flexible without ferrule
Connection capacity acc. to UL/CSA
Stripping length
Tightening torques
Coil terminals
Built-in auxiliary terminals
Main terminals
Coil terminals
Built-in auxiliary terminals
All terminals
AC operated
DC operated
1 or 2 x
1 or 2 x
1 or 2 x
1 or 2 x
1 or 2 x
1 or 2 x
B6, VB6, VB6A B7, VB7, VB7A
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Screw terminals with cable clamp
1 ... 4 mm²
1 ... 2.5 mm²
AWG 22 ... 10
9 mm
0.8 ... 1.1 Nm / 7 lb.in
1 ... 4 mm²
1 ... 2.5 mm²
AWG 22 ... 10
9 mm
0.8 ... 1.1 Nm / 7 lb.in
0.8 ... 1.1 Nm / 7 lb.in
IP20
IP20
IP20
(Delivered in open position, screws of unused terminals must be tightened)
M3
Flat Ø 5.5 mm / Pozidriv 1
3
1)
Soldering pin connection acc. to DIN 40801: 0.8 x 1 mm / 0.8 x 2.54 mm
Flat pin connection acc. to DIN 46248: 1 x 6.3 mm / 1 x 2.8 mm
ABB | 3 /45
2CDC102043C0201