1 In15A = 10kA@277 VAC 10kA@347 VAC
2 In15A = 35kA@240 VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version-
4 2p T4N250 and T5N400 available only in N interrupting capacity.
5 In from 15A up to 30A=65kA@480 VAC
6 Applies to MCS only.
Low Voltage Products & Systems 17.13
ABB Inc. 1SXU000023C0202 Rev. A
Tmax
MCCBs
T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic
Dimensions3P Fixed Version 5.12H x 3.00W x 2.76D
2.34 (Ibs)
Weight
T1
General
The T1 breaker family ranges from 15 through 100 amperes. The T1 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays for
overcurrent trip protection. Thermal overload protection is provided by heat sensitive
bimetals. Short circuit protection for the breaker is accomplished using a precise
magnetic coil. State of the art construction in contacts and arcing chambers aid in
limiting damaging fault currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T1 also carries an IEC-60947-2 rating.
Versions
The T1 frame is available in two versions:
T = Thermal-magnetic, xed
D = Molded case switch
Performance levels
The T1 breaker has two performance levels available:
B = Basic single pole
N = Normal three pole
Number of poles
The T1 molded case circuit breaker is available in single, three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB sales
person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous trip
mechanism for self protection.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
VoltageContinuous ratingB (1 pole)N
240VAC15 – 100A—
347VAC
480VAC ∆
600Y/347VAC15 – 100A—10
250VDC 2 pole series15 – 100A—25
500VDC 3 pole series15 – 100A—25
15A
20 – 100A
15A 2
20 – 100A
10
14
—
—
50 1
IEC 60947-2 Interrupting capacity (kA RMS)
VoltageContinuous ratingB (1 pole)N
230VAC15 – 100A
415VAC15 – 100A—36
690VAC15 – 100A—6
500VDC 3 pole series15 – 100A—36
25 3
—
—
14
22
50
17
1 In 15A 35kA @ 240VAC.
2 15A available in 480Y/277 VAC only.
3 Interrupting capacity for 16-20A is 16kA
Low Voltage Products & Systems 17.15
ABB Inc. 1SXU000023C0202 Rev. A
Tmax
MCCBs
T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic/Molded Case Switch
1 Electrical/mechanical accessories cannot be installed on single pole breakers.
2 Rated 480Y/277 VAC for 15A.
3 When protected by a OCPD with appropriate ratings.
The T2 breaker family ranges from 15 through 100 amperes. The T2 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays for
overcurrent trip protection as well as a version with microprocessor-based electronic
trip unit. Thermal overload protection is provided by heat sensitive bimetals. State of
the art construction in contacts and arcing chambers aid in limiting damaging fault
currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T2 also carries an IEC-60947-2 rating.
Versions
The T2 frame is available in four versions:
T = Thermal-magnetic, xed
B = Adjustable LS/I electronic
M = Magnetic only (MCP)
E5 = Electronic instantaneous only (MCP)
Trip functions
These tripping functions are available:
L = Long time
S = Short time
I - Instantaneous
Performance levels
The T2 breaker has two performance levels available:
S = Standard
H = High - UL Current Limiting
Number of poles
The T2 is available in three and four pole versions. Estimate 4 pole pricing by adding
35% to the 3 pole price and contact your ABB sales person for details.
The T3 breaker family ranges from 60 through 225 amperes. The T3 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays for
overcurrent trip protection. Thermal overload protection is provided by heat sensitive
bimetals. Short circuit protection begins at 10 times the thermal rating of the breaker
using a precise magnetic coil. State of the art construction in contacts and arcing
chambers aid in limiting damaging fault currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T3 also carries an IEC-60947-2 rating.
Versions
The T3 frame is available in three versions:
T = Thermal-magnetic, xed
M = Magnetic only (MCP)
D = Molded case switch
Performance levels
The T3 breaker has two performance levels available:
N = Normal
S = Standard
Number of poles
The T3 molded case circuit breaker is available in three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB
sales person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
1 When protected by a OCPD with appropriate ratings.
17.22 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc.
Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic
Dimensions3P Fixed Version 6.7H x 4.13W x 4.07D
6.75 (Ibs)
Weight
Ts3
General
The Ts3 breaker family ranges from 15 through 225 amperes. The Ts3 trip
mechanisms are non-interchangeable and use sensitive electromagnetic relays for
overcurrent trip protection. Heat sensitive bimetals are used for thermal overcurrent
protection. Short circuit current protection begins at 10 times the thermal rating of
the breaker and uses a magnetic coil principle.
Standards
The UL489/CSA 22.2 version of Ts3 also carries an IEC-60947-2 rating.
Versions
To meet all application needs, the Ts3 is available in various versions:
T =Thermal-magnetic
D = Molded case switch
M = Magnetic only (MCP)
Performance level
Each version is also available in different maximum fault interrupting levels
N = Normal
H = High
L = Extra high
Number of poles
The Ts3 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
VoltageNHL
150AF, 15A-150A
240 VAC65100150
480 VAC2550
600 VAC141425
500 VDC355065
600 VDC203550
225AF, 175A-225A
240 VAC65100150
480 VAC255065
600 VAC–––
500 VDC203550
600 VDC–––
IEC-60947-2 Interrupting capacity (kA RMS)
230 VAC65100170
415 VAC356585
690 VAC141820
750 VDC 2
2035
85
50
1
Tmax
MCCBs
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
1 15-30A are 65kA at 480VAC
Low Voltage Products & Systems 17.23
ABB Inc. 1SXU000023C0202 Rev. A
17