ABB SACE EMAX 2 Part Numbering Designation

Page 1
Instructions for ordering
Emax 2 order code explanation
Emax 2 circuit breaker order code explanation
Z 2 H F UJ A E 4 8 N B E A A 0 Q C E A
1 2 3 4 5&6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 — Emax 2 Prefix
Z
E1.2 E2.2 E4.2 E6.2 E6.2 100%N
3p 1 2 4 6
4p — N Left A B C D E
4p — N Right F G H J K
3 — Breaking Capacity
B C N S H V
UL kA @ 5 08VAC 42 50 65 85 100
UL kA @ 6 35VAC 42 50
1)
1)
65
85 85/100
4)
IEC kA @ 440VAC 42 50 66 85 100 150
2)
IEC kA @ 690VAC 42 42 66
1)
E1.2 has 42kA
2)
E1.2 has 50kA
3)
85kA for E2.2 and E4.2, 100kA for E6.2
4)
85kA for E2.2 and E4.2, 100kA for E6.2
5)
125kA for E4.2, 150kA for E6.2
6)
E1.2 available in N, E2.2 and E4.2 in H and E6.2 in X versions.
66 85/1003)100
4 — Frame Rating (A)
UL
250 400 800 1200 1600 2000 2500 3200 4000 5000 6000
A B C D E F G H J K L
IEC
250 630 800 1000 1250 160 0 2000 2500 3200 4000 5000 6300
M N P Q R S T U V W X Y
9
5&6 — Rating Plug
Switch Disconnector
UL Rating Plug ( A)
00
100 200 250 400 600 800 1000 1200 16 00 2000 2500 3000 3200 3600 4000 5000 6000
UA UB UC UD UE UF UG UH UJ UK UL UM UN UQ UR US UT
IEC Rating Plug (A)
100 200 250 400 630 800 1000 12 50 1600 2000 2500 3200 4000 5000 6300
EA EB EC ED EE EF EG EH EJ EK EL EN ER ES ET
IEC "L-Of f" Rating Plug (A)
IEC RC Rating Plug (A)
100 200 250 400 630 800 1000 12 50 1600 2000 2500 3200 4000 5000 6300
LA LB LC LD LE LF LG LH LJ LK LL LN LR LS LT
100 200 250 400 630 800 1250 2000 3200 4000
RA RB RC RD RE RF RH RK RN RR
7)
7 — Version
Drawout (Less Cradle) A
Fixed W/Std Term B
Fixed W/Alternative
Lower Terminals
1)
Standard terminals for E1.2 fixed are Front. Standard terminals for E2.2 - E6.2 are Rear Horrizontal except for UL E4.2 3200A and E6.2 6000A, which are Rear Vertical
2)
Not available for UL E4.2 3200A or UL E6.2 6000A. Not UL listed.
3)
Available for E1.2 only
4)
Not available for UL E4.2 3200A or E6.2 6000A, it is their standard termination
5)
Available for E2.2 - E6.2 only
6)
Available for E2.2 IEC only; not available as factory installed with other terminal combinations
7)
Not yet available. Contact ABB
8)
Not UL listed.
Note: Additional, non-factory installed options are available.
9/2 | 1SXU200040C0201 | ABB catalog
1)
Upper Terminals
Rear Horiz
2)
Rear Horiz
2)
3)
C
Rear Vert H J
8)
Front
3)8)
Ext Front
FcCuAl Cable
Spread Rear Horiz
Spread Rear Vert
N P Q
T U V W X
3)8)
2 3 4 5 6
6)8)
7
6)8)
8
Rear Vert Front
D E F G
4)
8)
Ext Front
3)8)
FcCuAl Cable
3)8)
K L M
5)
R S
Spread Rear Horiz
6)8)
Spread Rear Vert
6)8)
Page 2
Z 2 H F UJ A E 4 8 N B E A A 0 Q C E A
1 2 3 4 5&6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
8 — Trip Unit
Switch Disconnector
W/Std 250V Bell A larm
W/24V Digital Bell Alarm
Note: An LCD screen version trip unit is available as a separate item for Ekip Touch, Ekip Hi-touch and Ekip
G versions
1)
The Ekip Power Controller requires the use of either the Ekip Measuring or the Ekip Measuring Pro module
0
LI LSI LSIG
DIP A B C
Touch D E F
1)
Touch + Power Controller
G H I
Hi-Touch J K
1)
Hi-Touch + Power Controller
L M
G Touch N
1)
G Touch + Power Controller
P
G Hi-Touch Q
1)
G Hi-Touch + Power Controller
R
LI LSI LSIG
Dip S T U
Touch V W X
1)
Touch + Power Controller
Y Z 1
Hi-Touch 2 3
1)
Hi-Touch + Power Controller
4 5
G Touch 6
1)
G Touch + Power Controller
7
G Hi-Touch 8
1)
G Hi-Touch + Power Controller
9
9 — Measuring and Power Supply
None 0
Measuring Measuring Pro Future
1 2 N
Pwr Sply 24-48VDC 3 4 5 P
Pwr Sply 110-240VAC/ DC 6 7 8 Q
UTMO A B R
EMO C D S
UTMO + P wr Sply 24 -48VDC E F T
UTMO + P wr Sply 110-240VAC/D C
G H U
EMO + Pwr Sply 24-48VD C J K V
EMO + Pwr Sply 110-240VAC/DC
Note: Ekip Hi-Touch and all Ekip G trip units are supplied with Measuring Pro as standard. Note: Voltage outlets are installed on the bottom terminals as standard. UTMO = Upper terminal mounting option of voltage outlets EMO = External mounting option of voltage outlets Future Arangement is the pre-wiring for the ability to easily add a measuring module at a future date
L M W
Arrangement
9
10 — Communication Modules
None 0
Single
Combos MOD-RS-485 + MOD-TCP MOD-TCP + Profibus Profibus + Profinet Profinet + DeviceNet
Note: Communication modules are not usable with Ekip Dip trip units or for Switch Disconnectors.
MOD-RS-485 MOD-TCP Profibus Profinet DeviceNet Ethernet/IP IEC 61850
2 3 4 5 6 7 8
A B C D E F
MOD-RS-485 + Profibus MOD-TCP + Profinet Profibus + DeviceNet
Profinet + Ethernet/IP DeviceNet + IEC 61850
G H J K L
MOD-RS-485 + Profinet MOD-TCP + DeviceNet Profibus + Ethernet/IP
Profinet + IEC 6185 0
M N P Q
MOD-RS -485 + DeviceNet MOD-TCP + Ethernet/IPProfibus + IEC 6185 0
R S T
MOD-RS-485 + Ethernet/IP MOD-TCP + IEC 61850
U V
MOD-RS -485 + IEC 61850
W
DeviceNet + Ethernet/IP
Ethernet/IP + IEC 61850
continued
ABB catalog | 1SXU200040C0201 | 9/3
Page 3
Instructions for ordering
Emax 2 order code explanation
(cont.)
Emax 2 circuit breaker order code explanation
Z 2 H F UJ A E 4 8 N B E A A 0 Q C E A
1 2 3 4 5&6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
11 — Redundant Communication & Other Modules
None 0
Redundant Com.
Other Modules
Combos
1)
Ekip Synchrocheck requires the use of the Ekip Measuring Pro module. Note: Communication, Ekip 2K and Ekip Synchrocheck modules are not usable with Ekip Dip trip units or for Switch Disconnectors. Ekip Link is compatible with all trip units, but not with switch disconnectors. If the redundant communication plus another module is selected (D-F), the redundant module will automatically match the selected communication type of digit 10. If two communication options are selected in digit 10, then the specific redundant module required is needed (2-7). The maximum number of modules allowed for the combination of digit 10 and 11 is 3 for E2.2-E6.2 and 2 for E1.2.
MOD-RS-485 MOD-TCP Profibus Profinet DeviceNet Ethernet/IP
2 3 4 5 6 7
1)
Ekip Link Synchrocheck
A B C
Rdt Com + Link Redun Com + Sync
D E F
Link + Sync
G H J
Link + Sync
K L M
Link + 2K
N
Link + 2K + 2K
P
1)
1)
+ 2K Sync1) + 2K + 2K 2K+2K+2K
Sync1) + 2K 2K+2K
Signaling 2K
1)
Redun Com + 2K
12 — Auxiliary Contacts & Signaling
9
6 AUX (40 0V)
6 AUX (24V)
6 AUX (3 400V & 3-24V )
4-K Signaling
Note: Circuit breakers include the standard 400V 4 AUX as a standard item, but the 24V or mix options
Note: Options 0, D, H and M are available for use with switch disconnectors only.
1)
Not available for the E1.2.
2)
Not compatible with Ekip Dip trip units or switch disconnectors.
1)
1)
1) 2)
can be selected in its place.
None 0
4 AU X (400V ) 4 AUX (24V ) 4 AUX (2-400 V & 2-24V)
A B C
D E F G
H J K L
1)
M N P Q
R S T
13 — Remote Reset (YR) & Ready to Close (RTC)
None 0
YR 24VAC/DC YR 110VAC/ DC YR 220V AC/DC
A B C
RTC 24V DC D E F G
RTC 250VAC/DC H J K L
14 — Closing Coil (YC) & Redundant Closing Coil (YC2)
None 0
24VAC/DC 30VAC/DC 4 8VAC/DC 60VAC/DC 110 -120 VAC/ DC 120-127V A C/DC 220-240VAC/DC 240-250VAC/DC 277 VAC 380-400VAC 415-440VAC 480-500VAC
YC Only
YC + YC2
(equal V )
1)
A B C D E F G H J K L M
N P Q R S T U V W X Y Z
1)
Not available for E1.2
15 — Shunt Trip — YO
None 0
24VAC/DC 30VAC/ DC 48VAC/DC 60 VAC/D C 110 -120V AC/D C 120 -127 V AC/DC 220-240VAC/DC 240-250VAC/DC 27 7VAC 380-400VAC 415-440VAC 480-500VAC
A B C D E F G H J K L M
9/4 | 1SXU200040C0201 | ABB catalog
Page 4
Z 2 H F UJ A E 4 8 N B E A A 0 Q C E A
1 2 3 4 5&6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
16 — Undervoltage (YU) & Redundant Shunt Trip (YO2)
None 0
24VAC/DC 30VAC/DC 4 8VAC/DC 60VAC/DC 110 -120 VAC/ DC 120-127 V AC/D C 220-240VAC/DC 240-250VAC/DC 2 77VAC 380-400VAC 415-440VAC 480-500VAC
YU Only
A B C D E F G H J K L M
YO2 Only
N P Q R S T U V W X Y Z
17 — Spring Charge Motor (M) and Ekip Communication Actuator
None 0
Actuator Only
M W/ Std Aux
M W/ 24VDC Aux
M W/ Std Aux + Actuator
M W/ 24VDC Aux + Actuator
Note: Standard AUX contact for motors are 250V for E1.2 and 400V for E2.2-E6.2
1)
Not available for E1.2
1
24-30VAC/DC 48-60VAC/DC 100 -130V AC/D C 220-250VAC/DC 277VAC 380-415VAC 440-480VAC
2 3 4 5 6 7 8
A B C D E F G
H J K L M N P
Q R S T U V W
1)
18 — Push Button Lock Options
None 0
Push Button Covers Padlocks in Open Positions
PBC Sp Key PBC PL - 4mm PBC PL - 7mm PBC PL - 8mm PLC - 4mm PLC - 7mm PLC - 8mm
2 3 4 5 6 7 8
Key Lock in Open Pos. — Diff Keys
Key Lock in Open Pos — Same Keys1)B L M N P Q R S
Key Lock in Open Pos. — Kirk Key
1)
Standard key for Same Key option is #20005. Locks with keys #20006, #20007, #20008 and #20009 are available as separate items.
Note: Key lock options for Castell and Ronis/Profalux are available for order as separate items.
A D E F G H J K
C T U V W X Y Z
9
19 — 1st Racking Lock Options
None X
1st KLP-Same Keys
A B C D
PLP Padlock
1)
Standard key for Same Key option is #20005. Locks with keys #20006, #20007, #20008 and #20009 are available as separate items.
2)
Two Castell adapters cannot be used together, but a Castell adapter can be used in either position with another style lock.
Note: The racking locks above are for E2.2-E6.2 only; for E1.2 they are located on the cradle. The supplement for locking in racked out only is located on the cradle for all breaker sizes.
E F G H J
1)
1st KLP-Diff Keys 1st KLP-Kirk/Ron/Prof 1st KLP - Castell
20 — 2nd Racking Lock Options & Mechanical Operation Counter
None X
2nd KLP-Same Keys
B C D E
MEC OP CTR
1)
Standard key for Same Key option is #20005. Locks with keys #20006, #20007, #20008 and #20009 are available as separate items.
2)
Two Castell adapters cannot be used together, but a Castell adapter can be used in either position with another style lock.
Note: The racking locks above are for E2.2-E6.2 only; for E1.2 they are located on the cradle.
A F G H J
1)
2nd KLP-Diff Keys 2nd KLP-Kirk/Ron/Prof 2nd KL P - Castell
2)
2)
ABB catalog | 1SXU200040C0201 | 9/5