ABB S294-C100 Data Sheet

5 (1)
ABB S294-C100 Data Sheet

S294-C100

General Information

Extended Product Type:

S294-C100

Product ID:

GHS2942001R0824

EAN:

4016779570817

Catalog Description:

Miniature Circuit Breaker - S290 - 4P - C - 100 A

Long Description:

S290 miniature circuit breakers are current limiting. They have two different tripping

 

mechanisms, the delayed thermal tripping mechanism for overload protection and the

 

electromechanic tripping mechanism for short circuit protection. They are available in

 

different characteristics (B,C,K), configurations (1P,2P,3P,4P), breaking capacities (up to 20

 

kA at 230/400 V AC) and rated currents (up to 125A). All MCBs of the product range S290

 

comply with IEC/EN 60898-1, IEC/EN 60947-2 and UL1077, allowing the use for residential,

 

commercial and industrial applications.

Categories

Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs

Ordering

Minimum Order Quantity:

1 piece

Customs Tariff Number:

85362090

EAN:

4016779570817

Dimensions

Product Net Depth:

70 mm

Product Net Height:

90 mm

Product Net Weight:

1.05 kg

Product Net Width:

105 mm

Container Information

Package Level 1 Width:

92 mm

Package Level 1 Length:

110 mm

Package Level 1 Height:

82 mm

Package Level 1 Gross Weight:

1.07 kg

Package Level 1 Units:

1 piece

Environmental

Ambient Air Temperature:

Operation -25 ... +45 °C

 

Storage -40 ... +70 °C

Resistance to Shock acc. to IEC

15g / 1 shock / 11 ms

60068-2-27:

 

Resistance to Vibrations acc. to IEC 5g, at 25 ... 150 Hz, 6g at 35 Hz with load 0.8 In

60068-2-6:

 

Environmental Conditions:

28 cycles

 

with 55 °C / 90-96 %

 

and 25 °C / 95-100 %

RoHS Status:

Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical

Number of Poles:

4

Tripping Characteristic:

C

Rated Current (In):

100 A

Rated Operational Voltage:

acc. to IEC 60898-1 400 V AC

Power Loss:

32 W

 

at Rated Operating Conditions per Pole 8 W

Rated Insulation Voltage (Ui):

acc. to IEC/EN 60664-1 500 V

Operational Voltage:

Maximum (Incl. Tolerance) 125 V DC

 

Maximum (Incl. Tolerance) 253 / 440 V AC

 

Minimum 24 V AC / 24 V DC

Rated Frequency (f):

50 Hz

 

60 Hz

Rated Short-Circuit Capacity (Icn):

10 kA (AC) kA

Rated Ultimate Short-Circuit

10 kA

Breaking Capacity (Icu):

 

Rated Service Short-Circuit

(AC) 10 kA

Breaking Capacity (Ics):

 

Loading...
+ 2 hidden pages