ABB SA-1 Instruction Leaflet

Page 1
ABB Automation, Inc.
Substation Automation & Protection Division Coral Springs, FL Allentown, PA
Instruction Leaflet
41-348.1H
Effective: November 1997 Supersedes I.L. I.L. 41-348.1G, Dated January 1985
( | ) Denotes Change Since Previous Issue
CAUTION
!
Before putting relays into service, operate the relay to check the electrical connections. Close red handle switch last when placing relay in service. Open red handle switch first when removing relay from service.
1. APPLICATION
The SA-1 relay is a three-phase high-speed relay used for differential protection of ac generators and motors. With proper selection of current transformers, the relay is unaffected by dc transients associated with asymmetrical through short-circuit conditions.
Current transformer burden in ohms should not exceed (N
should not differ by more than a 2 to 1 ratio between the two sets of ct’s. The above terms are defined as:
N
P
V
CL
B
F
R
B
= proportion of total number of ct turns in
= current transformer relaying accuracy
=
= resistance of the burden, excluding ct
)/133; further, the burden factor, BF,
PVCL
use
class voltage (e.g. C400, V
R
NPV
B
CL
1000
--------------------- -
winding resistance
CL
= 400)
Type SA-1
Generator Differential Relay
In calculating the burden, use the longest one-way lead resistance from the ct to the SA-1 for distribution transformer or resistance grounded machines. Use twice the longest one-way lead resistance for reac­tance grounded machines.
For example, if the 400/5 tap of a 600/5 multi-ratio ct is used, N
rating, V
Assuming a resistance burden of R burden factor, BF is:
The other set of ct’s may than have a burden factor as high as 2 x 3.8 = 7.6, or as low as 1/2 x 3.8 = 1.9.
If the other set of ct’s also has a burden of 0.5 ohm, a C100, C200, or C400 rating would be satisfactory since the burden factors are 7.6, 3.8 and 1.9 respec­tively.
2. CONSTRUCTION
The type SA-1 relay consists of a Restraint Circuit, Operating Circuit, Sensing Circuit, Amplifier Circuit, Trip Circuit, Indicating Circuit, Surge Protection Cir­cuit and external reactors. The principal parts of the relay and their location are shown in Figures 1 through 8.
= 400/600 = 0.67. If this ct has a C200
P
= 200, and the burden should not exceed:
CL
NPV
------------------- -
133
BF
CL
1000
---------------------
NPV
0.67 200×
--------------------------- - 1.0 ohm== 133
= 0.5 ohms, the
B
R
B
1000 0.5×
--------------------------- - 3.8== =
0.67 200×
CL
All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
Page 2
41-348.1H
Type SA-1
Generator Differential Relay
2.1. RESTRAINT CIRCUIT
The restraint circuit of each phase consists of a cen­ter-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are connected in parallel. The parallel connection of rec­tifiers is a maximum voltage network. Hence, the voltage applied to the filter circuit is proportional to the phase current with the largest magnitude.
2.2. OPERATING CIRCUIT
The operating circuit consists of a transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are connected in parallel. This par­allel connection of rectifiers is a maximum voltage network. Hence, the voltage applied to the filter cir­cuit is proportional to the phase current with the larg­est magnitude.
2.3. SENSING CIRCUIT
The sensing circuit is connected to the output of the restraint filter circuit, the operating filter circuit and the input to the amplifier circuit.
With no gate current flowing, the thyristor acts as an open circuit to the breaker trip coil. When a gate cur­rent is applied tot he thyristor the thyristor connects the breaker trip coil to the dc supply.
2.6. INDICATING CIRCUIT
The indicating circuit is triggered by a signal from the amplifier of the relay. Under normal or non-fault con­ditions, the indicating circuit is turned off. When a fault is applied to the relay, the amplifier will conduct to cause a signal to flow into the indicator circuit. When the indicator circuit is triggered, the lamp will turn on. This lamp will remain lit until the indicator cir­cuit is interrupted by resetting the micro-switch.
2.7. SURGE PROTECTION CIRCUIT
The surge protection circuit consists of two capaci­tors (C10 and C11) and a R-C network which is con­nected across the anode and cathode of the tripping thyristor to prevent the SCR from firing by a surge of voltage.
2.8. EXTERNAL REACTORS
2.4. AMPLIFIER CIRCUIT
The amplifier circuit consists of a two-transistor amplifier which controls the operation of a relaxation oscillator.
The amplifier circuit is connected to the sensing cir­cuit such that it receives the difference in output of the restraint filter and the operating filter. Thus, the polarity of the input voltage to the amplifier depends upon the relative magnitude of the voltages appear­ing on the restraint and operating filters. When the voltage output of the operating filter is greater than the output voltage of the restraint filter, a voltage of a certain polarity appears across the input of the ampli­fier. To trigger the amplifier requires that the output voltage of the operating filter be greater than the out­put voltage of the restraint filter.
2.5. TRIP CIRCUIT
The trip circuit consists of a thyristor which has an anode, cathode, and a gate. The anode of the thyris­tor is connected to the positive side of the dc supply and the cathode of the thyristor is connected to the negative side of the dc supply through the trip coil of a breaker. The gate of the thyristor is connected to the output of the amplifier circuit through a pulse transformer.
Three reactors are mounted on a metal plate with a separate terminal strip. The reactors are of the satu­rable type.
3. OPERATION
The Type SA-1 relay is connected to the protected apparatus as shown in Figure 9. On external faults, current flows through the primary winding of the restraint transformers to induce a voltage on the restraint side of the sensing circuit. If the two sets of main current transformers have different perfor­mances, some current will flow out of the mid-tap of the restraint transformers to the operating transform­ers. This will produce a voltage on the operating side of the sensing circuit. With the relay correctly applied, sufficient restraint voltages will exist to prevent the operating voltage from triggering the amplifier.
The percentage slope characteristic of the relay lim­its the operating voltage on heavy external faults where the performance of the two sets of current transformers may be quite different.
On internal faults, the operating coil current is the sum of the current flowing in each of the windings of the restraint transformer and sufficient operating volt­age is available to overcome the restraint voltage.
2
Page 3
Type SA-1 Generator Differential Relay
41-348.1H
4. CHARACTERISTICS
The percentage slope curves are shown in Figures 12 and 13. It will be observed that the relay operates at 5% unbalance at 5 amperes restraint (Figure 12) to provide high sensitivity for internal faults up to full load conditions. At 60 amperes restraint, the operat­ing current required to trip the relay is 30 amperes or 50% unbalance (Figure 13). Thus, when 60 amperes through-fault current is flowing, the output of the main current transformers may vary consider­ably without causing incorrect operation.
The minimum pickup of the relay is 0.14 ampere or
0.5 ampere for the desensitized version.
The operating characteristic of the desensitized SA­1 is shown in Figure 14.
The time curve of the relay is shown in Figure 15.
The frequency response characteristic of the SA-1 relay is shown in Figure 16.
6. SETTINGS
There are no taps on either transformer and, conse­quently, there are no settings to be made except for the choice of battery voltage level.
The 48/125 Vdc relays are normally shipped for 125 volts. For 48 Vdc applications use the mid-tap on the resistor mounted at the top of the relay. The red dot on the resistor is the common point – DO NOT REMOVE.
7. INSTALLATION
The relay should be mounted on switchboard panels or their equivalent in a location free from moisture. Mount the relay vertically by means of the four mounting holes on the flange for semi-flush mount­ing.
Either a mounting stud or the mounting screws may be utilized for grounding the relay. The electrical connections may be made directly to the terminals by means of screws.
5. ENERGY REQUIREMENTS
Each Restraint Circuit
Burden at 5 amperes is 0.25 VA Continuous rating 20 amperes 1 second rating 300 amperes
Operating Circuit
The burden imposed by the operating circuit on each circuit transformer is variable because of the saturating transformer and reactors. At 0.5 amperes, it is 0.37 VA, and at 60 amperes it is 170 VA.
Continuous rating 10 amperes 1 second rating 200 amperes
Amplifier
The dc burden on the station battery is:
Volts Milliamperes Watts
125 dc
48 dc
55 60
6.9
2.9
The external reactor assembly should be mounted and wired per “interwiring Connection Drawing”, Fig­ure 11.
For detailed FT case information, refer to I.L. 41-
076.
8. ADJUSTMENTS AND MAINTENANCE
The proper adjustments to insure correct operation of this relay have been made at the factory and should not be disturbed after receipt by the cus­tomer.
8.1. ROUTINE TEST
The following check is recommended to insure that the relay is in proper working order. All checks can best be performed by connecting the relay per the test circuit of Figure 17. Due to high impedance of the external reactor, prior to saturation, the test circuit of Figure 17 should be used to test the relay only. The reactors can be checked by applying 0.2 amperes 60 hertz and reading the voltage drop across the reactor with a high impedance True RMS reading voltmeter. The voltage drop will be between 20 and 26 volts True RMS. For 0.4 amperes input, the reading should be between 29 and 31 volts True RMS.
3
Page 4
41-348.1H
Type SA-1
Generator Differential Relay
1. Minimum Trip Current with IR set at zero amperes, apply 0.14 ±5% (0.5 ±5% got desensi-
tized SA-1) amperes operating current to each operating circuit of the relay. The relay should operate and the indicator lamp should light.
2. Differential Characteristic a) Apply IR of 5 amperes and adjust the operat-
ing current until the relay operates. The relay should operate and the indicator lamp should light with an operating current of 0.25 ±5% amperes (0.71 5% for desensitized SA-1). Repeat for each phase of the relay.
b) Apply IR of 60 amperes and adjust the oper-
ating current until the relay operates. The relay should operate and the indicator lamp should light with an operating current of 30 ±10% amperes. Repeat for each phase of the relay. (IR = 40 amperes and IO = 24 ±10% for desensitized SA-1).
8.2. MAINTENANCE
All relays should be checked once a year to detect any failures which may have occurred. The tantalum capacitors C1, C2, C3, C4 and C13 may have a com­mon mode failure characteristic and should be checked visually for symptoms of electrolyte leakage every year and replaced if necessary.
8.3. CALIBRATION
Use the following procedure for calibrating the relay if the relay adjustments have been disturbed. This pro­cedure should not be used until it is apparent the relay is not in proper working order.
1. Minimum Trip Current – Connect the relay per test circuit of Figure 17 with switch K open. Adjust the operating resistor in the rear of the relay until the relay operates with IO equal to
0.14 ampere, 0.5 ampere for desensitized SA-1.
DO NOT make adjustments to the resistor unless the dc is disconnected.
The indicator lamp should light when the relay operates.
Repeat for each phase of the relay.
2. Percentage Slope Characteristic (Low Cur- rent). Close switch K and set IR equal to 5
amperes and adjust the restraint resistor in the rear of the relay until the relay operates with Io =
0.25 ±.010 amperes. DO NOT adjust resistor with dc applied to relay.
The indicator lamp should light when the relay operates.
Repeat for each phase of the relay.
Percentage Slope Characteristic (High Cur­rent) – Set IR equal to 60 amperes for the oper-
ating current of 30 amperes. Replace the resistor R17 if necessary. The value of R17 can be between 0 and 100 ohms. Repeat for the other two phases if necessary, replacing R18 and R19 respectively.
3. Electrical Checkpoints – See Table 1.
9. RENEWAL PARTS
Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be fur­nished to customers who are equipped for doing repair work. When ordering parts, always give the nameplate data.
10.ELECTRICAL CHECKPOINTS
Connect relay per test circuit of Figure 17. All voltage readings should be made with a high resistance volt­meter. Refer to component location of checkpoints. Voltage readings are approximate. The voltage read­ings “Input to Amplifier” should not be taken with relay in service.
4
Page 5
Type SA-1 Generator Differential Relay
41-348.1H
Table 1:
(Values in Parenthesis Represent Desensitized SA-1)
CIRCUIT
Operating
Sensing
(Operating)
Restraint
Sensing
(Restraint)
PRIMARY
CURRENT PHASE
0.14A (0.5A)
1 2 3
Any
0.14A
phase
(0.5)
Any
30.0A
phase
5.0A 1 2 3
Any
5.0A
phase
CHECKPOINTS (Typical Value)
TERMINAL VALUE FUNCTION
2 - 7 3 - 6 4 - 5
2.5 ac
2.5 ac
2.5 ac
Input to operate rectifier Input to operate rectifier Input to operate rectifier
+ to ­23 - 26 24 - 26
24 - 8 8 - 25
25 - 26
2.1 dc
1.85 dc
0.55 dc
0.65 dc
0.65 dc
Output to rectifier a. Output to operating sensing circuit b. Input to amplifier c. d. Output to restraint sensing circuit
Ref.: a = b + c + d
+ to ­24 - 26 51.0 dc
18 - 13 17 - 14 15 - 16
6.0 ac
6.0 ac
6.0 ac
Input to restraint rectifier Input to restraint rectifier Input to restraint rectifier
+ to ­25 - 26
25 - 8 8 - 24
24 - 26
2.1 dc
1.2 dc
0.6 dc
0.3 dc
a. Output of restraint sensing circuit b. c. Input to amplifier d. Output to operating sensing circuit
Ref.: a = b + c + d
Amplifier
60.0A
0
Minimum
Trip
Current
+5%
Any
phase
Any
phase
+ to ­25 - 26 42.0 dc
+ to -
27 - 8 12 - 8 10 - 8
0.7 dc
24.0 dc
24.0 dc
+ to -
27 - 8 12 - 8 21 - 8
0.5 dc
24.0 dc
10.0 dc
5
Page 6
41-348.1H
Type SA-1
Generator Differential Relay
Table 2:
Electrical Part List
Circuit Symbol Reference Style
Resistors Resistors Resistors Zener SCR Reactor
Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor
Capacitor Capacitor Capacitor Capacitor Capacitor Capacitor
UT, UM, UB LT, LM, LB R14 Z2
60 Ohms, 25W 265 Ohms, 25W
1.8K, 40 W IN2986B
1875676 1725542 187A321H06 629A798H03 184A614H05
L1
1478B98G01
SA Module Style Number 408C673G01 Sub 35
R1 R2 R3, R4 R5 R6 R7 R8 R9 R10 R11 R12 R13
†
R17, R18, R19 C1, C2, C3, C13
C4 C5 C6 C7 C8, C9
270 Ohms, 1W 2K, 5% 15K, 5%
2.7K, 5% 68K, 5% 27K, 5%
2.2K, 5% 100 Ohms, 10% 220 Ohms, 5% 680 Ohms, 5% 47K, 5% 33 Ohms, 5%
25 MFD, 125V 22 MFD, 35V
0.5 MFD, 200V
2.2 MFD, 35V
2.0 MFD, 200V
0.47 MFD, 50V
184A635H06 184A763H34 184A763H55 184A763H37 184A763H71 184A763H61 184A763H35 184A763H03 184A763H11 184A763H23 184A763H67 187A290H13
184A637H01 184A661H16 187A624H03 837A241H16 187A624H05 762A680H04
Diode Diode
Zener SCR Transistor Transistor Transformer
D1 to D24 D25, D26
Z1 T1, T2
T3 TR-1
IN4821 IN645A
IN752A K1149-13 2N3417 2N2647
188A342H16 837A692H04
186A797H12 184A640H13 848A851H02 629A435H01 629A372H02
SPK Module Style Number 1584C21G01
Resistor Capacitor Capacitor
†
NOTE: The values of R17, R18 and R19 are between 0 and 100 Ohms. They are determined in test.
R15 C10, C11 C12
470 Ohms, 1W
0.01 MFD, 1.5KV
2.0 MFD, 200V
187A643H19 3516A36H03 3509A33H01
6
Page 7
Type SA-1 Generator Differential Relay
41-348.1H
Figure 1. Type SA-1 Generator Differential Relay without Case (Front View)
7
Page 8
41-348.1H
Type SA-1
Generator Differential Relay
Figure 2. Type SA-1 Generator Differential Relay without Case (Rear View)
8
Page 9
Type SA-1 Generator Differential Relay
41-348.1H
Figure 3. Internal Schematic of Type SA-1 Relay 48/125 Vdc
629A406 Sub 15
9
Page 10
41-348.1H
Type SA-1
Generator Differential Relay
10
876A613 Sub 9
Figure 4. Internal Schematic of Type SA-1 Relay 250 Vdc
Page 11
Type SA-1 Generator Differential Relay
41-348.1H
(DESENSITIZED)
TYPE FT-32 CASE
FOR GENERATOR PROTECTION IN
RELAY TYPE SA-1 HIGH SPEED DIFFERENTIAL
Figure 5. Internal Schematic of Desensitized SA-1 Relay
877A847 Sub 8
11
Page 12
41-348.1H
23
R17
Type SA-1
Generator Differential Relay
+
C1
12
762A601 Sub 9
Figure 6. Component Location for 48/125 Vdc
Page 13
Type SA-1 Generator Differential Relay
41-348.1H
*
Denotes Change
867A639 * Sub 5
Figure 7. Component Location for 250 Vdc
13
Page 14
41-348.1H
Type SA-1
Generator Differential Relay
COMPONENT LOCATION
COMPONENT LOCATION
48/125 V
48/125 V
2
2
5
C
C
C
C
1
1
1
1 1
1
3
3
1
1
0
0
C11 & C10 .01 uf 3516A36H03
C11 & C10 .01 uf 3516A36H03 C12 2.0 uf 3509A33H01
C12 2.0 uf 3509A33H01 R15 470 Ohm 187A643H19
R15 470 Ohm 187A643H19
5
4
4
R15
R15
C12
C12
SPK 1584C01G01
SPK 1584C01G01
COMPONENT LOCATION
250 V
2
C
C
1
1 1
3
1
0
5
4
R15
6 7
SPK 1584C01G02
C11 & C10 .01 uf 3516A36H03 R15 470 Ohm 187A643H19
Illustration
3532A07 Sub 2
14
Figure 8. Component Location of the SPK Module
Page 15
Type SA-1 Generator Differential Relay
41-348.1H
Figure 9. External Schematic of Type SA-1 Relay for Generator Protection
775B965 *Sub 4
Figure 10. Reactor Outline
775B982 Sub 1
15
Page 16
41-348.1H
Type SA-1
Generator Differential Relay
NOTE: A - PLACE IT. 1 TO 3 IN IT. 5 FOR SHIPPING
Lead
IT.
1 3.00 .164 - 32 .164 - 32 2 4.00 .164 - 32 .190 - 32 3 3.00 .164 - 32 .190 - 32 4 13.438 .164 - 32 .190 - 32
L
A
SCREW SIZE
AB
Figure 11. Relay and Reactor Interconnection
*
Denotes Change
16
±.156
L
PART
ITEM
NAME 01 LEAD 57Z0301 616 A 63-D-653 2 02 LEAD 57Z0401 622 A 63-D-655 3 03 LEAD 57Z0301 622 A 63-D-655 1 05 BAG 836A618 H04 B 27-D-5478 1
B
STYLE
DWG.
ITEM
GR.
NOTE CODE
ENG.
REF. REQ
775B981 * Sub 5
Page 17
Type SA-1 Generator Differential Relay
41-348.1H
Figure 12. Percentage Slope characteristic at Low Value of Restraint Current
3537A44 Sub 2
17
Page 18
41-348.1H
Type SA-1
Generator Differential Relay
18
878A742 Sub 3
Figure 13. Percentage Slope Characteristic at High Value of Restraint Current
Page 19
Type SA-1 Generator Differential Relay
41-348.1H
Figure 14. Percentage Slope Characteristic of High Value Restraint Current for Desensitized SA-1 Relay
619406 Sub 1
19
Page 20
41-348.1H
Type SA-1
Generator Differential Relay
20
477706 Sub 1
Figure 15. Typical Operation Time Characteristic
Page 21
Type SA-1 Generator Differential Relay
41-348.1H
3537A45 Sub 2
Figure 16. Typical Frequency Response Curve
Figure 17. Typical Frequency Response Curve
184A864 Sub 4
21
Page 22
41-348.1H
Type SA-1
Generator Differential Relay
*
Denotes Change
22
3519A69 * Sub 4
Figure 18. Outline and Drilling Plan for the Type SA-1 Relay in Type FT-32 Case
Page 23
Type SA-1 Generator Differential Relay
41-348.1H
NOTES
23
Page 24
41-348.1H
Type SA-1
Generator Differential Relay
ABB Automation, Inc.
Substation Automation & Protection Division 4300 Coral Ridge Drive Coral Springs, FL 33065 954 752-6700 800 523-2620
24
❖
www.abb.com/papd
ABB Automation, Inc.
Substation Automation & Protection Division 7036 Snowdrift Road, Suite 2 Allentown, PA 18106 610 395-7333 800 634-6005
Loading...