Power supply CP-E 24/10.0
Primary switch mode power supply
Data sheet
Features
쐍
Rated output voltage 24 V DC
쐍
Output voltage adjustable via front-face rotary potentiometer “OUTPUT Adjust”
쐍
Rated output current 10 A
쐍
Rated output power 240 W
쐍
Supply range 115/230 V AC (90-132 V AC, 186-264 V AC, 210-370 V DC), auto select
쐍
Typical effi ciency of 89 %
쐍
Low power dissipation and low heating
쐍
Free convection cooling (no forced cooling with ventilators)
쐍
Ambient temperature range during operation -25...+70 °C
쐍
Open-circuit, overload and short-circuit stable
쐍
Integrated input fuse
쐍
Redundancy unit CP-A RU offering true redundancy, available as accessory
쐍
Signalling contact "13-14" (Relay) for output voltage OK
쐍
LEDs for status indication
Approvals
UL 508, CAN/CSA C22.2 No.14 Approval refers to rated input voltage U
A
UL 60950, CAN/CSA C22.2 No.60950 Approval refers to rated input voltage U
H
GOST
D
IN
IN
햵 OUTPUT OK: green LED -
햵 OUTPUT OK: green LED -
output voltage OK
output voltage OK
햶 OUTPUT LOW: red LED -
햶 OUTPUT LOW: red LED -
output voltage too low
output voltage too low
햷 OUTPUT Adjust:
햷 OUTPUT Adjust:
potentiometer -
potentiometer adjustment of the output
adjustment of the output
voltage
voltage
햸 single/parallel:
햸 single/parallel:
sliding switch -
sliding switch -
adjustment of single or
adjustment of single or
parallel operation
parallel operation
햹 Circuit diagram
햹 Circuit diagram
Marks
CE
a
C-Tick pending
b
Order data
Type Rated input voltage Rated output voltage /
CP-E 24/10.0 115/230 V AC
auto select
current
24 V DC / 10 A 1SVR 427 035 R0000
Order code
Order data - Accessories
Type Description Order code
CP-A RU Redundancy unit
The CP-A RU provides decoupling of two CP-E power supply
units < 48 V and 5 A.
1SVR 427 071 R0000
Application
The primary switch mode power supply offers two voltage input ranges. This enables the supply with AC
or DC. Furthermore it is equipped with two generous capacitors, which ensure mains buffering of at least
30 ms (at 230 V AC). That is why the devices can be used worldwide also in high fl uctuating networks
and battery-powered plants.
1
Power supply CP-E 24/10.0
Primary switch mode power supply
Data sheet
Operating mode
By means of the potentiometer „OUTPUT Adjust“ the output voltage can be adjusted within a range
of 22.5 to 28.5 V DC. Thus, the power supply can be optimally adapted to the application, e.g.
compensating the voltage drop caused by a long line length.
The green LED „OUTPUT OK“ is lightening during proper operation, i.e. when the output voltage is more
than 75 %.
The red LED „OUTPUT LOW“ is lightening when the output voltage is less than 70 % of the rated output
voltage.
Switch „single/parallel“ for selection of single or parallel operation.
Signalling contact 13-14 (max. 60 V DC / 0.3 A) is ON when the output voltage is more than 75 %.
Installation
Mounting
The switch mode power supply can be snapped on a DIN
rail according to EN 50022 as shown in the accompanying
picture. For that the device is set with its mounting rail slide
on the upper edge of the mounting rail and locked by lifting it
downwards.
2CDC 272 017 F0b082CDC 272 017 F0b08
Demounting
Remove the switch mode power supply as shown in the
accompanying picture. For that the latching lever is pulled
downwards by means of the screwdriver. Alternatively you
can press the unlock button to release the device. Then in
both cases the device can be unhinged from the mounting
rail edge and removed.
Mounting position
The devices have to be mounted horizontally with the input
terminals on the bottom. In order to ensure a suffi cient
convection, the minimum distance to other modules should not
be less than 25 mm in vertical and horizontal direction.
2CDC 272 018 F0b082CDC 272 018 F0b08
2CDC 272 020 F0b08
2
Power supply CP-E 24/10.0
Primary switch mode power supply
Data sheet
Installation
Electrical connection
Connect the input terminals L and N. The protective earth conductor PE must be connected. The
installation must be executed acc. to EN 60950, provide a suitable disconnecting device (e. g. line
protection switch) in the supply line. The input side is protected by an internal input fuse.
Rate the lines for the maximum output current (considering the short-circuit current) or provide a
separate fuse protection. We recommend to choose the cable section as large as possible in order to
minimize voltage drops. Observe the polarity. The device is overload, short-circuit and open-circuit proof.
The secondary side of the power supply unit is electrically isolated from the input and internally not
earthed (SELV) and can therefore be earthed by the user according to the needs with L+ or L- (PELV).
Connection diagram
L- L- L+13 14
L+
L- L- L+13 14
L+
L
L
PWM
PWM
N
N
PE
PE
PE N L
PE N L
L+, L- Output voltage
L+
L+
L-
L-
L, N Input voltage
13-14 Signalling contact for output voltage OK
PE Protective earth
2CDC 272 023 F0b08
2CDC 272 023 F0b08
Safety instructions and warnings
The device must be installed by qualifi ed persons only and in accordance with the specifi c national
regulations (e.g., VDE, etc.). The devices are maintenance-free chassis-mounted units.
Disconnect system from supply network!
Before any installation, maintenance or modifi cation work: Disconnect the system from the supply
network and protect against switching on.
Before start of operation:
Attention! Improper installation/operation may impair safety and cause operational diffi culties or
destruction of the unit. Before operation the following must be ensured:
Connect to main according t the specifi c national regulations.
쐍
쐍
Power supply cables and unit must be suffi ciently fused. A disconnecting device has to be provided
for the end product to disengage unit and supply cables from supply mains if required.
The protective earth conductor must be connected to the terminal (Protection class I)
쐍
The secondary side of the power supply unit is not earthed and can be earthed by the user according
쐍
to the needs with L+ or L-.
쐍
Rate the output lines for the output current of the power supply and connect thme with the correct
polarity.
In order to ensure suffi cient air-cooling the distance to other devices has to be considered.
쐍
In operation:
쐍
Do not modify the installation (primary and secondary side)! High current! Risk of electric arcs and
electric shocks (danger to life)!
쐍
Risk of burns: Depending on the operation conditions the enclosure can become very hot.
쐍
The internal fuse is not user-replaceable. If the internal fuse blows, most probably the device is
defective. In this case, an examination of the switch mode power supply by the manufacturer is
necessary.
Attention! High voltage! Danger to life!
The power supplies contain components with high stored energy and circuits with high voltage! Do
not introduce any objects into the unit, and do not open the unit. With some units of this range the
output is capable of providing hazardous energy. Ensure that the service personnel is protected against
inadvertent contact with parts carrying energy.
3