ABB MS132 Data Sheet

Data sheet
Manual motor starter MS132
Manual motor starters are electro­mechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less against short-circuit, overload and phase failures. Fuse less protection with a manual motor starter saves costs, space and ensures a quick reaction under short­circuit condition, by switching off the motor within milliseconds. Fuse less starter combinations are setup together with contactors.
2CDC241020F0009
Description
– Overload protection – trip class 10 – Phase loss sensitivity – Disconnect function – Temperature compensation from -25 … +60 °C – Adjustable current setting for overload protection – Suitable for three- and single-phase application – Trip-free mechanism – Status indication – Clear switch position indication ON/OFF/TRIP – Lockable handle
Approvals
A
cULus UL 508
K
CB scheme
E
CCC
D
GOST-R
GOST-F
ABS
Lloyd’s Register
P
Marks
a
CE
Order data
MS132 screw terminal
Setting range
A
0.10...0.16 MS132-0.16 10A 1SAM350000R1001 1 0.215
0.16...0.25 MS132-0.25 10 1SAM350000R1002 1 0.215
0.25...0.40 MS132-0.4 10 1SAM350000R1003 1 0.215
0.40...0.63 MS132-0.63 10 1SAM350000R1004 1 0.215
0.63...1.00 MS132-1.0 10 1SAM350000R1005 1 0.215
1.00...1.60 MS132-1.6 10 1SAM350000R1006 1 0.265
1.60...2.50 MS132-2.5 10 1SAM350000R1007 1 0.265
2.50...4.00 MS132-4.0 10 1SAM350000R1008 1 0.265
4.00...6.30 MS132-6.3 10 1SAM350000R1009 1 0.265
6.30...10.0 MS132-10 10 1SAM350000R1010 1 0.265
8.00...12.0 MS132-12 10 1SAM350000R1012 1 0.310
10.0...16.0 MS132-16 10 1SAM350000R1011 1 0.310
16.0...20.0 MS132-20 10 1SAM350000R1013 1 0.310
20.0...25.0 MS132-25 10 1SAM350000R1014 1 0.310
25.0...32.0 MS132-32 10 1SAM350000R1015 1 0.310
Note: MS132 with pre-assembled auxiliary contact HKF1-11, please order as follow 1SAM350005Rxxxx
Type Trip
class
Order code
Pack­ing unit
PCE
Weight per PCE
kg
GL
DNV
RINA
Functional description
1
Terminals 1L1, 3L2, 5L3
1
2
3
4
5
6
7
2CDC241020F0009
2
Switch position TRIP
3
Lockable handle
4
Status indication for short-circuit
5
Current setting range
Adjustable current setting for overload protection
6
Test function
7
Terminals 2T1, 4T2, 6T3
Application
The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole protection devices with thermal tripping elements for overload protection and electromagnetic tripping elements for short­circuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and can be used for the manual switching of loads.
The manual motor starters have a setting scale in amperes, which allows the direct adjusting of the device without any additional calculation. In compliance with international and national standards, the setting current is the rated current of the motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current).
Operation mode
Single-phase operation
Wiring diagram
2CDC242023F0009
2CDC242025F0009
2CDC242024F0009
Three-phase operation
2 - 2CDC131021D0201