Data sheet
Manual motor starter MS132
Manual motor starters are electromechanical protection devices for the
main circuit. They are used mainly to
switch motors manually ON/OFF
and protect them fuse less against
short-circuit, overload and phase
failures.
Fuse less protection with a manual
motor starter saves costs, space and
ensures a quick reaction under shortcircuit condition, by switching off the
motor within milliseconds. Fuse less
starter combinations are setup together
with contactors.
2CDC241020F0009
Description
– Overload protection – trip class 10
– Phase loss sensitivity
– Disconnect function
– Temperature compensation from -25 … +60 °C
– Adjustable current setting for overload protection
– Suitable for three- and single-phase application
– Trip-free mechanism
– Status indication
– Clear switch position indication ON/OFF/TRIP
– Lockable handle
Approvals
A
cULus UL 508
K
CB scheme
E
CCC
D
GOST-R
GOST-F
ABS
Lloyd’s Register
P
Marks
a
CE
Order data
MS132 screw terminal
Setting
range
A
0.10...0.16 MS132-0.16 10A 1SAM350000R1001 1 0.215
0.16...0.25 MS132-0.25 10 1SAM350000R1002 1 0.215
0.25...0.40 MS132-0.4 10 1SAM350000R1003 1 0.215
0.40...0.63 MS132-0.63 10 1SAM350000R1004 1 0.215
0.63...1.00 MS132-1.0 10 1SAM350000R1005 1 0.215
1.00...1.60 MS132-1.6 10 1SAM350000R1006 1 0.265
1.60...2.50 MS132-2.5 10 1SAM350000R1007 1 0.265
2.50...4.00 MS132-4.0 10 1SAM350000R1008 1 0.265
4.00...6.30 MS132-6.3 10 1SAM350000R1009 1 0.265
6.30...10.0 MS132-10 10 1SAM350000R1010 1 0.265
8.00...12.0 MS132-12 10 1SAM350000R1012 1 0.310
10.0...16.0 MS132-16 10 1SAM350000R1011 1 0.310
16.0...20.0 MS132-20 10 1SAM350000R1013 1 0.310
20.0...25.0 MS132-25 10 1SAM350000R1014 1 0.310
25.0...32.0 MS132-32 10 1SAM350000R1015 1 0.310
Note: MS132 with pre-assembled auxiliary contact HKF1-11,
please order as follow 1SAM350005Rxxxx
Type Trip
class
Order code
Packing unit
PCE
Weight
per PCE
kg
GL
DNV
RINA
Functional description
1
Terminals 1L1, 3L2, 5L3
1
2
3
4
5
6
7
2CDC241020F0009
2
Switch position TRIP
3
Lockable handle
4
Status indication for short-circuit
5
Current setting range
Adjustable current setting for overload protection
6
Test function
7
Terminals 2T1, 4T2, 6T3
Application
The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole
protection devices with thermal tripping elements for overload protection and electromagnetic tripping elements for shortcircuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and
can be used for the manual switching of loads.
The manual motor starters have a setting scale in amperes, which allows the direct adjusting of the device without any
additional calculation. In compliance with international and national standards, the setting current is the rated current of the
motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current).
Operation mode
Single-phase operation
Wiring diagram
2CDC242023F0009
2CDC242025F0009
2CDC242024F0009
Three-phase operation
2 - 2CDC131021D0201