ABB C505 User Manual

User Guide
IM/C505_6
Control
1
/2 DIN Advanced Process Controller
C505
IT
ABB
The Company
We are an established world force in the design and manufacture of instrumentation for industrial process control, flow measurement, gas and liquid analysis and environmental applications.
As a part of ABB, a world leader in process automation technology, we offer customers application expertise, service and support worldwide.
We are committed to teamwork, high quality manufacturing, advanced technology and unrivalled service and support.
The quality, accuracy and performance of the Company’s products result from over 100 years experience, combined with a continuous program of innovative design and development to incorporate the latest technology.
The UKAS Calibration Laboratory No. 0255 is just one of the ten flow calibration plants operated by the Company, and is indicative of our dedication to quality and accuracy.
R
E
G
R
I
S
E
T
Cert. No. Q5907
EN 29001 (ISO 9001)
Lenno, Italy – Cert. No. 9/90A
Use of Instructions
Warning.
An instruction that draws attention to the risk of injury or death.
Caution.
An instruction that draws attention to the risk of damage to the product, process or surroundings.
Although
Warning hazards are related to personal injury, and Caution hazards are associated with equipment or
property damage, it must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process system performance leading to personal injury or death. Therefore, comply fully with all
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of the Technical Communications Department.
Warning and Caution notices.
Note.
Clarification of an instruction or additional information.
Information.
Further reference for more detailed information or technical details.
D
E
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the information given.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets (where applicable) may be obtained from the Company address on the back cover, together with servicing and spares information.
GETTING STARTED
Step 3 – Setting the Parameters (Fig. GS.1)
A
Pow er-up the instrument. Press the and keys simultaneously and hold f or 3 seconds to advance directly to Level 6 – Basic Configuration.
B
Set the appropriate application template, output type and control action. Use the
key to advance between frames and upper and keys to adjust the
default values – see Section 4.2 for further information.
Note. When the output type has been selected, the availab le inputs and outputs
default to the settings shown in Table B on the rear fold-out.
C
If you are not using 4 to 20mA inputs, then select Level 7 using the upper and
keys and set up Analog Inputs I/P1 to I/P3 to suit your process – see Section 4.3.
D
Controller templates only: Select Level 2 using the upper and keys and set the tune parameters:
Analog or Motorized Valve Control – set the Proportional, Integral and
Derivative terms.
Time Proportioning Control – set the Cycle Time, Hysteresis and P, I & D Terms
Heat/Cool Outputs – set the points at which the Output 1 and Output 2
become active.
E
Press to return to the Operating displays.
F
Adjust the set point to the required value.
Your COMMANDER 500 is now in operation
50.1
50.5
50
A
+
LEV.6 APPL
LEV.7 INPt
LEV2 tUNE
F
E
50.1
50.5
B
t.APP
C D
50
01.SL
O.tYP ANLG
C.ACt rEV
FrEJ
50.1
50.5
50
Note. With the above configuration, no alarms or limits have been set and advanced functionality (gain scheduling, set point sources etc.) has not been enabled.
50
Fig. GS.1 Setting the Parameters
GETTING STARTED
The COMMANDER 500 can be configured and made ready for operation in three easy steps. This 'Getting Started' guide provides an overview of these steps and, where necessary, refers to the relevant section of the manual.
Step 1 – Decide on the Application Template and the
Output Configuration required Step 2 – Connect the process inputs and outputs Step 3 – Power up the instrument, set the template number and the output
configuration details
Your COMMANDER 500 is now ready for operation
Step 1 – Application Template and Output Configuration
Choose the Template which best suits your application from the list in Table A, located on the rear fold-out.
Choose the Control Output Type required from the list of options in Table B on the rear foldout.
Step 2 – Electrical Connections
Using the labels on the back of the instrument as a guide, connect the process inputs, outputs and power supplies. Refer to Section 5.2 of this man ual (Electrical Installation) for more information.
Continued…

OVERVIEW

This manual is divided into 5 sections which contain all the information needed to install, configure, commission and operate the COMMANDER 505 Advanced Process Controller. Each section is identified clearly by a symbol as shown in Fig. 1.
8
Displays and Controls
• Displays and Function Keys
• LED Indication
• Error Messages
Operator Mode (Level 1)
• Single Loop Controller
• Motorized Valve Controller
• Auto/Manual & Backup Stations
• Feedforward Controllers
• Cascade Controllers
• Ratio Station/Controller
Set Up Mode (Levels 2 to 5)
• Level 2 – Tuning
• Level 3 – Set Points
• Level 4 – Alarm Trip Points
• Level 5 – Valve Setup
Fig. 1 Overview of Contents
Getting Started
Configuration Mode (Levels 6 to E)
• Level 6 – Basic Configuration
• Level 7 – Input Configuration
• Level 8 – Alarm Configuration
• Level 9 – Set Point Configuration
• Level A – Control Configuration
• Level B – Operator Configuration
• Level C – Output Configuration
• Level D – Serial Communications
• Level E – System Calibration
Installation
• Siting
• Mounting
• Electrical Connections
Table A – Template Applications
B – Output Sources
Getting Started
Shunt Resistors
2 x 100
(+1 optional)
Process Labels
x3
Fig. 3 Accessories
Fig. 2 Foldouts
Panel Clamps
x2
Table C – Digital Sources
D – Analog Sources
CJ Sensor
x1
(+1 optional)
1
CONTENTS
Section Page
OVERVIEW....................................................1
1 DISPLAYS AND FUNCTION KEYS ........3
1.1 Introduction .......................................3
1.2 Use of Function Keys .......................4
1.3 Secret-til-Lit Indicators......................8
1.4 Character Set ....................................8
1.5 Error Messages ................................9
1.6 Processor Watchdog ......................10
1.7 Loop Break Monitor ........................10
1.8 Glossary of Abbreviations...............10
2 OPERATOR LEVEL............................... 11
2.1 Introduction ..................................... 11
2.2 Single Loop Controller
(Templates 1 and 2)........................1 2
2.3 Auto/Manual Station
(Templates 3 and 4)........................1 4
2.4 Analog Backup
(Templates 5 and 6)........................1 6
2.5 Indicator/Manual Loader Station
(Templates 7 and 8)........................1 8
2.6 Single Loop with Feedforward
(Templates 9 and 10)......................19
2.7 Cascade Control
(Templates 11 and 12) .................... 21
2.8 Cascade with Feedforward
(Template 13) ..................................24
2.9 Ratio Controller
(Templates 14 and 15)....................26
2.10Ratio Station
(Templates 16 and 17)....................27
2.11 Heat/Cool Output Types .................28
2.12Motorized Valve Output Types .......29
2.13Auto-tune ........................................30
2.14Control Efficiency Monitor ..............33
3 SET UP MODE .......................................36
3.1 Introduction .....................................36
3.2 Level 2 – Tune ................................ 37
3.3 Level 3 – Set Points........................41
3.4 Level 4 – Alarm Trip Points.............43
3.5 Level 5 – Valve Setup.....................44
4 CONFIGURATION MODE ..................... 47
4.1 Introduction...................................... 47
4.2 Level 6 – Basic Configuration ........48
4.3 Level 7 – Analog Inputs ..................52
4.4 Level 8 – Alarms .............................56
4.5 Level 9 – Set Point Configuration...60
4.6 Level A – Control Configuration......63
4.7 Level B – Operator Configuration...68
4.8 Level C – Output Assignment.........70
4.9 Level D – Serial Communications ..76
4.10Level E – Calibration ......................77
2
Section Page
5 I NSTALLATION......................................80
5.1 Mechanical Installation ...................80
5.2 Electrical Installation .......................85
5.3 Relays ............................................. 87
5.4 Digital Output ..................................87
5.5 Control or Retransmission
Analog Output .................................87
5.6 Motorized Valve Connections .........88
5.7 Input Connections ...........................89
5.8 Output Connections ........................89
5.9 Power Supply Connections.............89
SPECIFICATION .........................................90
APPENDIX A – CONTROL TEMPLATES ..94
A1 Single Loop Controller
(Templates 1 and 2) ........................94
A2 Auto/Manual Station and
Analog backup Station.................... 95
A3 Indicator/Manual Loader Station
(Templates 7 and 8) ........................98
A4 Single Loop Controller with
Feedforward (Templates 9 and 10). 99
A5 Cascade Controllers
(Templates 11 and 12)..................100
A6 Cascade Controller with
Feedforward (Template 13)...........101
A7 Ratio Controller
(Templates 14 and 15)..................102
A8 Ratio Station
(Templates 16 and 17)..................103
APPENDIX B – COMMANDER
CONFIGURATION EDITOR......................104
B1 Introduction ...................................104
B2 Analog Input Customization ......... 104
B3 Programmable Maths Blocks........104
B4 Logic Equations ............................104
B5 Process Alarm Customization ......104
B6 Real Time Alarms .........................104
B7 Delay Timers .................................105
B8 Custom Linearizers.......................105
B9 Template Customization ...............105
B10 Connecting the COMMANDER
PC Configurator ............................105
FRAMES INDEX .......................................106
INDEX ......................................................109

1 DISPLAYS AND FUNCTION KEYS

1.1 Introduction
The COMMANDER 500 front panel displays, function keys and LED indicators are shown in Fig. 1.1.
COMMANDER 500
100
58.8
Raise
Alarm
Acknowledge
80
60
40
L
20
M OP1 OP2 FF
0
Function Keys
62.4
MST SLV
R
L
15.0
R
Lower
Parameter Advance
Local/Remote
Fig. 1.1 Front Panel Displays and Function Keys
L
R
L
Up Down
Auto/manual
3
…1 DISPLAYS AND FUNCTION KEYS
1.2 Use of Function Keys
A – Raise and Lower Keys
bIAS
+
50.0
Use to change/set a parameter value… …move between levelsand…
B – Up and Down Keys
700
Use to adjust the output value…
C – Parameter Advance Key
LEV2 tUnE
CYCl
51.0
49.0
+
710
690
and…
Frame 1 (top of level)
Frame 2
…move between frames within a Setup or Configuration level. Any changes made on the current frame are stored when the next frame is selected.
5.0
2.00
2.01
LEV1
OPEr
LEV2 tUnE
CYCl
5.0
LEVx 1001 1002 1003
Frame 1 (top of level)
Frame 2
Press and hold
LEV2
tUnE
Note. This key also stores any changes made in the previous frame
D – Auto/Manual Key
4
Use to advance to the next frame within a level…
Auto Manual
450.2
500.0
70
Use to select Auto or Manual control mode
Fig. 1.2a Use of Function Keys
or…
M
…select the top (LEV.x) frame from within a level
450.2
500.0
70
Process Variable Control Set Point
Control Output (%)
…1.2 Use of Function Keys
E – Alarm Acknowledgement
Any active,
unacknowledged
alarms
All active
alarms
acknowledged
(Flashing)
450.2
500.0
70
200.3
1.HP1 2003
1HP1
ACt
ACK
LAt
or
CLr
ACK
LAt
or
200.3
2.xxx
ACt
1
2
3
4
Unacknowledged
alarms only
450.2
500.0
70
(On continuously) (Off)
No active
alarms present
Pressing again acknowledges the displayed alarm. Lower display changes to reflect new status.
3
Next active and unacknowledged alarm is displayed. If no alarms are active, the next enabled alarm is displayed.
4
The first active and unacknowledged alarm is displayed (or if no alarms are active, the first enabled alarm is displayed)
1
The lower display shows alarm status:
ACt
Alarm active and unacknowledged
ACK
Alarm active and acknowledged
CLr
Cleared or Inactive alarm
LAt
Unacknowledged latched alarm
2
Note. The time of the power failure
PF.t, is shown in the set point display.
High Process, PV High Output Low Process, PV Low Output High Latch, PV Power Failure Time Low Latch, PV Maths Block 1 High High Deviation Maths Block 1 Low Low Deviation Maths Block 2 High High Process I/P1 Maths Block 2 Low Low Process I/P1 Maths Block 3 High High Process I/P2 Maths Block 3 Low
Low Process I/P2 Maths Block 4 High High Process I/P3 Maths Block 4 Low Low Process I/P3
HPV HO LPV LO HLP PF.t LLP Hb1 Hd Lb1 Ld Hb2 HP1 Lb2 LP1 Hb3 HP2 Lb3 LP2 Hb4 HP3 Lb4 LP3
Note. If no alarms have been enabled in the Set Up level, pressing
the key has no effect.
1 DISPLAYS AND FUNCTION KEYS…
Fig. 1.2b Use of Function Keys
5
…1 DISPLAYS AND FUNCTION KEYS
…1.2 Use of Function Keys
F – Local / Remote Key
Changing between Local and Remote Set Points
450.2
1
500.0
70
1
Process variable and local set point (ratio) displayed on red and green displays. Remote set point (ratio) value is displayed. The value and symbol flash to
2
2
450.2
L
R
L
400.0
R
4
L
R
L
3
450.2
400.0
R
R
indicate local set point (ratio) still selected.
3
Remote set point (ratio) selected.
4
Remote selection aborted.
Note. When an Analog Backup Station template is selected, the key
L
is used to switch between local and remote mode – see Sections 2.4 and 4.2.
Selecting Local Set Points 1 to 4
450.2
1
350.0
70
Process variable and local set point 1 displayed.
1
Process variable and local set point 2 displayed
2
Process variable and local set point 3 displayed
3 4
Process variable and local set point 4 displayed
450.2
L
R
L
400.0
2
450.2
L
R
L
475.0
450.2
L
R
L
475.0
43
Selecting Master and Slave Set Points – Cascade Mode
Abbreviations are
detailed in Section 1.8.
Slave PID
Control Loop
When the SLV indicator (see Fig 1.3) is lit, the key can be used to switch between the local slave set point and the cascade
LSPt RSPt
M.PV S.PV
1
L
R
L
M.SPt
Master
Control Loop
450.2
When the MST indicator
350.0
(see Fig 1.3) is lit, the
L
R
L
key can be used to switch between the Master
70
local and remote set points
PID
Local S.SPt
M.OP x CrtO + CbIA
L
R
L
S.SPt
450.2
2
350.0
70
slave set point generated from the master output.
R
L
L
R
L
OP1
L
R
L
Fig. 1.2c Use of Function Keys
6
…1.2 Use of Function Keys
G – Short-cut Keys
1 DISPLAYS AND FUNCTION KEYS…
+
Press simultaneously and hold for 3 seconds
LEVA
CntL
LEV1
OPEr
Press to move from anywhere in the Configuration level to the first frame in the Operator level
450.2
350.0
Press and hold to move from the Operator Level to the Security Code Frame and then to other levels:
70
Tune Level – See Section 2.13.3 Set Up Level – See Fig. 3.1 Configuration Level – See Fig. 4.1
COdE
0
LEV6
APPL
450.2
350.0
Press to move from anywhere in the Operator or Setup levels to the first page of the Configuration
70
Note. This Short-cut key operates only when the configuration password is set to ‘0’
level
Fig. 1.2d Use of Function Keys
7
…1 DISPLAYS AND FUNCTION KEYS
1.3 Secret-til-Lit Indicators
450.2
350.0
MST SLV
R
450.2
350.0
150
150
M OP1 OP2 FF
MST
SLV
R
M
OP1
OP2
FF
Flashing
One or more alarms active and unacknowledged
A – Upper Display
Flashing
Autotune in progress
ON
All active alarms acknowledged
Master controller parameters displayed
Slave controller parameters displayed
Remote or Cascade set point in use
ON
Manual control selected
Output 1 (heat) value displayed
Output 2 (cool) value displayed
Feedforward disturbance variable displayed
Valve opening Valve stopped Valve closing
B – Lower Display
OFF
No alarms active
Local set point in use
OFF
Auto control selected
1.4 Character Set – Fig. 1.4
A B C D E F G H
8
Fig. 1.3 Secret-til-lit Indicators
I
A b C d E F G H
Fig. 1.4 Character Set
I
J
J
K
K
L
L
M
M
N
N
or
n
O
O
P
P
R
r
S
S
T
t
U
U
V
V
Y
Y
1.5 Error Messages
1 DISPLAYS AND FUNCTION KEYS…
Display
70
70
70
70
70
70
70
or
CAL Err
Err NVx
A-d Err
9999
t.Err 1
CJ.F 1
rSP.F 9999
rAt.F 9999
Error/Action Calibration Error
Turn mains power off and on again (if the error persists contact the Customer Support Organization).
Non-volatile Memory Error
x = 1, 2: Motherboard Memory x = 3: Option Board Memory Turn mains power off and on again (if the error persists, check configuration/setup settings).
A to D Converter Fault
The analog to digital converter is not communicating correctly.
Input Value Over/Under Range
Auto-tune Error
The number displayed indicates the type of error present – see Table 2.1 on page 30.
Cold Junction Failed
Cold junction sensor is faulty or has not been fitted correctly.
Remote Set Point or External Ratio Failed. Remote set point input
value is over or under-range. Only appears if the remote set point (or external ratio) is displayed or in use.
To clear the display:
Press the key
Press the key
Contact the Customer Support Organization
Restore valid input
Press the key
Check connections or replace if faulty.
Restore valid input
StK
999
Valve Sticking
Motorized valve not moving at the speed expected. Valve may be sticking.
Position Feedback Fail
Input value is over- or under-range. Only appears if output type set to 'PFb' – motorized valve with feebac k.
Check that the correct Regulator Travel Time has been set – see Section 3.5. Check the valve.
Restore valid input
9
…1 DISPLAYS AND FUNCTION KEYS
1.6 Processor Watchdog
The instrument's processor activity is monitored by an independent watchdog device. When the output of the watchdog is assigned to a relay or digital output, the relay/digital output de-energizes if the instrument fails to function correctly.
1.7 Loop Break Monitor
Both analog outputs are monitored continuously to detect a loop break. A warning signal or other action can be initiated by assigning the loop break signals to relays or digital outputs.
1.8 Glossary of Abbreviations
noitaiverbbAnoitpircseDnoitaiverbbAnoitpircseD
VPelbairaVssecorP1id1tupnIlatigiD
tPSLeulaVtnioPteSlacoL2id2tupnIlatigiD 1PSLeulaV1tnioPteSlacoL3id3tupnIlatigiD 2PSLeulaV2tnioPteSlacoL4id4tupnIlatigiD 3PSLeulaV3tnioPteSlacoL1oa1tuptuOgolanA 4PSLeulaV4tnioPteSlacoL2oa2tuptuOgolanA
tPSCeulaVtnioPteSlortnoC1od1tuptuOlatigiD
tPSReulaVtnioPteSetomeR2od2tuptuOlatigiD
P/ODIPmhtiroglADIPehtfotuptuOVP.MelbairaVssecorPretsaM 1PO)taeh(1tuptuOrellortnoCtPS.MtnioPteSlortnoCretsaM 2PO)looc(2tuptuOrellortnoCPO.MtuptuODIPretsaM
1P/I1tupnIgolanAtPS.StnioPteSevalS 2P/I2tupnIgolanAVP.SelbairaVssecorPevalS 3P/I3tupnIgolanAVWelbairaVdliW
VDelbairaVecnabrutsiD
10
Table 1.1 Glossary of Abbreviations

2 OPERATOR LEVEL

2.1 Introduction
The Operator level (Level 1) is the normal day-to-day mode of the COMMANDER 500. This section describes the operator facilities available on each frame depending on the control template and output type selected.
The template types detailed in this section are:
Single loop controller
Auto/Manual station
Analog backup station
Indicator/manual loader station
Single loop with feedforward control
Cascade control
Cascade with feedforward
Ratio controller
Ratio station Note. Only the frames relevant to the selected template are displayed – see Section 4.
In addition, frames used to view the Control Efficiency Monitor and operate motorized valve and heat/ cool output types are also described.
C501
01.SL
2001
01
Fig. 2.1 Power-up Displays
Model – C501
Template (see rear fold-out)
Software series
Software version
11
2 OPERATOR LEVEL
2.2 Single Loop Controller (Templates 1 and 2)
The single loop controller is a basic feedback control system using three-term PID or on/off control with either a local set point (template 1) or remote set point (template 2).
L
Local Set Point
LSPt
LR
Remote Set Point Input
•1
I/P2
Process Variable Input
I/P1
•1 Template 2 Only
I/P2 x rAtO + bIAS
RSPt
CSPt
PV
Manual Output
PID
Control Loop
Fig. 2.2 Single Loop Controller
PID O/P
Control Output
OP1
12
2.2 Single Loop Controller (Templates 1 and 2)
2 OPERATOR LEVEL
Set Point
Process Variable
Set Point
Process Variable
OP1
OP1
•1
Process Variable
450.2
500.0
70
rAtO
•1
•2
Control Set Point
['SPLO' to 'SPHI' – see Section 4.5] Adjustable in Local Control Only
Control Output
[0 to 100% (digital/relay outputs), –10 to 110% (analog outputs)] Adjustable in manual mode only. With on/off control selected, 0% = control output off, 100% = control output on. In manual mode, intermediate values can be selected. These use 'time proportioning' with a 60s cycle time, e.g. 25% = 15s on, 45s off.
Remote Set Point Ratio
1.000
[0.001 to 9.999] Remote set point value = (ratio x remote set point input) + bias
70
Set Point Process
Variable
bIAS
1.000
•3
Remote Set Point Bias
[In engineering units]
70
OP1
Return to top of page
•1 With the Ramping Set Point function enabled (see Section 3.3, Set Points/ Ramp Rate), the bargraph shows the actual (ramping) set point value and the digital display shows the target set point value.
•2 Only displayed if template 2 selected and Ratio Display is enabled – see Section 4.2, Basic Configuration and Section 4.7, Operator Configuration.
•3 Only displayed if template 2 selected and Bias Display is enabled – see Section 4.2, Basic Configuration and Section 4.7, Operator Configuration.
13
2 OPERATOR LEVEL
2.3 Auto/Manual Station (Templates 3 and 4)
Note. Refer also to Appendix A2.1 – Series and Parallel Operation.
The auto/manual station provides a backup for a master controller. In normal operation the COMMANDER 500’s analog output follows the master controller’s output value. A fault in the master system can be identified either by detecting a low signal on the master output (template 3) or via a digital signal (template 4). When a fault is detected the COMMANDER 500 goes into manual mode with its output either set to the last valid master output value or to a configured output value – see Section 4.6, Control Configuration/ Configured Output 1. When the master output is restored or the digital input returns to its inactive state, the COMMANDER 500 switches back to auto mode.
Note. The Alarm A1 Trip value must be set when using template 3.
Manual Output
Master Output
I/P2
Digital Select
di1
•1 Template 3 Only
•2 Template 4 Only
Low Signal Select
(Alarm A1)
•1
•2
Fig. 2.3 Auto/Manual Station
Analog Output
ao1
Auto / Manual
Select
14
2.3 Auto/Manual Station (Templates 3 and 4)
2 OPERATOR LEVEL
Master output
Process Variable
•1
•2
Low Master Output Value
•3
Digital Input Active
Master output
Process Variable
or
or
55.0
50.0
70
55.5
50.0
•1
or
•2
Restored Master Output
or
•3
Digital Input Inactive
Auto Mode
Process Variable Master Output (I/P2)
Control Output = Master Output
[Master Output, 0 to 100%]
Manual Mode
50
M
•1 In template 4 the Auto/Manual switch is overridden by the digital input signal.
•2 Template 3 only – see Section 4.2, Basic Configuration/ Template Application.
•3 Template 4 only – see Section 4.2, Basic Configuration/ Template Application.
Control Output (under COMMANDER 500 control)
[0 to 100%]
15
2 OPERATOR LEVEL
2.4 Analog Backup (Templates 5 and 6)
Note. Refer also to Appendix A2.1 – Series and Parallel Operation.
The analog backup station provides a backup for a master controller. In normal operation (remote control mode selected) the COMMANDER 500’s current output follows the master controller’s output value. A fault in the master system can be identified either by detecting a low signal on the master output (template 5) or via a digital signal (template 6). When a fault is detected the COMMANDER 500 switches into local control mode and the process is controlled by the PID output of the COMMANDER 500. The COMMANDER 500 PID algorithm tracks the master output value continuously in order to ensure bumpless transfer from remote to local mode operation. When the master output is restored or the digital input returns to its inactive state, the COMMANDER 500 switches back to remote control mode.
Note. The Alarm A1 Trip value must be set when using template 5.
Manual Output
Local Set Point
LSPt
Process Variable
I/P1
Master Output
I/P2
Digital Select
di1
•1 Template 5 Only
•2 Template 6 Only
PID
Control Loop
PV
Low Signal Select
(Alarm 1)
L
LR
Fig. 2.4 Analog Backup Station
•1
•2
Local/
Remote
Select
Analog Output
ao1
16
2.4 Analog Backup (Templates 5 and 6)
2 OPERATOR LEVEL
Set Point
Process Variable
•1
•2
Set Point
Process Variable
R
OP1
or
Low Master Output Value
or
Digital Input Active
55.0
50.0
70
55.5
50.0
or
•1
Restored Master Output
or
•2
Digital Input Inactive
Remote Mode
Process Variable
Set Point
['SPLO' to 'SPHI' – see Section 4.5]
Control Output = Master Output
[Master Output, 0 to 100%]
Local Mode
50
OP1
•1 Template 5 only – see Section 4.2, Basic Configuration/ Template Application.
•2 Template 6 only – see Section 4.2, Basic Configuration/ Template Application.
Control Output (under COMMANDER 500 control)
[0 to 100%] Adjustable in Manual Mode only.
17
2 OPERATOR LEVEL
2.5 Indicator/Manual Loader Station (Templates 7 and 8)
One or two process variables can be displayed on the digital and bargraph displays. If the control output is assigned to an analog output, the lower display indicates its value which can be adjusted by the user.
Process Variable (PV2)
Process Variable (PV1)
OP1
•1
55.0
50.0
•1
50
•2
Process Variable PV1
Process Variable PV2
Output Value
[–10 to 110%]
•1 Only displayed if template 8 selected – see Section 4.2, Basic Configuration/ Template Application.
•2 Only displayed if control output type is 'analog' (output is assigned to Analog Output 1).
18
2 OPERATOR LEVEL
2.6 Single Loop with Feedforward (Templates 9 and 10)
These templates provide three-term PID control with feedforward. The disturbance variable is weighted by the feedforward gain (FFGn) and the feedforward bias (FFbS) values and added to the controller output value.
L
Local Set Point
LSPt
LR
Manual Output
Remote Set Point input
•1 PV input
Feedforward Disturbance Variable
I/P2
•1 Template 10 Only
I/P3
I/P1
RSPt x rAtO + bIAS
Control Set Point
Process
•1
450.2
500.0
Variable
OP1
Control Set Point
Process
450.2
500.0
Variable
CSPt
PID O/P +
(DV x FFGn + FFbS)
DV x FFGn + FFbS
MPV
PID
Control Loop
FFGN = 0
Fig. 2.5 Single Loop Controller with Feedforward
Process Variable
Control Set Point
•1
['SPLO' to 'SPHI' – see Section 4.5] Adjustable in Local control only.
Control Output
70
[0 to 100%] Adjustable in Manual control only.
Feedforward
Note. To disable feedforward action (e.g.
during system tuning), set the Feedforward Gain parameter to 0FF – see Section 3.2, Tune/Level 2 – Tune.
OP1
50
[0 to 100%]
FF
•1 With the Ramping Set Point function enabled (see Section 3.3, Set Points/ Ramp Rate), the bargraph shows the actual (ramping) set point value and the digital display shows the target set point value.
Feedforward disturbance variable signal.
Continued…
19
2 OPERATOR LEVEL
2.6 Single Loop with Feedforward (Templates 9 and 10)
Set Point Process
Variable
Set Point Process
Variable
OP1
OP1
rAtO
1.000
70
bIAS
0. 0
70
•1
•1
Remote Set Point Ratio
[0.001 to 9.999] Remote set point value = (ratio x remote set point input) + bias
Remote Set Point Bias
[In engineering units]
Return to Process Variable display
•1 Only displayed if template 10 selected – see Section 4.2, Basic Configuration/Template Application and Section 4.7, Operator Configuration/Operator Ratio Display and Operator Bias Display.
20
2 OPERATOR LEVEL
2.7 Cascade Control (Templates 11 and 12)
For cascade control, two internally-linked PID controllers are used, with the first (master) PID controller providing the set point for the second (slave) controller. The master output is weighted using the cascade ratio (C.rtO) and bias (C.bIA) values to create the slave set point value.
Local Set Point
LSPt
Remote Set Point input
•1
I/P3
Master PV Input
I/P1
Slave PV Input
I/P2
•1 Template 12 Only
Master Set Point (MSPt)
MST
Master Process Variable (MPV)
OP1
RSPt x
RSPt
rAtO + bIAS
•1
L
LR
MPV
SPV
450.2
500.0
70
Slave Set Point
SSPt
Master
Control Loop
PID
M.OP
M.OP x CrtO + CbIA
Fig. 2.6 Cascade Controller
Master Process Variable (MPV)
•1
Master Control Set Point (MSPt)
['SPLO' to 'SPHI' – see Section 4.5] Adjustable in local control only.
Slave Control Output
[0 to 100%] (–10 to 110% for analog outputs) Adjustable in manual mode only.
to change between local/remote set point values.
L
LR
SSPt
Manual Output
Slave PID
Control Loop
Note. With template 12 the
L
R
L
key can be used
OP1
Slave Set Point (SSPt)
450.2
500.0
Slave Process Variable (SPV)
Slave Set Point (SSPt)
['SPLO' to 'SPHI' – see Section 4.5]
Slave Process Variable (SPV)
SLV
70
OP1
Adjustable in manual or local slave set point modes only.
L
R
Note. The
L
key can be used in this frame to
change between cascade and local slave set points.
Continued…
•1 With the Ramping Set Point function enabled (see Section 3.3, Set Points/ Ramp Rate), the bargraph shows the actual (ramping) set point value and the digital display shows the target set point value.
21
2 OPERATOR LEVEL
2.7 Cascade Control (Templates 11 and 12)
Master Set Point (MSPt)
Master Process Variable (MPV)
Master Set Point (MSPt)
Master Process Variable (MPV)
Slave Set Point (SSPt)
Slave Process Variable (SPV)
MST
OP1
MST
OP1
SLV
OP1
rAtO
1.000
70
bIAS
0. 0
70
C.rtO
1.000
70
•1
•1
•2
Remote Set Point Ratio
[0.001 to 9.999] Master remote set point value = (ratio x remote set point input) + bias
Remote Set Point Bias
[in engineering units]
Cascade Slave Set Point Ratio
[0.001 to 9.999] Slave set point (SSPt) value = (ratio x master ouput) + bias [in engineering units]
Continued…
•1 Only displayed if template 12 selected and ratio/bias display enabled – see Section 4.2, Basic Configuration and Section 4.7, Operator Configuration.
•2 Only displayed if ratio/bias display enabled – see Section 4.7, Operator Configuration.
22
2.7 Cascade Control (Templates 11 and 12)
2 OPERATOR LEVEL
Slave Set Point (SSPt)
Slave Process Variable (SPV)
SLV
OP1
C.bIA
0. 0
70
•1
Cascade Slave Set Point Bias
[In engineering units]
Return to Master Process Variable (MPV) display
•1 Only displayed if ratio/bias display enabled – see Section 4.7, Operator Configuration.
23
2 OPERATOR LEVEL
2.8 Cascade with Feedforward (Template 13)
For cascade control, two internally-linked PID controllers are used, with the first (master) PID controller providing the set point for the second (slave) controller. The feedforward disturbance variable signal is added to the master output (slave set point). The disturbance signal is weighted by the feedforward gain (FFGn) and the feedforward bias (FFbs) values.
Local Set Point
LSPt
MSPt
Master PV Input
I/P1
Feedforward Disturbance Variable
I/P3
Slave PV Input
I/P2
Master Set Point (MSPt)
MST
MPV
SPV
•1
450.2
500.0
Master Process Variable (MPV)
OP1
L
R
L
FFGn
= 0
SSPt
Master
PID
Control Loop
DV x FFGn + FFbS
Local Slave Set Point
SSPt
M.OP x
CrtO + CbiA
Fig. 2.7 Cascade Controller with Feedforward
Master Process Variable (MPV)
•1
Master Control Set Point (MSPt)
['SPLO' to 'SPHI' – see Section 4.5] Adjustable in Local control only
Slave Control Output
70
[0 to 100% (–10 to 110% for analog outputs)] Adjustable in Manual mode only.
Manual Output
Slave
PID
Control Loop
OP1
Slave Set Point (SSPt)
1997 2000
Slave Process Variable (SPV)
Slave Set Point (SSPt)
['SPLO' to 'SPHI' – see Section 4.5] Adjustable in Manual mode only
L
R
Note. The
L
key can be used in this frame to
change between cascade and local slave set points.
Slave Process Variable
SLV
70
(SPV)
OP1
Continued…
•1 With the Ramping Set Point function enabled (see Section 3.3, Set Points/ Ramp Rate), the bargraph shows the actual (ramping) set point value and the digital display shows the target set point value.
24
2.8 Cascade with Feedforward (Template 13)
2 OPERATOR LEVEL
Master Set Point (MSPt)
Master Process Variable (MPV)
Slave Set Point (SSPt)
Slave Process Variable (SPV)
Slave Set Point (SSPt)
Slave Process Variable (SPV)
MST
FF
SLV
OP1
SLV
OP1
450.2
500.0
50
C.rtO
1.000
70
C.bIA
0. 0
70
Feedforward Disturbance Variable
Note. To disable feedforward action (e.g.
during system tuning), set the Feedforward Gain parameter to 0FF – see Section 3.2, Tune.
[0 to 100%] Feedforward disturbance variable input.
•1
•1
Cascade Slave Set Point Ratio
[0.001 to 9.999] Slave set point (CSP2) value = (ratio x master ouput) + bias [in engineering units]
Cascade Slave Set Point Bias
[In engineering units]
Return to Master Process Variable (MPV) display.
•1 Only displayed if enabled in Level B, Operator Configuration – see Section 4.7.
25
2 OPERATOR LEVEL
2.9 Ratio Controller (Templates 14 and 15)
Ratio control enables a controlled process variable to be maintained automatically in definite proportion to another variable known as the wild variable. The wild variable, weighted by ratio (rAtO) and bias (bIAS), values forms the control set point for the process variable.
L
LR
Local Ratio
•1
Remote Ratio
I/P3
Wild Variable
I/P2
Process Variable input
I/P1
•1 Template 15 only
Control Set Point
Process Variable (PV)
OP1
Control Set Point
Process Variable (PV)
55.0
50.0
70
bIAS
0. 0
70
rAtO
WV
WV
rAtO +bIAS
x
Fig. 2.8 Ratio Controller
•1
Manual Output
Control
CSPt
PV
PID
Control Loop
PID O/P
Output
OP1
Actual Ratio
Process Variable (PV) – Bias
=
Wild Variable (WV)
Desired Ratio
Adjustable in Local control only. Control Set Point = (WV x Ratio) + Bias
Control Output
[0 to 100% (–10 to 110% for analog outputs)] Adjustable in manual mode only.
Bias
[in engineering units]
OP1
Return to Actual Ratio display.
•1 Only displayed if enabled in Level B, Operator Configuration – see Section 4.7.
26
Loading...
+ 90 hidden pages