AF mechanically interlocked, reversing, 3-pole
For applications up to 700 hp, 600 kW
Electronic AC/DC operated coils
Across the line
Contactors
1
Electrical ratings 12
AC general
purpose
ratings (A)
CSA C22.2 No.14, 60947-4-1-07
Maximum
motor
switching
current
(A)
UL 508, 60947-4-1A
AC motor ratings, breaking all lines,
three phase, 50/60 Hz (hp)
200...
208V
220...
240V
R
440...
480V
550...
Mechanically interlocked Reversing
Standard
600V
auxiliary
contacts
NO NC NO NC
Catalog
number
3
Standard
auxiliary
contacts
25 9 2 2 5 7.5 2 2 AF09M-30-22-Δ 2 2 AF09R-30-22-Δ
28 11 3 3 7.5 10 2 2 AF12M-30-22-Δ 2 2 AF12R-30-22-Δ
30 17 5 5 10 15 2 2 AF16M-30-22-Δ 2 2 AF16R-30-22-Δ
Catalog
number
3
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4
20...60V DC 11 72 -
24...60V AC 11 - -
AF09…AF30 AF50…AF300 AF400…AF750
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
24...60V DC - - 68
48...130V AC/DC 12 69 69
100...250V AC/DC 13 70 70
250...500V AC/DC 14 - 71
Example(s):
24V DC input voltage: AF16M-30-22-11
120V AC input voltage: AF300R-30-11-70
1 For selection purposes; for complete electrical ratings, see Technical Data.
2 For ratings according to IEC/EN 60947-4-1, refer to AF non-reversing selection table or Technical Data.
3 AF09R(M)…AF30R(M) assembled using connection clips, AF50R(M)…AF750R(M) mounted on common baseplate.
4 AC coil input voltage(s) at 50/60 Hz unless specied.
Low Voltage Products & Systems 1.15
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A