Ie / Rated operational current AC-8a
Rated operational power AC-8a
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500V AC - gG type fuse100 A125 A160 A160 A200 A
Rated short-time withstand current Icw
at 40°C ambient temperature,
in free air from a cold state
Maximum breaking capacity
cos φ = 0.45
Power dissipation per pole
Max. electrical switching frequency
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50Hz or 1800 r.p.m, 60Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
(3) On request.
1500 r.p.m. 50Hz
1800 r.p.m. 60Hz
3-phase motors
AC / DC operated
θ ≤ 40°C
θ ≤ 60°C
θ ≤ 70°C
220-230-240V
380-400V
415V
440V
500V
690V
220-230-240V
380-400V
415V
440V
500V
690V
1s
10s
30s
1 min
15 min
at 440V
at 690V
Ie / AC-1
Ie / AC-3
AC-1
AC-3
AC-2, AC-4
AF40AF52AF65AF80AF96
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
690 V
50 / 60 Hz
105 A105 A105 A130 A130 A
70 A100 A105 A125 A130 A
60 A80 A90 A100 A105 A
50 A70 A80 A85 A90 A
40 A53 A65 A80 A96 A
40 A53 A65 A80 A96 A
40 A53 A65 A80 A96 A
40 A53 A65 A80 A96 A
35 A45 A55 A65 A80 A
25 A35 A39 A49 A57 A
1000 A1000 A1000 A1200 A1200 A
600 A600 A600 A780 A780 A
350 A350 A350 A450 A450 A
250 A250 A250 A300 A300 A
110 A110 A110 A140 A140 A
(3)
(3)
3 W6.3 W7 W7.6 W8.2 W
1 W1.7 W2.7 W3 W4.5 W
600 cycles/h
1200 cycles/h
150 cycles/h
2.62 | Motor protection and controlMotor protection and control | 2.63
2.62 | Motor protection and controlMotor protection and control | 2.63
AF40 ... AF96 3-pole contactors
Technical data
Main pole - Utilization characteristics according to UL / NEMA / CSA
Contactor types
1
StandardsUL 60947-1 / 60947-4-1A and CSA 60947-1 / 60947-4-1A
Maximum operational voltage600 V
NEMA size2--3-
NEMA continuous amp rating
2
NEMA maximum horse power ratings
1-phase, 60Hz
NEMA maximum horse power ratings
3-phase, 60Hz
UL / CSA general use rating
600V AC60 A80 A90 A105 A115 A
With conductor cross-sectional areaAWG 6AWG 4AWG 3AWG 2AWG 2
UL / CSA maximum 1-phase motor rating
Full load current
Horse power rating
UL / CSA maximum 3-phase motor rating
Full load current (1)
Horse power rating (1)
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
High fault current100 kA
Fuse rating150 A150 A150 A200 A200 A
Fuse type, 600VJ
Maximum electrical switching frequency
For general use 600 cycles/h
For motor use1200 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50Hz or 1800 r.p.m, 60Hz, 3-phase motors, see "Motor rated operational powers and currents".
AC / DC operated
Thermal current
115V AC
230V AC
200V AC
230V AC
460V AC
575V AC
120V AC
240V AC
120V AC
240V AC
200-208V AC
220-240V AC
440-480V AC
550-600V AC
200-208V AC
220-240V AC
440-480V AC
550-600V AC
34 A34 A56 A80 A80 A
40 A50 A68 A68 A88 A
3 hp3 hp5 hp7-1/2 hp7-1/2 hp
7-1/2 hp10 hp15 hp15 hp20 hp
32.2 A48.3 A62.1 A78.2 A92 A
42 A54 A68 A80 A80 A
40 A52 A65 A77 A77 A
41 A52 A62 A77 A77 A
10 hp15 hp20 hp25 hp30 hp
15 hp20 hp25 hp30 hp30 hp
30 hp40 hp50 hp60 hp60 hp
40 hp50 hp60 hp75 hp75 hp
General technical data
Contactor types
Rated insulation voltage Ui
acc. to IEC 60947-4-1690 V1000 V
acc. to UL / CSA600 V
Rated impulse withstand voltage Uimp.6 kV8 kV
Electromagnetic compatibilityDevices complying with IEC 60947-1 / EN 60947-1
Ambient air temperature close to contactor
OperationFitted with thermal overload relay(2)
Storage-60...+80 °C
Climatic withstandCategory B according to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)3000 m
Mechanical durability
Number of operating cycles10 millions operating cycles
Maximum switching frequency3600 cycles/h
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
(2) On request.
2.66 | Motor protection and controlMotor protection and control | 2.67
2.66 | Motor protection and controlMotor protection and control | 2.67
Without thermal overload relay-40...+70 °C
AC / DC operated
Shock direction
AF40AF52AF65AF80AF96
1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
AF40 ... AF96 3-pole contactors
Pos. 2
Technical data
Magnet system characteristics
1
Contactor types
Coil operating limits
acc. to IEC 60947-4-1
AC control voltage 50/60Hz
Rated control circuit voltage Uc24...500 V AC
2
Coil consumption
DC control voltage
Rated control circuit voltage Uc20...500 V DC
Coil consumption
PLC-output controlDrop-out voltage≤ 60 % of Uc min.
Voltage sag immunity
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminalsIP10
Coil terminalsIP20
Built-in auxiliary terminalsIP20
Screw terminalsDelivered in open position, screws of unused terminals must be tightened
Main terminalsM6M8
Coil terminalsM3.5
Built-in auxiliary terminalsM3.5
1 or 2 x
Screwdriver type
Screwdriver type
Screwdriver type
AWG 18...14
Flat Ø 6.5 / Pozidriv 2Hexagon socket (s = 4 mm)
Flat Ø 5.5 / Pozidriv 2
Flat Ø 5.5 / Pozidriv 2
2.74 | Motor protection and controlMotor protection and control | 2.75
2.74 | Motor protection and controlMotor protection and control | 2.75
AF09 ... AF96 3-pole contactors
Technical data
Built-in auxiliary contacts according to IEC
Contactor types
Rated operational voltage Ue max.
Rated frequency (without derating)
Conventional free air thermal current Ith - θ ≤ 40 °C
Ie / Rated operational current AC-15
acc. to IEC 60947-5-1
Making capacity AC-15
Breaking capacity AC-15
Ie / Rated operational current DC-13
acc. to IEC 60947-5-1
Short-circuit protection device gG type fuse
Rated short-time withstand current Icw
Minimum switching capacity
with failure rate acc. to IEC 60947-5-410
Non-overlapping time between N.O. and N.C. contacts
Power dissipation per pole at 6 A
Max. electrical switching frequency
Mechanically linked contactsBuilt-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA4, CAL4, CAT4
acc. to annex L of IEC 60947-5-1
Mirror contactsBuilt-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA4, CAL4, CAT4 aux. contact blocks)
acc. to annex F of IEC 60947-4-1
AC / DC operated
24-127 V 50/60 Hz
220-240 V 50/60 Hz
400-440 V 50/60 Hz
500 V 50/60 Hz
690 V 50/60 Hz
24 V DC
48 V DC
72 V DC
110 V DC
125 V DC
220 V DC
250 V DC
400 V DC
500 V DC
600 V DC
for 1.0 s
for 0.1 s
AC-15
DC-13
AF09AF12AF16AF26AF30AF38AF40AF52AF65AF80AF96
690 V
50 / 60 Hz
16 A
6 A
4 A
3 A
2 A
2 A
10 x Ie AC-15 acc. to IEC 60947-5-1
10 x Ie AC-15 acc. to IEC 60947-5-1
6 A / 144 W
2.8 A / 134 W
1 A / 72 W
0.55 A / 60 W
0.55 A / 69 W
0.27 A / 60 W
0.27 A / 68 W
0.15 A / 60 W
0.13 A / 65 W
0.1 A / 60 W
10 A
100 A
140 A
12 V / 3 mA
-7
≥ 2 ms
0.1 W
1200 cycles/h
900 cycles/h
aux. contact blocks) are mechanically linked contacts.
are mirror contacts.
1
2
Built-in auxiliary contacts according to UL / CSA
Contactor types
Max. operational voltage
Pilot duty
AC thermal rated current10 A
AC maximum volt-ampere making7200 VA
AC maximum volt-ampere breaking720 VA
DC thermal rated current2.5 A
DC maximum volt-ampere making-breaking69 VA
AC / DC operated
AF09AF12AF16AF26AF30AF38AF40AF52AF65AF80AF96
600 V AC, 600 V DC
A600, Q600