without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse
Rated short-time withstand current Icw
at 40 °C ambient temperature,
in free air from a cold state
63 A100 A125 A160 A160 A200 A
1 s
600 A1000 A1320 A
10 s
400 A650 A800 A
30 s
225 A370 A500 A
1 min
150 A250 A350 A
15 min
65 A110 A135 A135 A160 A175 A
Maximum breaking capacity
cos φ = 0.45
(cos φ = 0.35 for Ie > 100 A)
Power dissipation per pole
Max. electrical switching frequency
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
(3) Unauthorized for TAL.., TAE.. contactors.
(4) AC-3, 690 V values for AL40 and TAL40 contactors: 18.5 kW, Ie = 21 A.
(5) Max. breaking capacity for AL40 and TAL40 contactors: 470 A at 440 V, 175 A at 690 V.
(6) AF contactors excluded.
at 440 V
at 690 V
Ie / AC-1
Ie / AC-3
AC-1
AC-3
AC-2, AC-4
820 A (5)1300 A1160 A
340 A (5)630 A800 A
3 W5 W6.5 W7 W6.5 W7.5 W
1.3 W1.3 W1.5 W2 W2.7 W3.6 W
600 cycles/h600 cycles/h (300 for AF.., AE.., TAE..)300 cycles/h
1200 cycles/h600 cycles/h (300 for AF.., AE.., TAE..)300 cycles/h
300 cycles/h150 cycles/h
1.84 Low Voltage Products & Systems
1SXU000023C0202 Rev. AABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
UL/NEMA/CSA Technical data
C1
Across the line
1
Contactors
Main pole - Utilization characteristics according to UL / NEMA / CSA
Contactor types
Standards
Max. operational voltage
NEMA size
NEMA continuous amp rating
NEMA maximum horse power ratings 1-phase, 60 Hz
NEMA maximum horse power ratings 3-phase, 60 Hz
UL / CSA general use rating
600 V AC60 A80 A90 A105 A125 A150 A
With conductor cross-sectional areaAWG 6AWG 4AWG 3AWG 2AWG 1AWG 1/0
UL / CSA maximum 1-phase motor rating
Full load current
Horse power rating
UL / CSA maximum 3-phase motor rating
Full load current (1)
Horse power rating (1)
Max. electrical switching frequency
For general use600 cycles/h600 cycles/h (300 for AF.., AE..)300 cycles/h
For motor use1200 cycles/h 600 cycles/h (300 for AF.., AE..)300 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.
8 kV
AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
55 °C max. for TAL.., and TAE.. contactor
acc. to IEC 60068-2-30 and 60068-2-11
)
acc. to IEC 60068-2-30
UTE C 63-100 specification II
3000 m
1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position (2)
20 g
10 g closed position / 5 g open position
15 g
20 g
20 g
For AL40, TAL40
A : 20 g closed position / 10 g open position
B1 : 15 g closed position / 5 g open position
B2 : 10 g closed position / 10 g open position
C1 : 20 g closed position / 8 g open position
C2 : 14 g closed position / 8 g open position
1.88 Low Voltage Products & Systems
1SXU000023C0202 Rev. AABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
General technical data
Pos
Across the line
1
Contactors
Magnet system characteristics
Contactor types
Coil operating limits
acc. to IEC 60947-4-1
AC control voltage
50/60 Hz
DC control voltage
Drop-out voltage
Voltage sag immunity
acc. to SEMI F47
Dips withstand
Operating time
Between coil energization and:
Between coil de-energization and:
Rated control circuit voltage Uc48…250 V 50/60 Hz
Coil consumption
Rated control circuit voltage Uc20…250 V DC
Coil consumption