ABB AC500 Technical Data

04
96 MAIN CATALOG PLC AUTOMATION
AC500
Technical data
AC500 CPUs
Typ e PM572 PM573-ETH PM582 PM583-ETH PM585-ETH
Supply voltage 24 V DC Current consumption on 24 V DC
Min. (module alone) 0.050 A 0.110 A 0.050 A 0.110 A 0.150 A
Max. (all couplers and I/Os) 0.750 A 0.810 A 0.750 A 0.810 A 0.850 A
User program memory – Flash EPROM and R AM 128 kB 512 kB 512 kB 1024 kB 1024 kB
Integrated user data memory 128 kB thereof
User Flashdisk (Data-storage, programm access or also external with FTP)
Plug-in memory card Depending on SD -Card used : no SD-HC card allowed, use MC502 accessory Web ser ver's data for user R AM disk 1 024 kB 4 096 kB 4 096 kB
Data buffering battery
Real-time clock (with battery back-up)
Cycle time for 1 instruction (minimum)
Binary 0.06 µs 0.06 µs 0.05 µs 0.05 µs 0.00 4 µs Word 0.09 µs 0.09 µs 0.06 µs 0.06 µs 0.008 µs Floating-point 0.7 µs 0.7 µs 0.5 µs 0.5 µs 0.008 µs
Max. number of centralized inputs/outputs
Max. number of extension modules on I/O bus up to max. 10 (S500 and/or S50 0-eCo modules allowed)
Digital inputs/outputs 320/320 Analog inputs/outputs 160/160
Max. number of decentralized inputs/outputs depends on the used standard Fieldbus (1)
Program execution
Cyclical / Time controlled / Multi task ing
User program protection by password
Internal interfaces
COM1
RS232 / RS485 conf igurable Connection (on terminal bases or CPU module) pluggable spring terminal block, use TK502 cable in accessory Programming, Modbus RTU, A SCII, CS31 master
COM2
RS232 / RS485 conf igurable
Connection (on terminal bases or CPU module) D-Sub 9 female, use TK501 cable in accessory
Programming, Modbus RTU, ASCII
FieldBusPlug
Serial neutral interface Connection (on terminal bases) M12 male, 5 pole Functions programming cable UTF-21-FBP, slave communication depending on FieldBusPlug used
Ethernet
Ethernet connection (on terminal bases) RJ45 RJ45 RJ45
Ethernet functions: Programming, TCP/IP, UDP/IP,
Modbus TCP, integrated Web server, IEC60870-5-104
remote control protocol, MQTT, SNTP (simple Network
Time Protocol), DHCP, FTP server HTTP, SMTP, PING
Ethernet based Fieldbus
Ethernet connection (on CPU module)
12 kB saved –
//
(PROFIBUS DP, CANopen, Dev iceNet)
416 kB thereof 288 kB saved
1024 kB thereof 288 kB saved
2560 kB thereof 1536 kB saved
Downloadable protocols like: PROFINET IO RT Controller / EtherCAT Master
CPU display LC display and 8 function keys
Function RUN / STOP, status, diagnosis
LEDs for various status display Run, Stop, Error
Timer/Counter unlimited/unlimited
Approvals See detailed page 238 or www.abb.com/plc
(1) e.g. C S31 Fieldbu s: up to 31 stations with up to 120 DIs / 1 20 DOs or up to 32 A Is / 32 AOs per stat ion.
Loading...