3M Water Filtration Products User Manual

3M™ Water Filtration Products RO Membrane Cartridge Change-out Instructions (HFRO-500)
FOR ScaleGard
TM
HP Reverse Osmosis System
Explanation of Signal Word Consequences
WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury and/or property damage.
NOTICE Indicates hazardous situation which, if not avoided, may result in property damage.
WARNING
Check with your local public works department for plumbing codes. You must follow their guidelines as you install the water ltration system.
Your water ltration system will withstand up to 125 pounds per square inch (psi) water pressure.
To reduce the risk associated with choking:
DO NOT allow children under 3 years of age to have access to small parts during the installation of this product.
To reduce the risk of serious injury associated with the potential ingestion of chemicals or contaminants:
Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system.
Flush RO Cartridge: Before use, you must ush the RO cartridge as specied in the installation instructions, and discard any water generated until ush is complete. Failure to do so could cause serious injury from exposure to chemicals that can be extracted from the RO membrane during this initial ush.
Sanitize and Flush Tank: Before use, you must sanitize and ush the hold tank as specied in the installation instructions. Sanitizing the hold tank minimizes the risk for exposure to contaminants. Failure to ush the hold with water after sanitizing could cause serious injury from exposure to sanitizer present.
NOTICE
To reduce the risk associated with property damage due to water leakage or ooding:
Read and follow Use Instructions provided with the original system prior to use of this replacement cartridge.
The pre-lter and post-lter cartridges MUST be changed every 12 months, or sooner if the rated capacity is achieved or a noticeable reduction in ow occurs.
The RO membrane cartridge MUST be changed every 24 months, or sooner if a noticeable reduction in ow occurs.
Failure to replace the lters and RO membrane cartridges at recommended intervals may lead to reduced lter performance and failure, causing property damage from water leakage or ooding.
Protect from freezing, remove all cartridges when temperatures are expected to drop below 40°F (4.4°C).
DO NOT install systems in areas where ambient temperatures may go above 100°F (37.8°C).
DO NOT install on hot water supply lines. The maximum operating water temperature of this lter system is 100°F (37.8°C).
DO NOT install if water pressure exceeds 125 psi (862 kPa). Contact a plumbing professional if you are uncertain how to check your water pressure.
IMPORTANT NOTE:
The RO membrane cartridges have green labels and will only t into the head on the right side of the manifold (head has a green 3M label).
Shut Off Procedure:
RO membrane cartridge MUST be changed every 24 months or sooner. The pre-lter and post lter cartridges MUST be changed every 12 months or sooner.
1. Unplug system from the electrical outlet, which will shutoff feedwater to RO unit.
2. Conrm the operating pressure gauge (left) decreases to 0 psi. Note: Tank pressure gauge (right) will not decrease from the observed pressure.
RO Membrane Cartridge (green label) Replacement:
1. Remove the reject tubing from the RO membrane cartridge. (See Figure 1).
2. Push and hold yellow tab to release RO membrane cartridge locking mechanism while simultaneously rotating RO membrane cartridge to the left.
3. Using both hands and holding the RO membrane cartridge from the bottom, rotate the RO membrane cartridge a quarter turn to the left and gently pull down. NOTE: A small amount of water will drain from manifold as cartridge is removed.
4. Remove sanitary cap from new RO membrane cartridge. Ensure o-rings are seated into their grooves. Remove drain tting plug from new RO membrane cartridge. Install with a quarter turn to the right until RO membrane cartridge comes to a complete stop. NOTE: RO membrane cartridges are keyed to t in proper location only.
5. Insert new ow control into the elbow (included with new RO membrane cartridge). Install this sub assembly into the drain tting (cartridge bottom) See Figure 3.
6. Connect reject line into elbow.
7. IMPORTANT: Complete System Start Up and Membrane Flushing procedure before system is brought back into use. See page 2.
Instructions continued on next page.
System Start Up
1. Turn on the feedwater supply.
2. Open unit inlet shutoff valve.
3. Power the unit by plugging into electrical outlet.
4. Open Pre-Filter ush valve to vent air from system and ush for 10 gallons (approximately 5 minutes).
5. Close Pre-Filter ush valve. The unit operating pressure gauge (left gauge) should read between 110-120 psi. (See Operating Pressure instructions to adjust)
6. Complete blending valve adjustment procedure below. (See instructions below)
7. Close the blend line shut off valve. (Figure 2, #1)
8. Allow storage tank to ll until the RO system turns OFF on full tank (See chart). Tank operating pressure for the 110-120VAC version is ON at 40 psi (276 kPa, 2.76 bar) and OFF at 60 psi (414 kPa, 4.14 bar) (right gauge). Tank operating pressure for the 220-240VAC is ON at 50 psi (345 kPa,
3.45 bar) and OFF at 70 psi (483 kPa, 4.83 bar).
9. Flush membrane by opening tank line sample valve and empty storage tank to drain. Operate the system for at least 24 hours to ush the RO membrane. Discharge all water generated during the ushing procedure to drain. Close the tank line sample valve after ushing is complete.
10. Sanitize the storage tank and RO system according to the storage tank and RO system sanitizing instructions on page 3.
11. Open the blend line shut off valve (if product water blending is desired). Allow storage tank to rell. System is now ready for use.
Required (Sold Separately)
Part Number Pressure Volume
5598408 20 gallons (76 liters) 0.6 hours
5598409 40 gallons (151 liters) 1.2 hours
Figure 1 (Reset Button)
Reset
Button
Approximate
Time to Fill
Start Up Test Checklist
Close the tank shut off valve, open the tank line sample valve.
• Pump turns on √
• Water will ow thru the tank line sample valve and drain line
Keep the tank shut off valve closed and close the tank line sample valve.
• Pump turns off √
• Water will stop owing from the drain line. √
• The operating pressure gauge will read 0 psi (0 kPa) at this point. √
• Tank pressure gauge will read 60 psi (414 kPa, 4.14 bar) for 110-120 VAC systems and 70 psi (483 kPa, 4.83 bar) for 220-240 VAC systems
Open the tank line sample valve.
• Pump will turn on. √
• Tank pressure gauge will read 0 psi (0 kPa). √
• Permeate being rinsed for rst 25 seconds √
• After 30 seconds of operation, check production rate. √
• After 30 seconds of operation, check operating pressure. The operating pressure gauge should read 110-120 psi. √
• After 30 seconds of operation, check TDS reductions.
Close the tank line sample valve and open the tank shut off valve. Allow storage tank to ll.
• Verify the tank pressure gauge increases to 60 psi (414 kPa, 4.14 bar) for 110-120 VAC systems and 70 psi (483 kPa, 4.83 bar) for 220-240 VAC systems
• Verify the pump turns off and the drain line ow stops.
Blending Valve Adjustment Instructions:
IMPORTANT NOTES:
• Typical TDS (Total Dissolved Solids) values for coffee are 80-200 ppm (parts per million) and occasionally lower for espresso, depending upon taste preference. Typical TDS valves for steam and combi ovens are less than 50ppm.
• The blending valve should be set at start-up and checked periodically. This valve is a precision metering valve that has a lock nut.
• To set blending valve use TDS monitor set in the "out" position.
1. Open the blend line shut off valve.
2. Allow the unit to run for 2 minutes.
3. To adjust blending, rotate the blending valve to the left (counterclockwise) to increase the product water TDS and to the right (clockwise) to decrease the product water TDS (See Figure 2 item #2 below). The blending valve should be opened intermittently a quarter turn at a time. Check the TDS after each incremental adjustment and again two (2) minutes after the desired TDS value is reached. Re-adjust and check, as needed. (See Figure 2-item #2 below)
4. Lock the blending valve using the lock nut.
5. After product water TDS is set, it should be checked periodically during operation to conrm it is at the desired level.
IMPORTANT NOTE: The TDS Monitor is push-button operated and requires two (2) 357A batteries. (Included in TDS meter)
Loading...
+ 2 hidden pages