Sanyo Quick Connect Guide
|
Indoor Unit Model |
|
|
Outdoor Unit Model |
|
SPW 1:1 Inverter 185 H |
|
|
Standard PAC SPW CR 184 GVH56B |
|
|
|
|
|
|
|
|
PIPING |
|
|
|
|
|
|
|
SUCTION |
|
1/2" |
|
|
|
|
|
|
|
LIQUID |
|
1/4" |
|
|
|
|
|
|
|
GAS PRE CHARGE LENGTH |
|
|
30m |
|
|
|
|
|
|
ADDITIONAL CHARGE |
|
|
20 g/m |
|
|
|
|
|
|
MAXIMUM PIPING LENGTH |
|
|
40m |
|
|
|
|
|
|
|
INTERCONNECTING WIRING |
||
|
|
|
|
|
|
SUGGESTED CABLE SIZE |
|
|
0.75 mm (Shielded) |
|
|
|
|
|
|
NUMBER OF CORES |
|
2 |
|
|
|
|
||
|
|
POWER SUPPLY WIRING |
||
|
|
|
|
|
|
INDOOR UNIT POWER SUPPLY |
|
|
5a Single Phase |
|
|
|
|
|
|
OUTDOOR UNIT POWER SUPPLY |
|
|
16a Single Phase |
|
|
|
|
|
|
|
REMOTE CONTROLLER WIRING |
||
|
|
|
|
|
|
SUGGESTED CABLE SIZE |
|
|
0.75 mm (Shielded) |
|
|
|
|
|
|
NUMBER OF CORES |
|
2 |
|
|
|
|
|
|
|
|
WIRING DIAGRAM |
DOWNLOADS
Installation Manual |
Technical Data & Service Manual |
|
|
|
|
Sanyo Quick Connect Guide
|
Indoor Unit Model |
|
|
Outdoor Unit Model |
|
SPW 1:1 Inverter 255 H |
|
|
Standard PAC SPW CR 254 GVH56B / GVH8B |
|
|
|
|
|
|
|
|
PIPING |
|
|
|
|
|
|
|
SUCTION |
|
5/8" |
|
|
|
|
|
|
|
LIQUID |
|
3/8" |
|
|
|
|
|
|
|
GAS PRE CHARGE LENGTH |
|
|
30m |
|
|
|
|
|
|
ADDITIONAL CHARGE |
|
|
40 g/m |
|
|
|
|
|
|
MAXIMUM PIPING LENGTH |
|
|
50m |
|
|
|
|
|
|
|
INTERCONNECTING WIRING |
||
|
|
|
|
|
|
SUGGESTED CABLE SIZE |
|
|
0.75 mm (Shielded) |
|
|
|
|
|
|
NUMBER OF CORES |
|
2 |
|
|
|
|
||
|
|
POWER SUPPLY WIRING |
||
|
|
|
|
|
|
INDOOR UNIT POWER SUPPLY |
|
|
5a Single Phase |
|
|
|
|
|
|
OUTDOOR UNIT POWER SUPPLY |
|
|
GVH56B 20a Single Phase - GVH8B 10a Three Phase |
|
|
|
|
|
|
|
REMOTE CONTROLLER WIRING |
||
|
|
|
|
|
|
SUGGESTED CABLE SIZE |
|
|
0.75 mm (Shielded) |
|
|
|
|
|
|
NUMBER OF CORES |
|
2 |
|
|
|
|
|
|
|
|
WIRING DIAGRAM |
DOWNLOADS
Installation Manual |
Technical Data & Service Manual |
|
|
|
|
Sanyo Quick Connect Guide
|
Indoor Unit Model |
|
|
Outdoor Unit Model |
|
SPW 1:1 Inverter 365 H |
|
|
Standard PAC SPW CR 364 GVH56B / GVH8B |
|
|
|
|
|
|
|
|
PIPING |
|
|
|
|
|
|
|
SUCTION |
|
5/8" |
|
|
|
|
|
|
|
LIQUID |
|
3/8" |
|
|
|
|
|
|
|
GAS PRE CHARGE LENGTH |
|
|
30m |
|
|
|
|
|
|
ADDITIONAL CHARGE |
|
|
40 g/m |
|
|
|
|
|
|
MAXIMUM PIPING LENGTH |
|
|
50m |
|
|
|
|
|
|
|
INTERCONNECTING WIRING |
||
|
|
|
|
|
|
SUGGESTED CABLE SIZE |
|
|
0.75 mm (Shielded) |
|
|
|
|
|
|
NUMBER OF CORES |
|
2 |
|
|
|
|
||
|
|
POWER SUPPLY WIRING |
||
|
|
|
|
|
|
INDOOR UNIT POWER SUPPLY |
|
|
5a Single Phase |
|
|
|
|
|
|
OUTDOOR UNIT POWER SUPPLY |
|
|
GVH56B 25a Single Phase - GVH8B 10a Three Phase |
|
|
|
|
|
|
|
REMOTE CONTROLLER WIRING |
||
|
|
|
|
|
|
SUGGESTED CABLE SIZE |
|
|
0.75 mm (Shielded) |
|
|
|
|
|
|
NUMBER OF CORES |
|
2 |
|
|
|
|
|
|
|
|
WIRING DIAGRAM |
DOWNLOADS
Installation Manual |
Technical Data & Service Manual |
|
|
|
|