ZKaccess C3-200 Installation Manual

Page 1
www.zkteco.com
Page 2
Safety Precautions
Product Contents
Product
PIN Diagram
indicators
Product Dimension
Installation of Panel with Casing
Wire Legend
Power
Wiring Diagram
WEIGAND Connection
Exit button Connection
Lock connection
Door
Sensor Connection
Aux. Input Connection
Aux. Output Connection
Ethernet Connection
RS485 Connection
DIP switch settings
Electrical
Specifications
Troubleshooting
Specification
s
1
02 04
06 06
07
08 09 10
11
11
12 12 14
14 15
16
17 18
19 20
Page 3
1
2
Safety Precautions
Do not install the device in a
place subject to direct sun light, humidity, dust or soot.
Do not place a magnet near the product. Magnetic objects such as magnet, CRT, TV, monitor or speaker may damage the device.
Do not place the device next to heating equipment
Be careful not to let liquid like water, drinks or chemicals leak inside the device.
Clean the device often to remove
dust on it
01 02 03
04 05 06
Do not let children touch the
device without supervision.
The list below is to keep user’s safety and prevent any loss. Please read carefully before installation.
Page 4
3
Safety Precautions
The list below is to keep user’s safety and prevent any loss. Please read carefully before installation.
Do not drop the device.
Do not use the device for any other purpose than specified.
Do not disassemble, repair or alter the device.
07
08
In cleaning, do not splash water on the device but wipe it out with smooth cloth or towel.
09
Contact your nearest dealer in case of a problem.
Do not damage the device
10
11 12
Page 5
4
Product Contents
Basic Contents
C3-200
Wall mounting screws – 2 pcs. Wall Plugs– 2 pcs. Surge Suppressing Diode– 4 pcs.
screw driver – 2 pcs.
Software CD C3 installation guide
Page 6
5
Product Contents
Optional accessories
Weigand Card Reader Prox Card
Card enroller
Door Sensor
K1-1 Exit Button
Alarm C3 Metal Case
RS485 convertor
Page 7
6
Product PIN Diagram
#2 Door Card
Reader 2
#2 Door Card
Reader 1
#1 Door Card
Reader1
#1 Door Exit
Button
Aux Input 4
Aux Input 1
SD Card Slot
LINK LED
ACT LED
Ethernet Port
DIP Switch
PC RS485 Port
Aux Output 1
Aux Output 2
Lock Power
C3 Power
LED indicators
LINK (Green)
LED solid green indicates TCP/IP communication is normal
ACT (Yellow)
Flashing LED indicates data communication is in progress
PC RS485 (Yellow & Green)
Flashing LED is sending or data in communication progress
POWER (Red)
Flashing LED indicates the panel is powered on.
RUN (Green)
Flashing LED indicates that panel is in normal working state
CARD
(Yellow)
Flashing LED indicates that
the card is read by the panel.
Reserved
485 LED
Status LED
#1 Lock Sensor
#1 Door Lock
#2 Lock Sensor
#1 Door Lock
#1 Door Card
Reader2
#2 Door Exit
Button
Page 8
7
C3-200
Product Dimension
Dimension(L*W):203.2× 106 (mm)
6.30 ×4.17inches
160mm
(6.30in.)
106mm
(4.17in.)
C3-Casing
400mm
(15.7in.)
330mm
(13.0in.)
330mm
(13.0in.)
90.5mm
(3.56in.)
Dimensions(L*W*H): 400 *90.5*330(mm)
15.7× 13.0× 3.56(inches)
Page 9
8
Installation of Panel & Case
Metal Case
Heat dissipation Hole
Cable Conduit
Box Lock Hole
Power Supply
Backup Battery
C3 Panel
Thread Hole
Wires need to be passed through this conduit
Mounting the case on the wall
Page 10
Wire Legend
9
Detector Infrared sensors #1Exit Switch #1Card Reader
#2 K1-1 Exit Switch
#2 Card Reader
12V
Power Supply
Normal Close Lock
Normal Open Lock
Alarm
RS485 Convertor
LAN Cable
Floodlight
12V DC
Power
DC
Page 11
Power wiring diagram
10
AC
AC
Switching power supply
C3-200
AC
AC
Switching power supply
C3-200
Backup Battery
+
-
Without
Backup Battery
With
Backup Battery
110-220V
110-220V
Page 12
Weigand Connection
11
Weigand Card Reader
Exit Button Connection
Beeper
Green LED
Weigand D1
Weigand D0
GND
DC+(6-14V)
BUT
GND
DV12V+
DV12V-
NO
COM
NC
separate power supply
Notice
ZK ABK Exit Button
K1-1 Exit Switch
Page 13
12
Lock Connection
Built-in Power Supply
Built-in Power Supply
Sensor
Sensor
GND
12V DC
12V DC
GND
Sensor
Sensor
GND
12V DC
12V DC
GND
FR107
FR107
For Normally Open Lock
For Normally Close Lock
Page 14
Lock Connection
13
Switching Wet Contact to Dry Contact
Important Notes:
C3-200 is set to supply lock power by default from external power supply , If you want to use built-in
power supply , you must do the following:
1. Select the wanted lock relay and find its jumpers
2. Take off the jumpers and change to
3. Connect the lock as shown in the diagram below
Steps:
C3-200
Select one Relay
FR107
GND
12V DC
SEN SEN GND 12V DC
4 Lock Relays
Default setting
1
5
Take off jumpers
Jumpers Plug Jumpers
Changed setting
5
1
Connecting a lock with external power supply
Page 15
14
Aux. I/O connection
Aux. Input Connection
Aux. output Connection
COM
NO NC
GND
12V DC
COM
NO NC
GND
12V DC
Page 16
15
Ethernet Connection
Direct connection
Important Notes:
1. Both 10Base-T and 100Base-T are supported
2. This cable distance must be less than 100 meters or 330 ft.
3. For cables length of more than 100m. use HUB to amplify the signal
TCP/IP
CR10 Card Issuer
The CR10 is connected to the server using USB connection.
To connect C3-200 with a PC directly, connect both devices with a straight network cable. As the C3-200 supports auto MDI/MDIX , it
is not necessary to use a crossover type cable.
CR10 Card Issuer
C3-200
C3-200
Page 17
16
RS485 Connection
Important Notes
#1 C3-200
#63 C3-200
RS485-
RS485+ GND
1. RS485 communication wires should be shielded or twisted pair calble. RS485 communication wires should be connected in a bus cascade instead of in a star form, to achieve a better shielding effect by reducing signal
reflection during communications.
2. A single 485 bus can be connected with 63 access control panels at the most, but preferably less than 32 panels should be connected.
3. To eliminate signal attenuation in communication cables and suppress interference, if the bus is longer than 200 meters, set the number 8 DIP switch to the ON position. This is equivalent to a parallel connection of one
120ohm resistance between the 485+ and 485- lines.
Distance
More than 200 meters
#1 C3-200
#* C3-200
Do's and Dont's for RS 485 connection
Page 18
17
DIP Switch Setting
Introduction
RS485 Address
1. Number 1-6 are reserved to set the device number for RS485 communication. The code is binary, and the numbering starts from left to
right. When the switch is set to ON position, it indicates 1 (on); when the
switch is set downwards, it indicates 0 (off). For example, to set a device number 39=1+2+4+32, which corresponds to the binary code 111001, put number 1, 2, 3, and 6 to ON position, as illustrated below.
2. For more details, please check the table at the end of this document
Restore factory setting
1. If you forget the C3 IP address or the device does not work normally, you can use the number 7 terminal to restore C3-200 to factory default settings. The parameters which gets reset are device IP address, communication password ,gateway ,subnet mask.
2. The switch is OFF by default. When it is moved upwards and downwards for three times within 10 seconds and finally returned to OFF position, the factory settings will be restored after the access control panel is restarted.
1 times
2 times
3 times
OFF
Terminal Resistance
1. Number 8 is for setting the RS485 termination resistance. Putting the switch to ON position is equivalent to parallel connection of a 120ohm termination resistance between 485+ and 485-
2. For more information please read RS485 connection - important notes
120ohm
Page 19
Electrical Specifications
18
Min. Typ. Max. Notes
Working power supply
Voltage(V) 9.6 12 14.4 Use regulated DC power adaptor only
Current(A) 2
Electronic lock relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 2
Auxiliary relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 1.25
Switch Aux. input
VIH (V) TBD
VIL (V) TBD
Pull-up resistance () 4.7k The input ports are pulled up with 4.7k resistors
WIEGAND Input
Voltage(V) 10.8 12 13.5
Current(mA) 500
ZK Electronic lock
Voltage(V) 10.8 12 13.2
Current(mA) 500
Page 20
Troubleshooting
19
1. How to switch four door one way to two door to way.
Connect four readers from reader 1 to reader 4. Connect two door locks , one connect LOCK1 ,another connect LOCK3. Switch on software then reader 1-Indoor, reader 2-Outdoor.
2. How many WEIGAND formats are supported ?
The panel is set to read 26 bit by default. However there are 9 other bit formats which can be selected from the software. In addition you
can also define your custom bit format.
3. How many verification mode can be support.
Card only Password only Card plus password
4. Can we integrate IP Camera and NVR
Currently ZKACCESS software supports ZKAccess’ IP Cameras and NVR
You can associate a camera to the door and setup a linkage for the same.
5. Can C3 panel support FR1200 fingerprint reader ?
No , Only Inbio series can support FR1200 fingerprint reader
Diagram:
Page 21
Specifications
20
Communication RS485, TCP/IP
Baud Rate for RS485 9600-115200
Power Supply 12V DC, 3A
Card Holders Capacity 30,000
Log Events Capacity 100,000
LED Indicator Indication for communication, power, status and prox card
Environment
32-113 °F (0-45 °C)
Operating Humidity 20% to 80%
Number of doors controlled Four Door (four door one way two door two way)
Number of readers supported 4
Types of readers supported 26-bits WIEGAND, others upon request
Number of Inputs 6 (2 Exit Device, 2 Door Status, 2 AUX)
Number of Outputs 4 (2- Form C relay for lock and 2- Form C relay for Aux output)
Weight 7.8lbs (3.55kg)
Enclosure Stainless Steel
Mounting Wall Mount
Dimensions (Bundle Only) 15.7in. × 3.56in.× 13.0in 400mm(L) X 90.5mm(W) X 330mm(H)
Dimensions ( Board Only) 6.30in. X 4.17in. 160mm(L)X 106mm(W)
CPU 32 bit 400MHz
RAM 32MB
Flash 128MB
Certified
Page 22
Attached
21
PC 485 Setting table
Place Address
Switch Setting
1 2 3 4 5 6
Address No. 1 2 4 8 16 32
01 ON OFF OFF OFF OFF OFF 02 OFF ON OFF OFF OFF OFF 03 ON ON OFF OFF OFF OFF 04 OFF OFF ON OFF OFF OFF 05 ON OFF ON OFF OFF OFF 06 OFF ON ON OFF OFF OFF 07 ON ON ON OFF OFF OFF 08 OFF OFF OFF ON OFF OFF 09 ON OFF OFF ON OFF OFF 10 OFF ON OFF ON OFF OFF 11 ON ON OFF ON OFF OFF 12 OFF OFF ON ON OFF OFF 13 ON OFF ON ON OFF OFF 14 OFF ON ON ON OFF OFF 15 ON ON ON ON OFF OFF 16 OFF OFF OFF OFF ON OFF 17 ON OFF OFF OFF ON OFF 18 OFF ON OFF OFF ON OFF 19 ON ON OFF OFF ON OFF 20 OFF OFF ON OFF ON OFF 21 ON OFF ON OFF ON OFF 22 OFF ON ON OFF ON OFF 23 ON ON ON OFF ON OFF 24 OFF OFF OFF ON ON OFF 25 ON OFF OFF ON ON OFF 26 OFF ON OFF ON ON OFF 27 ON ON OFF ON ON OFF 28 OFF OFF ON ON ON OFF 29 ON OFF ON ON ON OFF 30 OFF ON ON ON ON OFF 31 ON ON ON ON ON OFF 32 OFF OFF OFF OFF OFF ON
Place Address
Switch Setting
1 2 3 4 5 6
Address No. 1 2 4 8 16 32
33 ON OFF OFF OFF OFF ON 34 OFF ON OFF OFF OFF ON 35 ON ON OFF OFF OFF ON 36 OFF OFF ON OFF OFF ON 37 ON OFF ON OFF OFF ON 38 OFF ON ON OFF OFF ON 39 ON ON ON OFF OFF ON 40 OFF OFF OFF ON OFF ON 41 ON OFF OFF ON OFF ON 42 OFF ON OFF ON OFF ON 43 ON ON OFF ON OFF ON 44 OFF OFF ON ON OFF ON 45 ON OFF ON ON OFF ON 46 OFF ON ON ON OFF ON 47 ON ON ON ON OFF ON 48 OFF OFF OFF OFF ON ON 49 ON OFF OFF OFF ON ON 50 OFF ON OFF OFF ON ON 51 ON ON OFF OFF ON ON 52 OFF OFF ON OFF ON ON 53 ON OFF ON OFF ON ON 54 OFF ON ON OFF ON ON 55 ON ON ON OFF ON ON 56 OFF OFF OFF ON ON ON 57 ON OFF OFF ON ON ON 58 OFF ON OFF ON ON ON 59 ON ON OFF ON ON ON 60 OFF OFF ON ON ON ON 61 ON OFF ON ON ON ON 62 OFF ON ON ON ON ON 63 ON ON ON ON ON ON
Page 23
ZK USA office:
201 Circle Drive North, Suite 116 Piscataway, NJ 08854, USA Tel: +1 732-412-6007 Fax +1 732-412-6008 sales@zkaccess.com zkaccess.com
Copyright 2013 ZKAccess Inc. All right reserved.
ZKTeco May, at any time and without notice , Make changes or improvements to the product and services offered and/or cease producing or commercializing them.
Functions and specifications of the product are subject to change without notice due to quality enhancement or function update. For any inquiry for the product, please contact ZKTeco Inc .
Loading...