Zero Zone Kelvin II Installation Manual

SD-324
Sporlan Kelvin II Refrigeration Controller
User’s Manual, November 2009
Page 1
1
24 VAC
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
19
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
24 VAC
N/C
N/C
N/C
N/C
N/C
Ground
RS-485 A+
RS-485 B-
N/C
N/C
N/C
Load
Line
N/C
N/C
N/C
N/C
N/C
N/C
T3-
T3+
T2-
T2+
T1-
T1+
PWR
Room
Tout
RS485
Valve
LL Sol
N/C
Pressure
Aux
SER, SEI, SEH ESX
Red Black
Green Red
White Yellow
Black Orange
N/C Gray
Black
Green
White
+5VDC
Ground
Sense
Description
The Kelvin II is a standalone superheat controller. The Kelvin II may be connected with a MODBUS master or a Network Master to give remote access to pressure and temperature readings in addition to viewing and editing the controller’s setpoints. The user can also take advantage of the easy to use local display or a Remote Display to accomplish the same tasks.
1. Kelvin II Configuration
Specifications
n Input Voltage: 24 VAC (± 10%), 40 VA minimum to board
with external transformer
n Operating ambient temperature: -40°F to 120°F n LED: One Power LED n Communications: 1 RS485 Port, 1 USB port
(Not operational)
n 4 Digit 7 segment display n Inputs:
– Optical Encoder (Knob) – One Pressure Input – Three Temperature inputs
n Valve Control of all Sporlan Electric Expansion Valves
“EEV”
n 3 amp Solid State Relay for Liquid Line Solenoid Kelvin II
w/o Local Display
n 1 amp Solid State Relay for Liquid Line Solenoid Kelvin II
w/Local Display
2. Kelvin II Connections
Figure 1
Item Wire (line)
Power
Valve
RS-485
Liquid Line Solenoid
Auxiliary Temperature Sensor (Displayed menu item: S-3)
Room Temperature Sensor (Displayed menu item: CtP)
Coil Out Temperature Sensor (Display option: tout)
Pressure Transducer (Displayed menu item: SucP)
24VAC 1 24 VAC 2 SEI, SER, SEH ESX — N/C Gray 4 Black Orange 5 White Yellow 6 Green Red 7 Red Black 8 Ground 13 A+ 14 B- 15 Line 19 Load 20
T3
T2
T1
Sense (WHITE) 33 Ground (GREEN) 34 +5 VDC (BLACK) 35
Kelvin II
connect point
27 28 29 30 31 32
3. Kelvin II Display
Upon the rst power-up from Sporlan, the Kelvin II will en­ter the setup menu. This menu allows the user to set some critical setpoint values, seen in Table 1, before the controller will operate. These critical values can be set via the local or remote displays, MODBUS, or Network Master. (Note: Only the Valve Type and Refrigerant have to be set via MODBUS or Network Master for the controller to operate) Once these values are entered the Kelvin II will then begin its control. If the setup menu is displayed on the local or remote displays
Page 2
and the user sets these values via MODBUS then the Kelvin II will automatically leave the setup menu.
Table 1 Setup Menu
Displayed Menu Item Description Selections
StEP
rEFr
PtYP
un_T
un_P
Valve Type 1596, 3192, 2500, 6384, 400
Refrigerant
Pressure Sensor Type gAUg, AbSL
Temperature Units FAHR, CELS
Pressure Units PSI, BAR
r22, 134A, 402A, 404A, 407A, 407C, 410A, 417A, r507, 422d, r744, 245F
After setup, the Kelvin II defaults to showing the Superheat value. The user can then turn the knob to view the other pro­cess values of their system. The screen will alternate between the process values identity and value alternating every 3 sec­onds. For ease of use, the value that is displayed for a process value may come in the form of text to eliminate the need of ‘looking up the meaning’. The menu text and meanings for process values are described in Table 2.
The user may also view/edit the setpoints by pressing the knob and holding it down for 5 seconds. The user is then prompted for a password to verify his credentials. The knob should be rotated up to ‘111’ for the password. If the password is cor­rect the user may change the setpoints to the value he desires in order to obtain optimum system performance. The menu text and meanings for setpoint values are described in Table 3. Setpoints are saved to the controller when the user leaves the Setpoint menu by pressing the knob when “ESC” is shown. The setpoint menu has a timeout of 60 seconds for inactiv­ity. When this timeout is reached the controller goes back to showing the process values and does not save any setpoints that might have been changed. If the user is in the Manual Valve Position setpoint then this timeout length is 60 minutes. As long as the controller does not time out the 60 minutes, Setpoints are saved to the controller when the user leaves the Setpoint menu by pressing the knob when “ESC” is shown.
All process values and setpoints are accessible1 through the local and remote displays.
Table 2 Process Value Menus
Displayed Menu Item Description Range
SuPH SucP tSAt tout CtP PoSn S-3 rELA
StAt
ALS
Superheat 0 to 165°F, 0 to 91.6°C Suction Pressure Saturation Temperature -60 to 150°F, -51.1 to 65.6°C Suction Temperature -60 to 150°F, -51.1 to 65.6°C System Temperature -60 to 150°F, -51.1 to 65.6°C Valve Position 0 to 100% Open Auxiliary Temperature Solenoid Status dEng, Eng
System Cycle Status
Alarm Status
4
0 to 150 PSI, 0 to 10.34 Bar
2
-60 to 150°F, -51.1 to 65.6°C
Current cycle and manual
3
valve position state noAL or all active alarms
Table 3 Setpoint Menu
Displayed
Menu
Item
ESC
SHSP
rEFr
d_On dOFF
d_St
CtSP
H_oP
C_in
Cout
HiCP SUPS
-P-
-I-
-d-
StEP
SPoS
nEt
Addr
un_P un_T
PtYP
CaLP
CLt1
CLt2
CLt3
CAdr
Description Range
Escape and save settings
Superheat Setpoint 0 to 45°F, 0 to 25°C 8
Refrigerant
Delay On 0 to 60 seconds 0 Delay Off 0 to 60 seconds 0 Delay Percent Open
of Valve Cut-out Suction
Pressure Maximum Operating
Pressure
Cut-in Temperature
Cut-out Temperature
Max Valve Capacity 20 to 100% 100 Supermarket Setting OFF, ON OFF Proportional
Coefficient Integral Coefficient 0 to 100 25 Derivative
Coefficient
Valve Type
Manual Valve Position
Network Type (MODBUS or Network Master)
MODBUS/Network Master Address
Pressure Units PSI, BAR PSI Temperature Units FAHR, CELS FAHR Pressure Sensor
Type Pressure Sensor
calibration value Tout calibration
value
Ctp calibration value
S-3 calibration value
Controller Display Address
r22, 134A, 402A, 404A, 407A, 407C, 410A, 417A, r507, 422d, r744, 245F
0 to 100 percent 0
4
PSI,
0 to 150
4
4
4
Bar
PSI,
Bar
0 to 10.3 0 to 150
0 to 10.3
-60 to 125°F,
-51.1 to 51.6°C
-60 to 124°F,
-51.1 to 51.1°C
0 to 100 40
0 to 100 5
1596, 3192, 2500, 6384, 400
0 to 100% Open
nbUS (MODBUS) or ProP (Network Master)
1 to 255 1
AbSL, gAUg gAUg
-5 to 5 PSI,
-0.34 to 0.34 Bar
-5 to 5°F, -2.7 to
2.7°C
-5 to 5°F, -2.7 to
2.7°C
-5 to 5°F, -2.7 to
2.7°C
0 to 99
Default Setting
404A
0
150
-59
-60
1596
Present Position
nbUS
0
0
0
0
0 or 1 for local display
User
Setpoints
4. Kelvin II MODBUS
The Kelvin II can communicate with a MODBUS master. The Kelvin II will transfer process values and setpoints via MODBUS.
1 Setpoints can only be viewed and edited when the proper password is entered. 2 The Auxiliary Temperature sensor input has a special Pumpdown feature. If a “short” or switch closure is placed across these terminals, the valve will
shut for pumpdown. The full details of this feature are described in Section 5.
3 The Alarm Status process value is described in Section 6. 4 The maximum value varies based on which refrigerant is selected. (R-410A is 300 PSI, R-744 is 500 PSI and all others are 150 PSI).
Page 3
The Kelvin II only supports the RTU transmission mode. The serial settings are as follows:
n 9600 baud n 8 data bits n 1 stop bit n Even parity
The Kelvin II supports the ‘Read Input Registers’, ‘Read Holding Register’, ‘Write Single Register’, ‘Read Multiple Coils’ and ‘Write Single Coil’ function codes. Any other re­quest will result in an exception response. The Kelvin II will allow a full and partial block read of the Input and Holding registers and Coils.
4.1. Scaling
In order to preserve precision, scaling was implemented when using Bar or Celsius for units. PSI and Fahrenheit units are both in whole numbers and have no scaling. The tables of the
MODBUS memory map below reect this implementation.
The Bar values that are transferred via MODBUS are 100X. For example, if Bar is chosen for the pressure units then 1034 Bar is transferred for the Maximum Operating Pressure. The actual Maximum Operating Pressure is 10.34 Bar. If the user desired to change a setpoint they should keep this in mind when they enter a value.
4.2. MODBUS Memory Map
Table 4 Memory Map
MODBUS
Function
Code
Read Coils
(0x01)
Read Holding
Register
(0x03)
Mapped
Data
Manual
Valve
Control
Setpoints
Data Map Range
Bit 0 = Manual Valve Enabled Flag Bit 1 = Manual Valve Duration Enabled Flag
0. Superheat Setpoint
1. Refrigerant Type
2. Delay On Relay 0 to 60 seconds
3. Delay Off Relay 0 to 60 seconds
4. Delay Steps 0 to 100 % Open
5. Cut-out Suction Pressure
0 = Disabled, 1 = Enabled.
0 to 45°F, 0 to 250°C (0.0 to 25.0°C)
0 = r22 1 = 134A 2 = 402A 3 = 404A 4 = 407A 5 = 407C 6 = 410A 7 = 417A 8 = 422A 9 = 422d 10 = r507 11 = r744 12= 245F
5
PSI, 0 to 1034
0 to 150 Bar (0 to 10.34 Bar)
MODBUS
Function
Code
Read Holding
Register
(0x03)
Read Input
Registers
(0x04)
Mapped
Data
Setpoints
Process
Variables
Data Map Range
6. Max Operation Pressure
7. Temperature Cut-in
8. Temperature Cut-out
9. Valve Maximum 20 to 100 %
10. Supermarket Mode
11. P 0 to 100
12. I 0 to 100
13. D 0 to 100
14. Valve Type
15. Manual Valve Position
16. Network Type
17. Unit Address 1 to 255
18. Pressure Units 0 = PSI, 1 = BAR
19. Temperature Units
20. Pressure Sensor Type
21. Pressure Calibration Offset
22. Suction Temperature Calibration Offset
23. Room Temperature Calibration Offset
24. Auxiliary Temperature Calibration Offset
0. Superheat
1. Suction Pressure
2. Saturation Temperature
3. Suction Temperature
4. Room Temperature
5. Valve Capacity
6. Auxiliary Temperature
7. Relay Status
6
6
0 to 150 Bar (0 to 10.34 Bar)
-60 to 125°F,
-511 to 516 °C (-51.1 to 51.6 °C)
-60 to 124°F,
-511 to 511 °C (-51.1 to 51.1 °C)
0 = OFF 1 = ON
0 = 1596 1 = 3192 2 = 2500 3 = 6384 4 = 400
0 to 100 % Open
0 = MODBUS 1 = Network Master
0 = FAHR, 1 = CELS
0 = GauG, 1 = ABSL
-5 to 5°F,
-34 to 34 Bar (-0.34 to 0.34 Bar)
-5 to 5°F,
-27 to 27°C (-2.7 to 2.7°C)
-5 to 5°F,
-27 to 27°C (-2.7 to 2.7°C)
-5 to 5°F,
-27 to 27°C (-2.7 to 2.7°C)
0 to 165°F, 0 to 916°C (0 to 91.6°C)
0 to 150 PSI, 0 to 1034 Bar (0 to 10.34 Bar)
-60 to 150°F,
-511 to 656°C (-51.1 to 65.6°C)
-60 to 125°F,
-511 to 656°C (-51.1 to 65.6°C)
-60 to 125°F,
-511 to 656°C (-51.1 to 65.6°C)
0.0 to 100.0% Open (0.0 to 100.0)
-60 to 125°F,
-511 to 656°C (-51.1 to 65.6°C)
0 = Deenergized, 1 = Energized
PSI, 0 to 1034
5 The maximum value varies based on which refrigerant is selected. (410A is 300 PSI, r744 is 500 PSI and all others are 150 PSI). 6 The maximum value varies based on which refrigerant is selected. (410A is 300 PSI, r744 is 500 PSI and all others are 150 PSI).
Page 4
MODBUS
Function
Code
Read Input
Registers
(0x04)
Write Single Coil (0x05)
Write Single Register (0x06)
Mapped
Data
Process
Variables
Manual Valve Control
Setpoints Same as above.
Data Map Range
8. Alarm Status
9. System Cycle Status
Bit 0 = Manual Valve Enabled Flag
If Bit set then alarm is active: Bit 0 = Suction Transducer Failure Bit 1 = Tout Sensor Failure Bit 2 = High Superheat Bit 3 = Low Superheat
If Bit set then mode is active: Bit 1 = Setup Mode Bit 2 = Off Cycle Bit 3 = Cooling Cycle Bit 4 = Pump-down Cycle Bit 5 = Manual Valve Override Mode
0 = Disabled, 1 = Enabled. The Manual Valve duration Bit is read-only.
The max number of registers written at a time is
1. The limits can be seen above in the ‘Read Holding Register’ definition.
5. Kelvin II Features
5.1. Pumpdown Feature
The Kelvin II will initiate a pumpdown when Auxiliary Tem­perature sensor terminals are shorted. If desired, this temper­ature connection could be set up as a dry contact. When a pumpdown is desired the contact should be closed. The pump­down will be ended when the short is removed provided that there are no sensor alarms.
7. Kelvin II Display Networking
The Kelvin II displays can be set up to access other Kelvin II controllers on the network. The controller’s current ‘CAdr’ value can be determined by pressing down the button on the display while viewing a process value. To enable the display network the ‘CAdr’ setting MUST be set to a unique nonzero value with the RJ-45 connector on the side of the controller DISCONNECTED.
After ‘CAdr’ has been set, an ‘End’ screen is added just be­fore the ‘SuPH’ process value. Pressing the button on the display while viewing the ‘End’ screen brings up a menu al­lowing the selection of other Kelvin II controllers connected to the display network. Turning the knob allows the selec­tion of other Kelvin II controllers based on their appropriate ‘CAdr’ address. The local controller is listed as ‘LocL’ by a local display. Note: the remote display always includes the ‘End’ screen since it must be able to view any controller on the display network.
8. Kelvin II Factory Reset
A factory reset can be performed by holding the button down on the local or remote displays for 5 seconds when power is
rst applied. If using a local display the display will show
‘FrSt’ while the factory reset is being performed and then automatically connect to the local controller.
5.2. Manual Valve Position Feature
The Kelvin II has the ability to manually control the valve. To enable this manual control via the local or remote displays simply open the setpoint menu and edit the ‘SPoS’ setpoint. When the value is displayed for this setpoint the user is manu­ally controlling the valve. The valve position can be changed by rotating the knob clockwise or counterclockwise. There is an inactivity timer of 60 minutes while in manual control. The timer is reset each time the user moves the valve. The manual control of the valve is ended when the user presses the knob to go back to displaying ‘SPoS’ or a timeout has been reached.
6. Kelvin II Alarms
The Kelvin II has 4 alarms. The following table lists the possible alarms and the text that is seen on the controller. The controller’s alarm status can be viewed via MODBUS, Network Master, and local and remote displays.
Table 5 Alarms
Alarm Text Meaning
NoAL PSAL TSAL HSAL LSAL
No Alarms active Pressure Sensor alarm Tout Sensor alarm High Superheat alarm Low Superheat alarm
If using a remote display the display will show ‘FrSt’ and switch to a menu that allows the selection of the controller to reset. To perform a factory reset, select the controller with the appropriate ‘CAdr’ value. The display should show ‘----‘ while the reset is being performed. When nished perform­ing factory resets turn the knob counterclockwise until ‘ESC’ is shown on the display. Pressing the button while ‘ESC’ is shown on the display exits the factory reset menu and should automatically connect to a controller on the display network.
Table 6 Replacement Parts
Part Number Description
952560 Kelvin II without display 952561 Kelvin II with local display 952562 Kelvin II Remote panel display 952662 Temperature Sensor Assembly 952795 Well Sensor Kit 953091 Pressure Transducer 150 psig with cable 952995 Pressure Transducer 150 psia with cable
952740
952504
Pressure Transducer 300 psig with cable for R-410A applications only
Pressure Transducer 500 psig with cable for R-477 applications only
Parker Hannifin Corporation
Sporlan Division
206 Lange Drive • Washington, MO 63090 USA phone 636 239 1111 • fax 636 239 9130 www.sporlan.com
112009 / SD-324
Loading...