Zephyr W007102013 Owner Manual

Siena
ZSI-E30AS-ES ZSI-E36AS-ES
www.zephyronline.com
Model number:
Serial Number:
Use, Care, and Installation Guide
MAR19.0401 © Zephyr Ventilation LLC.
www.zephyronline.com
LIST OF MATERIALS ....................................................... 4
INSTALLATION
Ducting Calculation Sheet ....................................... 5
Mounting Height & Clearance ................................ 6
Ducting Options ........................................................... 7
Hood Specications ................................................... 8
Mounting the Range Hood ...................................... 9
Horizontal Ducting Conversion.............................. 10-11
FEATURES & CONTROLS
ICON Touch Controls ................................................ 12
MAINTENANCE
Cleaning and Filter Care .......................................... 13
Light Bulbs ..................................................................... 14
TROUBLESHOOTING................................................................ 15
Table of Contents
ACT CONVERSION ..................................................................... 16
WIRING DIAGRAM ...................................................................... 17
LIST OF PARTS AND ACCESSORIES .............................. 18
WARRANTY .................................................................................... 19
PRODUCT REGISTRATION .................................................... 20
1
READ AND SAVE THESE INSTRUCTIONS
www.zephyronline.com
WARNING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY SOLID-STATE CONTROL DEVICE.
WARNING
TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Use this unit only in the manner intended by the manufacturer, if you have questions, contact the manufacturer.
b. Before servicing or cleaning unit, switch power o󰀨 at service panel and lock panel to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service
panel.
CAUTION
For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors. Take care when using cleaning agents or detergents. Suitable for use in household cooking area.
WARNING
TO REDUCE THE RISK OF RANGE TOP GREASE FIRE:
a. Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly
on low or medium settings.
b. Always turn hood ON when cooking at high heat or when aming food c. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or lter.
Important Safety Notice
d. Use proper pan size. Always use cookware appropriate for the size of the surface element. e. Keep fan, lters and grease laden surfaces clean.
f. Use high setting on hood only when necessary.
g. Don’t leave hood unattended when cooking. h. Always use cookware and utensils appropriate for the type of and amount of food being prepared.
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE, OBSERVE THE FOLLOWING:
a. SMOTHER FLAMES with a close-tting lid, cookie sheet, or metal tray, then turn o󰀨 the burner. BE CAREFUL TO PREVENT BURNS.
If the ames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
b. NEVER PICK UP A FLAMING PAN – You may be burned. c. DO NOT USE WATER, including wet dishcloths or towels – a violent steam explosion will result. d. Use an extinguisher ONLY if:
1. You know you have a Class ABC extinguisher, and you already know how to operate it.
2. The re is small and contained in the area where it started.
3. The re department is being called.
4. You can ght the re with your back to an exit
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable codes and standards.
Including re-rated construction.
b. Su󰀩cient air is needed for power combustion and exhausting of gases through the ue (chimney) of fuel burning equipment to prevent
back-drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and
the local code authorities. c. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. d. Ducted fans must always vent to the outdoors. e. NEVER place a switch where it can be reached from a tub or shower.
f. Make sure the power is o󰀨 before installing, wiring or maintenancing.
2
WARNING
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
CAUTION
To reduce risk of re and to properly exhaust air outside - Do not vent exhaust air into spaces within walls, ceilings,
attics, crawl spaces or garages.
OPERATION
Always leave safety grilles and lters in place. Without these components, operating blowers could catch onto hair, ngers
and loose clothing.
The manufacturer declines all responsibility in the event of failure to observe the instructions given here for installation, maintenance and suitable use of the product. The manufacturer further declines all responsibility for injury due to negligence and the warranty of the unit automatically expires due to improper maintenance.
*NOTE: Please check www.zephyronline.com for revisions before doing any custom work.
ELECTRICAL REQUIREMENTS
Important:
Observe all governing codes and ordinances.
It is the customer’s responsibility:
- To contact a qualied electrical installer.
- To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 latest edition* or CSA standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest edition** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician determine that the
ground path is adequate.
Do not ground to a gas pipe.
Check with a qualied electrician if you are not sure the range hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.
*National Fire Protection Association Batterymarch Park, Quincy, Massachusetts 02269 ** CSA International 8501 East Pleasant Valley Road, Cleveland, Ohio 44131-5575
This appliance requires a 120V 60Hz electrical supply and connected to an individual properly grounded branch circuit
protected by a 15 or 20 ampere circuit breaker or time delay fuse. Wiring must be 2 wire with ground. Please also refer to
Electrical Diagram on product.
A cable locking connector (not supplied) might also be required by local codes. Check with local requirements, purchase
and install appropriate connector if necessary.
ZSI-E30AS-ES / ZSI-E36AS-ES - 136 Watts, 1.2 Amps
Power consumption shown above is the default power specs. Hoods with Zephyr’s proprietary Airow Control Technology (ACT) enabled will consume less power. See wiring diagram at the end of this manual for more information.
Important Safety Notice
Prop. 65 Warning for California Residents
WARNING:
Cancer and Reproductive Harm - www.P65Warnings.ca.gov
3
PARTS NOT SUPPLIED
- Ducting, conduit and all installation tools
- Cable connector (if required by local codes)
- Duct cover extension accessory
HARDWARE PACKAGE CONTENTS
MODELS: ZSI-E30AS-ES, ZSI-E36AS-ES
PARTS SUPPLIED
1 - Hood with internal blower 2 - Baffle filters 1 - Duct cover assembly (top and bottom) 1 - Duct cover wall bracket 2 - Fluorescent light bulbs 1 - 8” round backdraft damper 1 - 3-1/4” x 10” rectangular collar (rear ducting only) 2 - Rear ducting motor mount brackets 1 - Top Cover Plate (rear ducting only) 1 - Hardware package
(6) M4 x 38
(6) M4 x 8
(4) M4 x 8
(8) 3/16 x 3/8”
(4) M4 x 6
www.zephyronline.com
List of Materials
4
Duct pieces
3- 1/4” x 10” Rect., straight
6”, 7”, 8”, 10” Round, straight
3- 1/4” x 10”
0
Rect. 90 elbow
3- 1/4” x 10”
0
Rect. 45 elbow
3- 1/4” x 10”
0
Rect. 90 flat elbow
7” to 6” or 8” to 7” Round tapered reducer
6”, 7“, 8” Round in-line damper
6”, 7”, 8”, 10” Round,
0
90
elbow
6”, 7”, 8”, 10” Round,
0
45
elbow
Equivalent number length x used =
1 Ft. x ( ) =
1 Ft. x ( ) =
15 Ft. x ( ) =
9 Ft. x ( ) =
24 Ft. x ( ) =
25 Ft. x ( ) =
15
Ft. x ( ) =
15 Ft.
x ( ) =
9 Ft. x ( ) =
Subtotal column 1 =
To tal
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Duct pieces
3- 1/4” x 10” Rect. to 6” round transition
3- 1/4” x 10” Rect. to 6” round transition
0
elbow
90
6” round to 3- 1/4” x 10” rect. transition
6” round to 3- 1/4” x 10” rect. transition
0
90
elbow
7” round to 3 1/ 4” x 10” rect. transition
7” round to 3- 1/4” x 10” rect. transition
0
elbow
90
3- 1/4” x 10” Rect. wall cap with damper
6”, 7”, 8”, 10” Round, wall cap with damper
6”, 7”, 8”, 10” Round roof cap
Equivalent number length x used =
5 Ft. x ( ) =
20 Ft. x ( ) =
1 Ft. x ( ) =
16 Ft. x ( ) =
8 Ft. x ( ) =
23 Ft. x ( ) =
30 Ft. x ( ) =
30 Ft. x ( ) =
30 Ft. x ( ) =
To tal
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Installation – Ducting Calculation Sheet
Maximum Duct Length: For satisfactory air movement,
the total duct length
should not exceed 100 equivalent feet.
Subtotal column 2 =
Subtotal column 1 =
Total ductwork =
Ft.
Ft.
Ft.
5
ALWAYS, when possible, reduce the number of transitions and turns. If a long duct run is required, increase duct size from 8” to 10”.
If turns or transitions are required: Install as far away from opening and as far apart, between 2, as possible.
Minimum mount height between range top to hood bottom should be no less than 26”.
min. D
max. F
min. A
max. C
Maximum mount height should be no higher than
26” min. 34” max.
34”.
It is important to install the hood at the proper mounting height. Hoods mounted too low could
result in heat damage and re hazard; while hoods
mounted too high will be hard to reach and will
loose its performance and e󰀩ciency.
36”
If available, also refer to range manufacturer’s height clearance requirements and recommended
hood mounting height above range. Always check your local codes for any di󰀨erences.
Standard Extension
Hood Heights Duct Cover Duct Cover
minimum (A) 27-1/2” 46-1/2“
maximum (C) 42” 79”
Ceiling Heights
minimum (D) 89-1/2” (7’ 5-1/2”) 108-1/2“ (9‘ 1/2”)
maximum (F) 112” (9’ 4“ ) 149” (12’ 5”)
Duct cover extension kit available for ceiling
heights up to 12 feet. Turn to page 18 for part number and ordering information.
DAMAGE-SHIPMENT / INSTALLATION:
• Please fully inspect unit for damage before
• If the unit is damaged in shipment, return the
Installation – Mounting Height & Clearance
DUCTING
A minimum of 8” round duct is recommended to
• If the unit is damaged by the customer, repair
maintain maximum air ow e󰀩ciency.
Always use rigid type metal ducts only. Flexible
• If the unit is damaged by the installer (if other
ducts could restrict air ow by up to 50%.
Use calculation worksheet on page 5 to compute total duct work.
www.zephyronline.com
installation.
unit to the store in which it was bought for repair or replacement.
or replacement is the responsibility of the customer.
than the customer), repair of replacement must
be made by arrangement between customer and installer.
6
WARNING FIRE HAZARD
NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or garages. All exhaust must be ducted to the outside, unless using the recirculating option.
Use single wall rigid Metal ductwork only.
Fasten all connections with sheet metal screws and tape all joints w/ certied Silver Tape or Duct Tape.
Some Ducting Options
Roof Pitch w/ Flashing & Cap
Soffit or crawl space
side wall cap w/ gravity damper
side wall cap w/ gravity damper
Installation – Ducting Options
7
www.zephyronline.com
Side of HoodFront of Hood
10 1/2”
29 15/16”, 35 7/8”
Installation – Hood Specications
8 7/16”
STANDARD min. - 27 1/2” max. - 42”
Z1C-00SI
min. - 46 1/2” max. - 79”
1 9/16”
12 3/8”
21 15/16”
7 3/4”
Top of Hood
4 1/4”
C/L
AC In
5/8”
Back of Hood
4 3/8”
1 5/16”
5 1/16”
12 3/4”
8
A
B
C/L
13-1/8"
9-7/ 16"
C/L
26" min
Duct Cover Bracket
C
12-3/4"
1-5/16"
C
B
e
required
e
hood.
!
accordance
be
properly grounded. Turn off electrical power at service entrance before wiring.
!
24”
MAX.
HOOD
CENTERLINE
4¼”
MAX.
12”
CAUTION: At least two installers ar
due to the weight and size of th
1. Measure from range top to hood bottom and mark line A.
(26” minimum from range top).
2. Plum and mark center line.
3. Mark mounting height line B. (1-5/16” from line A)
4. Mark mounting height line C. (13-1/8” from line A)
5. Mark mounting spread from C/L on line B 12-3/4”
6. Mark mounting spread from C/L on line C 9-7/16”
7. Fasten (2) M4 x 1-1/2” screws into studs on line C. Do not
fasten screws all the way. Note: wood blocking may need to be added behind the drywall if no studs are present. Wall anchors may also be used but check local codes for compliance. Failure to use suitable wall anchors and screws to hold the weight of the hood could result in personal injury or damage to cooking surface or counter.
8. Install 8” round duct collar with backdraft damper to top of
body of hood by (4) M4x8 at screws.
9. Hang hood onto screws and hand tighten. (FIG. A #1) Use
(2) M4 x 1-1/2” screws to further secure the hood to the wall
from inside the hood on line B.
10. Center and attach duct cover bracket to wall below ceiling
or so󰀩t using (2) M4 x 1-1/2” screws.
11. Position electrical outlet within the space covered by the
telescopic duct covers and where it will not interfere with
the round duct. (FIG. B)
12. *Install duct work and duct tape.
13. Power up hood and check for leaks around duct tape.
14. Place telescopic duct covers onto hood and extend inner
(top) duct cover upwards and secure to duct cover bracket using (2) M4x8 screws.
The ducting from this fan to the outside of the building has
a strong e󰀨ect on the air ow, noise and energy use of the
fan. Use the shortest, straightest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed
with existing ducts may not achieve their rated air ow.
Installation – Mounting the Hood
FIG. A
WARNING: Electrical wiring must be done by a qualified person(s) in
with all applicable codes and standards. This range hood must
9
FIG. B
www.zephyronline.com
This range hood is equipped standard with a 8” round vertical duct option. To convert from 8” round vertical to 8” round horizontal ducting or 3-1/4” x 10” rectangular horizontal ducting please following the instructions below.
VERTICAL TO HORIZONTAL DUCTING CONVERSION
1. Remove (4) screws attaching motor to hood
body.
Installation – Horizontal Ducting Conversion
3. Attach rectangular or round duct collar to interior
of hood body by (4) screws.
2. Remove knock out plate A & B for rectangular ducting or knock out plates B & C for round
ducting.
4. Attach rear ducting brackets to motor by (4)
screws.
10
5. Position blower with brackets as shown. Be sure to tuck back of blower bracket into tabs at back of hood. Secure single blower plate to back of hood using (4) screws removed from step 2.
7. From outside hood body, attach top cover plate
to top of hood body using (4) M4 x 8 screws.
6. Attach motor to back of hood body by (8)
screws.
Installation – Horizontal Ducting Conversion
11
www.zephyronline.com
Lights On/Off
Display (speed level, delay off, filter clean/change)
Adjust 3 Speed Levels
Power / Delay Off
1 POWER / DELAY OFF BUTTON Power Button Function
- Button will turn power on and off for entire hood (fan and lights).
- Hood will remember the last speed and light level it was turned off at. (Example: Press Button to turn off hood when on fan speed 3 and lights on. Press Button again and the hood will turn back on at speed 3 and lights on.) Delay Off Button Function
- With the fan on press and hold the Button for two seconds. The fan will change to speed 1 and the 5 minute delay off timer will start. + LEDs will illuminate and slowly blink in accordance with the time remaining until the fan and lights automatically turn off.
- Pressing Button while Delay Off Function is enabled will turn the hood off and cancel the Delay Off Function.
ACT Verification
- Airflow Control Technology (ACT) allows the installer to set the maximum fan CFM to align with local codes and regulations.
- To verify the maximum fan CFM:
- With hood off, hold the Button for two seconds. If all five fan speed indicators illuminate = default maximum CFM. If 3 fan speed indicators illuminate = 290 maximum CFM.
2 SPEED SELECTION BUTTON Fan Speed Decrease Button
- Press this button to decrease fan speed. 3, 2, 1.
- If fan is On Speed 1 and this button is pressed, fan will power Off. Fan Speed Increase Button
- Press this button to increase fan speed. Fan On, 1, 2, 3.
- If hood is Off and this button is pressed, fan will turn On Speed 1.
3 LIGHTS BUTTON
- From off, press one time to power lights on. Press again to power lights off.
4 DISPLAY INDICATORS Mesh Filter Clean Reminder (always enabled)
- After 30 hours of fan usage, the button indicator will begin to slowly blink indicating it is time to clean the mesh filters.
- To reset: With hood off: hold the button for three seconds. All LED indicators will blink two times confirming the 30 hour timer has been reset.
Features & Controls - ICON Touch Controls
12
Loading...
+ 30 hidden pages