STAIRCASE TIME DELAY SWITCH ASH-01/U
Zakład Mechaniki i Elektroniki
ZAMEL sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com, e-mail: marketing@zamel.pl
INSTRUCTION
MANUAL
DESCRIPTION
The staircase lighting time delay
switch ASH-01/U is used to control lighting devices on staircases and corridors.
After releasing the system it switches
on the lighting for the preset time by the
user. After that it switches off automatically. The operating time can be adjusted
from 10 sec to 10 min by means of a potentiometer. The staircase lighting time
delay switch ASH-01/U can be used as
standard time delay relay. The hermetic
casing (IP65) secures the device functioning in unfavorable weather conditions.
FEATURES
● Operating time adjustment from 10 se-
conds to 10 minutes
● universal supply voltage 12÷240 V
AC/DC
● cooperation with 3- or 4-wires installa-
tion
● cable connection 0,5m length
● relay output - 1 voltage contact contact
max 16 A capacity,
● hermetic casing (IP65).
TECHNICAL PARAME-
TERS
Power supply cables: A1 (black), A2 (blue)
Input rated voltage: 12 ÷ 240 V AC/DC
Input voltage tolerance: from-5 to +10%
Nominal frequency: 50 / 60 Hz
Rated power consumption: 0,9 VA
Znamionowy pobór prądu: 8 mA
Release / output (load) cables:
Time adjustment range: from 10 sec to 10 min
Time accuracy adjustment: ±10 %
Time repeatability adjustment: ±5 %
Output relay parameters: 16 A / 250 V AC1 4000 VA
Number of switch cables: 4
Section of connecting cables: 4x 0,75 mm
Connecting cable length: 0,5 m
Ambient temperature range: from -20 to +45
Operating position: vertical, pointed down
Protection degree: IP65 (EN 60529)
Overvoltage category: II
Rated impulse withstand voltage: 1 kV (EN 61000-4-5)
Reference standards: EN 60669-1
ASH-01/U
grey / brown (connected inside)
Time adjustment: smooth (rotary potentiometer)
2
o
C
Mounting: 2x stretcher 5x(3x30)
Protective class: II
Pollution degree: 2
Dimensions: 69 x 56 x 27 mm
Weight: 0,101 kg
EN 60669-2-1
EN 61000-4-2,3,4,5,6,11
The device is designed for
one-phase installation and
must be installed in accordance with standards valid
in a particular country. The
CAUTION
device should be connec-
ted according to the details included in this operating manual. Installation, connection and control should
be carried out by a qualied electrician
staff, who act in accordance with the service manual and the device functions. Disassembling of the device is equal with a
loss of guarantee and can cause electric
shock. Before installation make sure the
connection cables are not under voltage.
The cruciform head screwdriver 3,5 mm
should be used to instal the device. Improper transport, storage, and use of the
device inuence its wrong functioning. It
is not advisable to instal the device in the
following cases: if any device part is missing or the device is damaged or deformed. In case of improper functioning of
the device contact the producer.
The symbol stands for selective
collection of electrical and
electronic devices. Placing used
devices with other waste is not
allowed
APPEARANCE
Time adjustment
k
c
a
l
b
e
u
l
b
g
r
e
y
b
r
o
n
w
Power supply cable (A1)
Power supply cable (A2)
Release / output (load)
cables
VER. 002_06.04.2010

CONNECTINGMOUNTING
1. Disconnect the power supply from the
mains by the phase fuse, the circuitbreaker or the switch-disconnector
that are joined to the proper circuit.
2. Check if there is no voltage on con-
nection cables by means of a special measure equipment.
3. Fasten the ASH-01/U to the base with
the screw.
NOTICE! It is forbidden to bore tting
holes in the cover! It may result in the
loss of containment of the cover and
by this – the loss of guarantee!
4. Connect the cables ASH-01/U with
the hermetic installation junction box
according to installing diagram.
5. Switch on the power supply from the
mains.
6. Take out the rubber hole plug cove-
ring the adjustment of the switch on
threshold potentiometer.
7. Adjust the demanded switch on time
by means of a potentiometer.
8. Put back the rubber hole plug cove-
ring the potentiometer.
FUNCTIONING
After proper mounting and installation
the device is ready to work. Releasing the
system with the monostable pushbutton
causes the lighting to switch on for the
preset time. After the preset time is over
the lighting is automatically switched off
till its another release. The staircase lighting time delay switch cooperates with
3-wire or 4-wire system. While mounting
the device pay attention the release and
load systems are properly connected,
otherwise the device can be irreparably
damaged. Because of no anti-blocking
system the light is constantly switched on
in cases the pushbutton is blocked.
L(+)
12 ÷ 240 V AC/DC
N(-)
k
c
a
l
b
e
u
l
b
g
r
e
y
b
r
o
w
n
3 wire system 4 wire system
EXAMPLE OF INSTALLATION
L(+) N(-)
k
c
a
l
b
e
u
l
b
g
r
e
y
b
r
o
w
n
k
c
a
l
b
e
u
l
b
g
r
e
y
b
r
o
w
n
INNER DIAGRAM
czarny
black
Typical application:
The staircase lighting time delay switch ASH-01/U operating the staircase lighting
works in 3-wire installation. Push-buttons (equipped with illumination) can be connected parallely.
szary
grey
brąz.
brown
nieb.
blue
DIMENSIONS TIME COURSE PRODUCT FAMILY
ASH-01/U belongs to staircase time delay
t
t ttt
RELAY CAPACITY
switches ASx family.
Voltage version:
24V - 24 V AC/DC
U - 12÷240 V AC/DC
Device version:
01 - basic, three or four - wire
02 - anti blocking function
03 - anti blocking function and ON/
10 - anti blocking function, uent
Casing type:
M - modular version (TH 35 DIN rail)
N - surface mounting
H - surface and hermetic casing
P - surface junction box 60 version