AUTOMATIC PHASE SWITCH FAZ APM-20
ZAMEL Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04
www.zamel.com, e-mail: marketing@zamel.pl
INSTRUCTION MANUAL
DESCRIPTION
The automatic phase switch APM-20 is
designed to ensure uninterrupted power
supply of a one-phase receiver in case
of phase loss or RMS voltage value decrease below the norm. The main advantage of the device is a small relative
voltage measurement error, which does
not exceed 1% even for highly distorted
waves. The above is a result of an implementation of the True RMS converter.
The APM-20 device is supplied by three
phases L1, L2, L3 with the L1 phase as
the prior one. The voltage switch threshold (180 V AC), switching time (150
ms) and voltage hysteresis (10 V AC)
have default settings and cannot be
changed by a user. Each phase parameters are optically signalled by means of
LEDs on the front panel of the device.
The internal system of output contacts
assures an increased resistance to their
bonding and protects against phase-to-
-phase short circuit. The maximum output capacity should not exceed 16 A for
AC1 class receivers. APM-20 is mounted
in distribution boards (TH35 rail). The ca-
sing has the width of 2 modules.
FEATURES
● maintaining uninterrupted power supply of a single-phase receiver,
● three-phase power supply L1-L2-L3
(L1-priority phase),
● automatic phase switching during power supply failure or its value decrease below 180 V AC,
● switching time at a level of 150 ms
● voltage switch threshold, switching
time and voltage hysteresis have default settings and cannot be changed
by a user,
● high voltage measuring accuracy – relative error < 1%,
● voltage measurement of distorted signals (True RMS),
● output load– maximum 16 A for AC1
loads,
● signalling the parameters of particular
voltage supply phases – 3 x LEDs,
● mounting in distribution boards (TH35
rail) – width of 2 modules.
TECHNICAL PARAMETERS
Power supply terminals: L1, L2, L3, N
Nominal supply voltage: 3 x 230 V AC + N
Nominal frequency: 50 Hz
Nominal power consumption: 1,7 W / 3,8 VA – per 3 phases
Priority phase: L1
Signalling parameters of power supply phases: 3 x red LED (L1, L2, L3)
Output terminals: L, L, N, N
Nominal output voltage: 230 V AC
Maximum output capacity: 16 A for AC1 class devices
Switch threshold for L1, L2, L3: <180 V AC
Voltage hysteresis: 10 V AC
Switching time: ~150 ms
Względny błąd pomiaru napięcia: <1%
Distorted signal measurement:
Number of terminal clamps:
Cross-section of connecting cables:
Operating temperature range:
Operating position:
Casing mounting:
Casing protection degree:
Protection level:
Overvoltage category:
Pollution degree:
Surge voltage:
Dimensions: monomodular 90x35x66 mm
Reference standard: PN-EN 60669-1, PN-EN 60669-2-1,
yes – True RMS
8
0,2 do 2,5 mm
-20 ÷ +45 °C
free
TH35 rail (2-MOD casing)
IP20
II
II
2
1 kV (PN-EN 61000-4-5)
Weight: 0,14 kg
PN-EN 61000-4-2,3,4,5,6,11
2
APPEARANCE
Power supply terminals
Signalling parameters
of power supply phases
The symbol means selective
collecting of electrical and
electronical equipment. It
is forbidden to put the used
equipment together with other
waste.
Output terminals
(to connect the load)
plik: inst_ext_gb_apm-20 | modykacja: 30.12.2016

MOUNTING
CONNECTION
1. Disconnect power supply by the phase
fuse, the circuit-breaker or the switch-
-disconnector combined to the proper
circuit.
2. Check if there is no voltage on connection cables by means of a special measure equipment.
3. Mount the APM-20 device on the TH35
rail.
4. Connect the cables with the terminals in
accordance with the installing diagram.
5. Switch on the power supply from the
mains.
6. Check if the device operates correctly.
CASING DIMENSIONS
L1
L2
L3
N
FUNCTIONIG
After power supply is applied, the device is ready to operate. If the voltage on the L1 phase
is higher than 180 V AC, then the receiver is supplied from another phase. If the voltage on
the L1 drops below 180 V AC, then there is an automatic switch to the L2 phase in <150
ms. Analogically, if the L2 phase voltage drops below 180 V AC, then there is an automatic
switch to the L3 phase. In case the L3 phase voltage is below 180 V AC, there is a power
supply switch off for the receiver connected to this output. If the given phase is switched off
due to a voltage drop of <180 V AC, then it is switched on again at a value of >190 V AC
(hysteresis 10 V). The L1 is the priority phase. In case its parameters are correct, then this
phase will supply the receiver. For example, if a receiver is supplied by the L3 phase and, at
the same time, the L1 has correct parameters again, then an automatic switch to the L1 phase supply will occur. If the voltage on a particular phase is >180 V AC, the appropriate LED
switches on. This LED switches off if voltage drops below 180 V AC. The phase switching
on and switching off times are the same and equals about 150 ms.
CAUTION
The device is designed for single-phase installation and must be installed
in accordance with standards valid in
a particular country. Installation, connection and control should be carried
out by a qualied electrician staff, who
act in accordance with the instruction
manual and the device functions. In
case of casing dismantling, the guarantee is lost and an electric shock may
occur. Before installation make sure
the connection cables are not under
voltage. The cruciform head screwdriver 3,5 mm should be used to install
the device. Improper transport, stora-
ge, and use of the device inuence its
wrong functioning. It is not advisable
to install the device in the following
cases: if any device part is missing
or the device is damaged or deformed. In case of improper functioning
of the device contact the producer.
WARRANTY CARD
There is a 24-month guarantee on the product
Salesman stamp and signature, date of sale
Operation – time diagram:
L1
190 V AC
180 V AC
L2
190 V AC
180 V AC
L3
190 V AC
180 V AC
OUT
L1
180 V AC
150 ms
OUT
OFF
L1L2 L2L3 L3
OUT
OFF
Internal connection arrangement – PK1, PK2, PK3 relays:
PK1 PK2 PK3
1. ZAMEL Sp. z o.o. assures a 24-month guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions:
a) mechanical damage during transport, loading / unloading or under other circumstances,
b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modications made by the PURCHASER or any third parties to the product or any other
devices required for the product functioning,
d) damage caused by Act of God or any other incidents independent of the manufacturer – ZAMEL Sp z o.o.
e) supply sources (batteries) included in the device during selling (if they are included).
3. The PURCHASER shall lay any claims in writing in the place of purchase or to ZAMEL Sp. z o.o.
4. ZAMEL Sp. z o.o. is liable for processing any claim according to current Polish legislation.
5. ZAMEL Sp. z o.o. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or
otherwise are not affected by this warranty.