Zamel APM-20 Instruction Manual

AUTOMATIC PHASE SWITCH FAZ APM-20
ZAMEL Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04 www.zamel.com, e-mail: marketing@zamel.pl
INSTRUCTION MANUAL
DESCRIPTION
The automatic phase switch APM-20 is
designed to ensure uninterrupted power
supply of a one-phase receiver in case of phase loss or RMS voltage value de­crease below the norm. The main ad­vantage of the device is a small relative
voltage measurement error, which does
not exceed 1% even for highly distorted waves. The above is a result of an im­plementation of the True RMS converter. The APM-20 device is supplied by three
phases L1, L2, L3 with the L1 phase as the prior one. The voltage switch thre­shold (180 V AC), switching time (150 ms) and voltage hysteresis (10 V AC)
have default settings and cannot be changed by a user. Each phase parame­ters are optically signalled by means of
LEDs on the front panel of the device.
The internal system of output contacts assures an increased resistance to their bonding and protects against phase-to-
-phase short circuit. The maximum out­put capacity should not exceed 16 A for AC1 class receivers. APM-20 is mounted in distribution boards (TH35 rail). The ca-
sing has the width of 2 modules.
● maintaining uninterrupted power sup­ply of a single-phase receiver,
● three-phase power supply L1-L2-L3
(L1-priority phase),
● automatic phase switching during po­wer supply failure or its value decre­ase below 180 V AC,
● switching time at a level of 150 ms
● voltage switch threshold, switching
time and voltage hysteresis have de­fault settings and cannot be changed by a user,
● high voltage measuring accuracy – re­lative error < 1%,
● voltage measurement of distorted si­gnals (True RMS),
● output load– maximum 16 A for AC1
loads,
● signalling the parameters of particular voltage supply phases – 3 x LEDs,
● mounting in distribution boards (TH35 rail) – width of 2 modules.
TECHNICAL PARAMETERS
Power supply terminals: L1, L2, L3, N
Nominal supply voltage: 3 x 230 V AC + N
Nominal frequency: 50 Hz
Nominal power consumption: 1,7 W / 3,8 VA – per 3 phases
Priority phase: L1
Signalling parameters of power supply phases: 3 x red LED (L1, L2, L3)
Output terminals: L, L, N, N
Nominal output voltage: 230 V AC
Maximum output capacity: 16 A for AC1 class devices
Switch threshold for L1, L2, L3: <180 V AC
Voltage hysteresis: 10 V AC
Switching time: ~150 ms
Względny błąd pomiaru napięcia: <1%
Distorted signal measurement:
Number of terminal clamps:
Cross-section of connecting cables:
Operating temperature range:
Operating position:
Casing mounting:
Casing protection degree:
Protection level:
Overvoltage category:
Pollution degree:
Surge voltage:
Dimensions: monomodular 90x35x66 mm
Reference standard: PN-EN 60669-1, PN-EN 60669-2-1,
yes – True RMS
8
0,2 do 2,5 mm
-20 ÷ +45 °C
free
TH35 rail (2-MOD casing)
IP20
II
II
2
1 kV (PN-EN 61000-4-5)
Weight: 0,14 kg
PN-EN 61000-4-2,3,4,5,6,11
2
APPEARANCE
Power supply terminals
Signalling parameters
of power supply phases
The symbol means selective collecting of electrical and electronical equipment. It is forbidden to put the used equipment together with other waste.
Output terminals (to connect the load)
plik: inst_ext_gb_apm-20 | modykacja: 30.12.2016
MOUNTING
CONNECTION
1. Disconnect power supply by the phase
fuse, the circuit-breaker or the switch-
-disconnector combined to the proper circuit.
2. Check if there is no voltage on connec­tion cables by means of a special me­asure equipment.
3. Mount the APM-20 device on the TH35 rail.
4. Connect the cables with the terminals in accordance with the installing diagram.
5. Switch on the power supply from the
mains.
6. Check if the device operates correctly.
CASING DIMENSIONS
L1 L2 L3 N
FUNCTIONIG
After power supply is applied, the device is ready to operate. If the voltage on the L1 phase is higher than 180 V AC, then the receiver is supplied from another phase. If the voltage on the L1 drops below 180 V AC, then there is an automatic switch to the L2 phase in <150 ms. Analogically, if the L2 phase voltage drops below 180 V AC, then there is an automatic switch to the L3 phase. In case the L3 phase voltage is below 180 V AC, there is a power supply switch off for the receiver connected to this output. If the given phase is switched off due to a voltage drop of <180 V AC, then it is switched on again at a value of >190 V AC (hysteresis 10 V). The L1 is the priority phase. In case its parameters are correct, then this phase will supply the receiver. For example, if a receiver is supplied by the L3 phase and, at the same time, the L1 has correct parameters again, then an automatic switch to the L1 pha­se supply will occur. If the voltage on a particular phase is >180 V AC, the appropriate LED switches on. This LED switches off if voltage drops below 180 V AC. The phase switching on and switching off times are the same and equals about 150 ms.
CAUTION
The device is designed for single-pha­se installation and must be installed
in accordance with standards valid in
a particular country. Installation, con­nection and control should be carried
out by a qualied electrician staff, who act in accordance with the instruction
manual and the device functions. In case of casing dismantling, the guaran­tee is lost and an electric shock may occur. Before installation make sure the connection cables are not under voltage. The cruciform head screwdri­ver 3,5 mm should be used to install the device. Improper transport, stora-
ge, and use of the device inuence its wrong functioning. It is not advisable to install the device in the following
cases: if any device part is missing or the device is damaged or defor­med. In case of improper functioning of the device contact the producer.
WARRANTY CARD
There is a 24-month guarantee on the product
Salesman stamp and signature, date of sale
Operation – time diagram:
L1
190 V AC
180 V AC
L2
190 V AC
180 V AC
L3
190 V AC
180 V AC
OUT
L1
180 V AC
150 ms
OUT OFF
L1L2 L2L3 L3
OUT OFF
Internal connection arrangement – PK1, PK2, PK3 relays:
PK1 PK2 PK3
1. ZAMEL Sp. z o.o. assures a 24-month guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions:
a) mechanical damage during transport, loading / unloading or under other circumstances, b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modications made by the PURCHASER or any third parties to the product or any other
devices required for the product functioning,
d) damage caused by Act of God or any other incidents independent of the manufacturer – ZAMEL Sp z o.o.
e) supply sources (batteries) included in the device during selling (if they are included).
3. The PURCHASER shall lay any claims in writing in the place of purchase or to ZAMEL Sp. z o.o.
4. ZAMEL Sp. z o.o. is liable for processing any claim according to current Polish legislation.
5. ZAMEL Sp. z o.o. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or
otherwise are not affected by this warranty.