• Cooling Only and Gas/Electric configurations available
• Scroll Compressors
• Up to 15.4 SEER and 12.2 EER on the Energy Star
Compliant Energy Level
• Up to 13.0 SEER and 11.2 EER on the ASHRAE 90.1
Compliant Standard Efficiency Level
• State of the art Microprocessor Controls with specific
programming for unitary product applications
Options and Accessories
• Economizers with Barometric Relief
• Louvered Hail Guards
• Non-fused Disconnect
• Power Exhaust
• High Altitude Heating Conversion Kits
• Flue Exhaust Extension Kit
• Flue Heat Shield
• MicroChannel Condenser Coils
• Evaporator coils utilize copper tube/aluminum fin design
for proven reliability and performance.
• TXV (Thermostatic Expansion Valve) Standard on:
(ASHRAE 90.1 Compliant Standard Efficiency Level 5 -
12.5 ton models and Energy Star Compliant Efficiency
Level 3 - 10 ton models)
• Single-stage Cooling (3 -6 ton models)
• Two-stage Cooling (7.5 - 12.5 ton models)
• Alternate Motor and Drives
• Optional Stainless Steel Heat Exchanger (Standard on 35 Ton Low-NOx Models)
• Thru-The-Base Connections for power, gas and control
wiring.
• IntelliSpeed
meet ASHRAE 90.1-2010 requirements (10-12.5 ton
models)
• Field Installed Electric Heat Kit (ZX- 3-6 ton, ZY- 3-5 ton),
Installation Instruction for the Electric Heat Kits may be
found in the Electric Heat Kits.
TM
with Premium Efficiency indoor motors to
2Johnson Controls Unitary Products
Component Location
B
D
E
F
G
H
J
A
B
C
E
F
G
Cooling With Gas Heat (3 Through 5 Ton)
1068152-YTG-H-0714
Click on the letters to see a description of the features.
Johnson Controls Unitary Products3
1068152-YTG-H-0714
Features and Benefits
Two Tiers of Efficiency - Entry level efficiency provides a cost
effective 13 SEER/11.2 EER product that meets ASHRAE 90.1
requirements. The Mid-efficiency meets the requirements
Energy Star that exceeds 15 SEER and 12 EER. Gas/electric
units have electronic spark ignition and power vented
combustion steady state efficiencies of 80%. These efficiencies
meet or exceed all legislated minimum levels providing lower
operating costs.
for
A All models utilize a scroll compressor that are
environmentally friendly by utilizing R-410A refrigerant. Use of
the scroll compressor technology means a simple internal
design, fewer moving parts, equating to a quiet, reliable, easy to
service and efficient system. Internal compressor protection is
standard and compressors include protection to prevent liquid
damage.
BBalanced outdoor fan design makes for a quieter unit -
The outdoor condenser fans are dynamically balanced for
better performance and reliability. The direct drive fan design
mounted to the fan grill allows for quick and easy service.
Where other's components might fail at extreme temperatures
UPG's units are tested and rated up to 125°F ambient cooling
operation.
Total system design - A TXV is used for precise metering on
the 6-12.5 Ton products and a fixed orifice is used to keep the
cost of the product down on the 3-5 ton product. Two
independent refrigerant circuits and compressors are used on
the 7.5- 12.5 ton units for economical and precise control. A
single circuit, single compressor design is used on the 3-6 ton
units for cost effectiveness and reliability without compromising
quality.
System Protection - Liquid line filter-driers, high and low
pressure safeties are standard on each independent refrigerant
circuit. Suction line sensors monitor temperature to prevent
possible liquid flood back to the compressors and also protect
against loss of charge and coil frosting.
4Johnson Controls Unitary Products
C Convertible Filter Rack - No tools required for easy field
conversion of the filter rack to accommodate either 2” or 4”
filters. Units will ship with MERV 4 throwaway filters standard;
however MERV 8 and MERV 13 filters can be easily added
through the tool-free filter access panel to meet LEED
requirements. Refer to physical data tables for filter size details.
D Units will come with the new state of the art Simplicity SE
(Smart Equipment) control system. The new unit control
incorporates the best of the already proven Simplicity™ unitary
controls and creates a more robust, intelligent control. The goal
of this control is to utilize cutting edge technology making the
equipment easier to install, operate, and service. All units are
Factory commissioned, configured, and run tested.
Versatile - The Simplicity SE control can be configured to use
with a standard thermostat (easy to connect screw terminals), A
zone sensor, or can be setup to communicate with multiple BAS
communication protocols to integrate with building automation
systems.
1068152-YTG-H-0714
are monitored on gas and electric heating units. The control
also monitors the voltage supplied to the unit and will protect
the unit if low voltage due to a brown out, or other electrical
issue occurs.
Low Ambient - An integrated low-ambient control allows units
to operate in the cooling mode down to 0°F outdoor ambient
without additional components or intervention. Optionally, the
control board can be programmed to lockout the compressors
when the outdoor air temperature is low or when free cooling is
available.
Anti-Short Cycle Protection - To aid compressor life, an antishort cycle delay is incorporated into the standard control.
Compressor reliability is further ensured by programmable
minimum run times. For testing, the anti-short cycle delay can
be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable.
Furthermore, the heating and cooling fan delay times are
independent of one another. All units are programmed with
default values based upon their configuration of cooling and/or
heating capacity.
Nuisance Trip Protection and Three Strikes - To prevent
nuisance calls, the control board uses a three times, you're out
philosophy. The high, low-pressure switch, anti-freeze
protection, low voltage or heating high limit must trip three times
within two hours before the unit control board will lock out the
associated compressor. The same safety must trip three times
before a hard lockout will occur.
Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key temperature
readings thus reduce field installed complexity.
On-board USB Port - The new control comes with a long list of
features including data logging, current and previous system
faults and software update capabilities using the on board USB
port and common flash drive. Energy use monitoring
capabilities allow custom tailoring to allow a system to work
more efficiently at all times and occupancy levels. Self test and
start-up reports also available from the board VIA the USB port.
Embedded LCD Display - The board has a easy to read, builtin LCD display and easy to use navigation joystick and buttons
allowing the user to quickly navigate the menus displaying unit
status, options, current function, supply, return and outdoor
temperatures, fault codes and other information.
Safety Monitoring - The control monitors the outdoor, supply,
and return air temperatures and the high and low pressure
switch status on the independent refrigerant circuits. On units
with heating the gas valve and high temperature limit switches
E Robust design - Each unit is designed with an embossed
top to increase structural support and ensure rigidity. The unit
has a powder paint exterior finish including a industry leading
1000 hour salt spray rating. All units are painted with a long
lasting, powder paint that stands up over the life of the unit.
Johnson Controls Unitary Products5
1068152-YTG-H-0714
F Full Perimeter base rail that fits on many existing curbs
with the stability to withstand an earthquake - This product
was designed with the replacement market in mind which is
why it will fit on many existing curbs in the field but it also takes
into account the new construction market by being versatile and
sturdy. This unit is equipped with heavier gauge and
innovatively designed base rails to prevent damage from
transporting and rigging.
H Rigid Mounted Blower Assembly - Dynamically balanced
indoor fans ensure better performance and reliability. Large
access panels for easier access, service, and maintenance.
X13 Direct drive (Standard Static Option) and belt drive
(Medium Static and High Static Options) options available on 35 ton products. The belt drive option is standard on 6-12.5 ton
products. Low, Medium, and High Static drive options for airflow
versatility up to 2" ESP with no field installed drive packages
necessary. The X13 motor technology offers several benefits w/
respect to efficiency, operation, comfort, and cost when
compared to other motors. Premium efficiency indoor motors
are standard on ZY06 and ZX14. The IntelliSpeed option is
available on 10 & 12.5 ton products to meet ASHRAE 90.1 and
Title 24 Requirements. The blower section includes a dual
density insulation for indoor air quality.
G Coils - All units utilize Micro-Channel "all-aluminum"
condenser coils that provides improved heat transfer
capabilities and reduced refrigerant charge volumes. This
equates to all units meeting LEED EA Credit 4 Requirements
for Enhanced Refrigerant Management. (Make sure to use the
EA 4 Credit 4 Calculator available at UPG net.com to ensure
that the entire project meets the requirements). MicroChannel
coils are also much easier to clean than your typical fin/tube
designs.
All evaporator coils utilize copper tube with aluminum fin design
for proven reliability and performance.
JBalanced Heating - The two stage gas heating offers
ultimate heating comfort with a balance between 1st and 2nd
stage gas heating. The first stage of a two stage gas heat
option provides approximately 70% of the heating capacity in all
3-12.5 tons two stage gas heat models. Balanced heating
allows the unit to better maintain desired temperatures and
helps saves energy. Low-NOx comes standard with a stainless
steel heat exchanger to meet California environmental
requirements. The heat exchanger section includes foil faced
insulation that is not only environmentally friendly but meets all
NFPA codes.
6Johnson Controls Unitary Products
1068152-YTG-H-0714
Warranty - All models include a 1-year limited warranty on the
complete unit. Compressors and electric heater elements each
carry a 5-year warranty. Aluminized steel heat exchangers
carry a 10-year warranty and stainless steel heat exchangers
carry a 15- year warranty.
Factory Installed Options
(Nomenclature Digit Position)
Airflow Options (8)
Alternate Indoor Blower Motor - For applications with high
static restrictions, units are offered with optional indoor motors
providing higher external static capability and/or higher airflow,
depending upon the installer's needs.
• A=Standard Static (Direct Drive for 3-5 ton; Belt Drive
for 6-12.5 Ton)
VFD/VAV Options (9)
IntelliSpeed™ Supply Fan Control Option (ASHRAE 90.1
compliant, section 6.4.3.10) - Units configured with the
IntelliSpeed™ Supply Fan Option will contain a VFD for
variable volume supply fan operation. This option allows the
supply fan RPM to vary based on the number of compressors
or heating stages energized. The economizer's minimum
position is also configurable.
• 1=None (Comes with standard constant volume
controls)
• 3=VFD IntelliSpeed
Coil Options (10)
E-Coat Coils – Coils are coated with an epoxy polymer
coating to protect against corrosion. A 3-year warranty is
added when this option is selected.
• A=Standard Indoor & Outdoor Coils (fin/tube design on
indoor coil and MicroChannel design used on outdoor
coil with no E-Coat coating added).
• B=Standard Indoor Coil & E-Coat Coil Outdoor Coil (fin/
tube design on indoor coil and MicroChannel design
used on outdoor coil. E-Coat coating added to outdoor
coil)
• C= E-Coat Indoor Coil & Standard Outdoor Coil (fin/tube
design on indoor coil and MicroChannel design used on
outdoor coil. E-Coat coating added to indoor coil)
• D= E-Coat Indoor Coil & Outdoor Coil (fin/tube design
on indoor coil and MicroChannel design used on
outdoor coil. E-Coat coating added to indoor and
outdoor coil)
Controls (11)
Simplicity SE (Smart Equipment) or SES - This is the
Standard microprocessor control with capabilities to work with
a sensor or thermostat only. SES with BAS includes
communication board with BACnet open-protocol system.
•A=SES
• B=SES + BAS (Standard Simplicity SE with BacNet
communication)
Sensor Options (12)
• 1=None (Units come standard with factory installed
supply air, return air, and outdoor ai r te mpe rature
sensors)
Economizer/Damper (13)
Down flow Economizers (with barometric relief) - All units
offer a variety of optional factory installed economizers that are
shipped, installed and wired with AMCA 511 Licensed Class
1A low leak dampers designed to exceed ASHRAE 90.1-2010
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3 cfm/
sq. ft. at 1" of static pressure. Each economizer goes through a
rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual
enthalpy (with field installed kit) can be selected. All
economizer options are fully integrated into the Simplicity SE
controls. The economizer has spring retu rn, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the return
air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provid es a se cond input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control are
provided).
Dry Bulb Economizer - Economizer operation is enabled by
the outdoor air temperature bein g l ess than the setpoint of the
economizer module.
Enthalpy Economizer - The added outdoor air enthalpy
sensor enables economizer operation if the outdoor enthalpy
is less than the setpoint of the economizer logic module.
• A=None
• B=Dry Bulb Economizer
• C=Enthalpy Economizer
Convenience Outlet (14)
Convenience Outlet - (Non-Powered) - This option locates a
120V single-phase GFCI outlet with cover, on the corner of the
unit housing adjacent to the compressors. The Non-powered
option requires the installer to provide the 120V single-phase
power source and wiring. Factory installed option only.
•1=None
• 2=Non-powered Convenience Outlet
Johnson Controls Unitary Products7
1068152-YTG-H-0714
Electrical Options (15)
Disconnect Switch - Gas heat units and cooling units
equipped with electric heat include an optional, non-fused
disconnect properly sized for the unit is provided. For cooling
only units, a switch sized to the largest electric heat available
for the particular unit is provided. Factory installed option only.
Thru-the-pan Utility Connections - Special design for thru
the base and thru the curb applications insuring a sealed
connection to avoid water entry.
Cabinet Options (16)
Louvered Hail Guard - This kit includes a decorative
louvered panel which installs over the outside condenser coil
and prevents damage to the coil fins from hail strikes.
• 1=None
• 2=Louvered Panels
Field Installed Accessories
• Down flow Economizers/Horizontal Economizers
(with barometric relief) - All units offer a variety of field
installed economizers that are installed and wired with
AMCA 511 Licensed Class 1A low leak dampers designed
to exceed ASHRAE 90.1-2010 and the International
Energy Conservation Code (IECC) certification
requirements by achieving leakage rates of 3 cfm/sq. ft. at
1" of static pressure. Each economizer goes through a
rigorous 60,000 cycle test. Dry bulb, single enthalpy, and
dual enthalpy (with field installed kit) can be selected. All
economizer options are fully integrated into the Simplicity
SE controls. The economizer has spring return, fully
modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy input. The dual
enthalpy kit provides a second input used to monitor the
return air (field installed). The installer needs only to
assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and
control are provided).
• Dry Bulb Economizer - Economizer operation is enabled
by the outdoor air temperature being less than the
setpoint of the economizer module.
• Single Enthalpy Control, Accessory for Economizer -
All field installed economizers will come standard as a dry
bulb economizer. This kit adds an outdoor air enthalpy
sensor which enables economizer operation if the outdoor
enthalpy is less than the setpoint of the economizer logic
module.
• Dual Enthalpy Control, Accessory for Economizer - All
field installed economizers will come standard as a dry
bulb economizer. This kit adds an outdoor air enthalpy
sensor and return air enthalpy sensor which enables
economizer operation if the outdoor enthalpy is less than
the setpoint of the economizer logic module.
• Power Exhaust - This accessory installs in the unit with a
down flow economizer or in the ductwork for a horizontal
application.
• Louvered Hail Guard - This kit includes a decorative
louvered panel which installs over the outside condenser
coil and prevents damage to the coil fins from hail strikes.
• Flue Exhaust Extension Kit - In locations where wind or
weather conditions may interfere with proper exhausting
of furnace combustion products, this kit can be installed to
prevent the flue exhaust from entering nearby fresh air
intakes.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
• Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available in
14 and 24 heights.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All 7.5
thru 12.5 ton units operate with two-stage heat/two-stage
cool or two-stage cooling only thermostats, depending
upon unit configuration.
8Johnson Controls Unitary Products
Nomenclature
ZX G 04 D 2 A 1A 1 1 1 A 1
Product Category
ZX = Pkg AC R410A ASHRAE 90.1 Efficiency
ZY = Pkg AC R410A Energy Star Efficiency
A = Standard Static
Airflow
B = Medium Static
C = High Static
Product Generation
1 = First Generation
Heat Type (3)
E = No Heat
G = Gas Heat
D = Low Heat
E = Medium Heat
F = High Heat
L = Low Heat (Low NOx)
M = Medium Heat (Low NOx)
N = High Heat (Low NOx)
R = Low Heat (Stainless Steel)
S = Medium Heat (Stainless Steel)
T = High Heat (Stainless Steel)
Gas Heat
Nominal Cooling Capacity
04 = 3 Ton
05 = 4 Ton
06 = 5 Ton
07 = 6 Ton
08 = 7-1/2 Ton
09 = 8-1/2 Ton
12 = 10 Ton
14 = 12-1/2 Ton (Standard Efficiency Only)
A = Standard Indoor & Outdoor Coils
B = Standard Indoor Coil & ElectroFin Outdoor Coil
C = E-Coat Indoor Coil & Standard Outdoor Coil
D = E-Coat Indoor & Outdoor Coils
3-12.5 Ton Model Number Nomenclature
Heat Size
A = No Heat (Cooling Only)
A = Simplicity™ SE
B = Simplicity™ SE + BAS
Coil Options
1 = 208/230-1-60 (3-5 Ton Only)
Convenience Outlet
Sensor Options
Controls
1A
A
Note: Not all options may be available. Contact
local distributor.
1068152-YTG-H-0714
Johnson Controls Unitary Products9
1068152-YTG-H-0714
Accessories
Accessory Kit
Number
2EE04706124 Econ, DB, Vertical Flow, Small FootprintZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06All
2EE04706224 Econ, DB, Vertical Flow, Large FootprintZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 All
2EE04706324 Econ, DB, Horizontal Flow, Small Footprint, Short CabinetZX04, ZX05, ZX06, ZY04All
2EE04706424 Econ, DB, Horizontal Flow, Small Footprint , Tall CabinetZX07, ZY05, ZY06All
2EE04706524 Econ, DB, Horizontal Flow, Large Footprint, Short CabinetZX08, ZY07All
2EE04706624 Econ, DB, Horizontal Flow, Large Footprint, Tall CabinetZX09, ZX12, ZX14, ZY08, ZY09, ZY12All
2EC0401Kit, Single Enthalpy Field InstalledAllAll
2EC0402Kit, Dual Enthalpy Field InstalledAllAll
1HG0419Hail Guard Kit Small Footprint, Short CabinetZX04, ZX05, ZX06, ZY04All
1HG0420Hail Guard Kit Small Footprint, Tall CabinetZX07, ZY05, ZY06All
1HG0421Hail Guard Kit Large Footprint, Short CabinetZX08, ZY07All
1HG0422Hail Guard Kit Large Footprint, Tall CabinetZX09, ZX12, ZX14, ZY08, ZY09, ZY12All
1RC0456Curb Rigid 14" Small FootprintZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06All
1RC0457Curb Rigid 14" Large FootprintZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 All
1RC0458Curb Rigid 24" Small FootprintZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06All
1RC0459Curb Rigid 24" Large FootprintZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 All
2PE04704206 Power Exhaust Vert Flow Small Footprint 208V-230V 1-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06208/230-1-60
2PE04704225 Power Exhaust Vert Flow Small Footprint 208V-230V 3-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06208/230-3-60
2PE04704246 Power Exhaust Vert Flow Small Footprint 460V 3-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06460-3-60
2PE04704258 Power Exhaust Vert Flow Small Footprint 575V 3-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06575-3-60
2PE04704306 Power Exhaust Vert Flow Large Footprint 208V-230V 1-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 208/230-1-60
2PE04704325 Power Exhaust Vert Flow Large Footprint 208V-230V 3-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 208/230-3-60
2PE04704346 Power Exhaust Vert Flow Large Footprint 460V 3-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 460-3-60
2PE04704358 Power Exhaust Vert Flow Large Footprint 575V 3-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 575-3-60
2PE04704406 Power Exhaust Horiz Flow Small Footprint 208V-230V 1-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06208/230-1-60
2PE04704425 Power Exhaust Horiz Flow Small Footprint 208V-230V 3-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06208/230-3-60
2PE04704446 Power Exhaust Horiz Flow Small Footprint 460V 3-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06460-3-60
2PE04704458 Power Exhaust Horiz Flow Small Footprint 575V 3-phZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06575-3-60
2PE04704506 Power Exhaust Horiz Flow Large Footprint 208V-230V 1-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 208/230-1-60
2PE04704525 Power Exhaust Horiz Flow Large Footprint 208V-230V 3-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 208/230-3-60
2PE04704546 Power Exhaust Horiz Flow Large Footprint 460V 3-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 460-3-60
2PE04704558 Power Exhaust Horiz Flow Large Footprint 575V 3-phZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 575-3-60
1TB0401Small Footprint Thru The Base Electrical & Thru The Curb Gas ZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06All
1TB0402Large Footprint Thru The Base Electrical & Thru The Curb Gas ZX08, ZX09, ZX12, ZX14, ZY07, ZY08, ZY09, ZY12 All
1TB0403Small Footprint Thru The Base Electrical & GasZX04, ZX05, ZX06, ZX07, ZY04, ZY05, ZY06All
1TB0404Large Footprint Thru The Base Electrical & GasZX08, ZY07, ZX09, ZX12, ZX14, ZY08, ZY09, ZY12 All
Gross Capacity @ AHRI A point (Btu)3820038200
AHRI net capacity (Btu)3460034600
EER1111
SEER1313
IEER-IEER IntelliSpeed-Nominal CFM12001200
System power (KW)2.82.8
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 13-133-13
System 2--
TypeScrollScroll
Quantity11
Unit Capacity Steps (%)100100
Face area (Sq. Ft.)16.316.3
Rows11
Fins per inch2323
Tube diameter (in./MM).63/16.63/16
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)5.55.5
Rows22
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlOrificeOrifice
12Johnson Controls Unitary Products
ZX04 Physical Data (Continued)
Component
Nominal Tonnage33
Quantity of fans11
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
DIRECT DRIVE
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors11
Motor HP each1/41/4
No. speeds11
RPM11001100
Nominal total CFM38003800
Airflow OptionAA
Quantity11
Fan Size (Inch)10 x 1010 x 10
TypeCentrifugalCentrifugal
Motor HP3/43/4
RPM10501050
Airflow OptionBCBC
Quantity1111
Fan Size (Inch)10 x 1010 x 1010 x 1010 x 10
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VL341VL44
Blower SheaveAK46AK46AK46AK46
BeltA39A40A39A40
Motor HP each1.51.51.51.5
RPM1725172517251725
Frame size56Y56Y56Y56Y
Gross Capacity @ AHRI A point (Btu)4970049700
AHRI net capacity (Btu)4500045000
EER1111
SEER1313
IEER-IEER IntelliSpeed-Nominal CFM16001600
System power (KW)3.63.6
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 13-123-12
System 2--
TypeScrollScroll
Quantity11
Unit Capacity Steps (%)100100
Face area (Sq. Ft.)16.316.3
Rows22
Fins per inch2323
Tube diameter (in./MM).63/16.63/16
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)5.55.5
Rows33
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlOrificeOrifice
14Johnson Controls Unitary Products
ZX05 Physical Data (Continued)
Component
Nominal Tonnage44
Quantity of fans11
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
DIRECT DRIVE
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors11
Motor HP each1/41/4
No. speeds11
RPM11001100
Nominal total CFM38003800
Airflow OptionAA
Quantity11
Fan Size (Inch)10 x 1010 x 10
TypeCentrifugalCentrifugal
Motor HP11
RPM10501050
Airflow OptionBCBC
Quantity1111
Fan Size (Inch)10 x 1010 x 1010 x 1010 x 10
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VL341VL44
Blower SheaveAK46AK46AK46AK46
BeltA39A40A39A40
Motor HP each1.51.51.51.5
RPM1725172517251725
Frame size56Y56Y56Y56Y
Gross Capacity @ AHRI A point (Btu)6370063700
AHRI net capacity (Btu)5900059000
EER1111
SEER1313
IEER-IEER IntelliSpeed-Nominal CFM18001800
System power (KW)4.64.6
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 15-45-4
System 2--
TypeScrollScroll
Quantity11
Unit Capacity Steps (%)100100
Face area (Sq. Ft.)16.316.3
Rows11
Fins per inch2323
Tube diameter (in./MM).79/20.79/20
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)5.55.5
Rows44
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlTXVTXV
16Johnson Controls Unitary Products
ZX06 Physical Data (Continued)
Component
Nominal Tonnage55
Quantity of fans11
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
DIRECT DRIVE
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors11
Motor HP each1/21/2
No. speeds11
RPM10851085
Nominal total CFM45004500
Airflow OptionAA
Quantity11
Fan Size (Inch)10 x 1010 x 10
TypeCentrifugalCentrifugal
Motor HP11
RPM10501050
Airflow OptionBCBC
Quantity1111
Fan Size (Inch)10 x 1010 x 1010 x 1010 x 10
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VL441VL44
Blower SheaveAK41AK41AK41AK41
BeltA37A39A37A39
Motor HP each1.521.52
RPM1725172517251725
Frame size56Y56Y56Y56Y
Gross Capacity @ AHRI A point (Btu)7660076600
AHRI net capacity (Btu)6900069000
EER1111.2
SEER-IEER11.912.1
IEER IntelliSpeed-Nominal CFM23002300
System power (KW)5.15.1
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 16-146-14
System 2--
TypeScrollScroll
Quantity11
Unit Capacity Steps (%)100100
Face area (Sq. Ft.)21.121.1
Rows11
Fins per inch2323
Tube diameter (in./MM).79/20.79/20
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)7.37.3
Rows44
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedInter twined
Refrigerant controlTXVTXV
18Johnson Controls Unitary Products
ZX07 Physical Data (Continued)
Component
Nominal Tonnage66
Quantity of fans11
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors11
Motor HP each1/21/2
No. speeds11
RPM10851085
Nominal total CFM46004600
Airflow OptionABCABC
Quantity111111
Fan Size (Inch)11 x 1011 x 1011 x 1011 x 1011 x 1011 x 10
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VP501VL341VL441VP50
Blower SheaveAK51AK51AK51AK51AK51AK51
BeltA39A40A41A39A40A41
Motor HP each1.5231.523
RPM172517251725172517251725
Frame size56Y56Y56HZ56Y56Y56HZ
Gross Capacity @ AHRI A point (Btu)9400094000
AHRI net capacity (Btu)8500085000
EER1111.2
SEER-IEER11.511.6
IEER IntelliSpeed-Nominal CFM29002900
System power (KW)6.66.6
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 14-84-8
System 24-124-12
TypeScrollScroll
Quantity22
Unit Capacity Steps (%)50/10050/100
Face area (Sq. Ft.)21.121.1
Rows11
Fins per inch2323
Tube diameter (in./MM)1/251/25
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)8.98.9
Rows33
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlOrificeOrifice
20Johnson Controls Unitary Products
ZX08 Physical Data (Continued)
Component
Nominal Tonnage7.57.5
Quantity of fans22
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors22
Motor HP each1/21/2
No. speeds11
RPM10851085
Nominal total CFM76007600
Airflow OptionABCABC
Quantity111111
Fan Size (Inch)15 X 1515 X 1515 X 1515 X 1515 X 1515 X 15
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VP501VL341VL441VP50
Blower SheaveAK74AK74AK74AK74AK74AK74
BeltA47A48A48A47A48A48
Motor HP each1.5231.523
RPM172517251725172517251725
Frame size56Y56Y56HZ56Y56Y56HZ
Gross Capacity @ AHRI A point (Btu)105600105600
AHRI net capacity (Btu)9900099000
EER1111.2
SEER-IEER11.711.9
IEER IntelliSpeed-Nominal CFM33003300
System power (KW)7.707.70
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 15-45-4
System 25-45-4
TypeScrollScroll
Quantity22
Unit Capacity Steps (%)50/10050/100
Face area (Sq. Ft.)25.525.5
Rows11
Fins per inch2323
Tube diameter (in./MM)1/251/25
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)11.111.1
Rows33
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlOrificeOrifice
22Johnson Controls Unitary Products
ZX09 Physical Data (Continued)
Component
Nominal Tonnage8.58.5
Quantity of fans22
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors22
Motor HP each 1/2 1/2
No. speeds11
RPM10851085
Nominal total CFM86008600
Airflow OptionABCABC
Quantity111111
Fan Size (Inch)15 x 1515 x 1515 x 1515 x 1515 x 1515 x 15
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VP501VL341VL441VP50
Blower SheaveAK74AK74AK74AK74AK74AK74
BeltA47A48A50A47A48A50
Motor HP each1.51.531.51.53
RPM172517251725172517251725
Frame size56Y56Y56HZ56Y56Y56HZ
Gross Capacity @ AHRI A point (Btu)125600125600
AHRI net capacity (Btu)116000116000
EER1111.2
SEER-IEER11.812.0
IEER IntelliSpeed14.414.8
Nominal CFM34003400
System power (KW)9.29.2
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 15-125-12
System 25-125-12
TypeScrollScroll
Quantity22
Unit Capacity Steps (%)50/10050/100
Face area (Sq. Ft.)25.525.5
Rows11
Fins per inch2323
Tube diameter (in./MM)1/251/25
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)11.111.1
Rows44
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlOrificeOrifice
24Johnson Controls Unitary Products
ZX12 Physical Data (Continued)
Component
Nominal Tonnage1010
Quantity of fans22
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors22
Motor HP each 1/2 1/2
No. speeds11
RPM10851085
Nominal total CFM86008600
Airflow OptionABCABC
Quantity111111
Fan Size (Inch)15 x 1515 x 1515 x 1515 x 1515 x 1515 x 15
TypeCentrifugalCentrifugal
Motor Sheave1VL441VP501VP561VL441VP501VP56
Blower SheaveAK79AK79BK85AK79AK79BK85
BeltA50A50BX52A50A50BX52
Motor HP each1.5351.535
RPM172517251725172517251725
Frame size56Y56HZ145TY56Y56HZ145TY
Gross Capacity @ AHRI A point (Btu)1450 00145000
AHRI net capacity (Btu)135000135000
EER10.811.0
SEER-IEER1111.2
IEER IntelliSpeed12.7513
Nominal CFM40004000
System power (KW)10.810.8
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 16-86-8
System 26-126-12
TypeScrollScroll
Quantity22
Unit Capacity Steps (%)50/10050/100
Face area (Sq. Ft.)24.924.9
Rows11
Fins per inch2121
Tube diameter (in./MM)1.26/321.26/32
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)11.111.1
Rows44
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlTXVTXV
26Johnson Controls Unitary Products
ZX14 Physical Data (Continued)
Component
Nominal Tonnage12.512.5
Quantity of fans11
Fan diameter (Inch)3030
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors11
Motor HP each1 1/21 1/2
No. speeds11
RPM11401140
Nominal total CFM1060010600
Airflow OptionABCABC
Quantity111111
Fan Size (Inch)15 x 1515 x 1515 x 1515 x 1515 x 1515 x 15
TypeCentrifugalCentrifugal
Motor Sheave1VL441V P501VP561VL441VP501VP56
Blower SheaveAK79AK79BK85AK79AK79BK85
BeltA50A52BX54A50A52BX54
Motor HP each2.93.75.252.93.75.25
RPM175017501750175017501750
Frame size56Z184TZ184TZ56Z184TZ184TZ
Gross Capacity @ AHRI A point (Btu)4070040700
AHRI net capacity (Btu)3600036000
EER1212
SEER1515
IEER-IEER IntelliSpeed-Nominal CFM12001200
System power (KW)2.602.60
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 14-104-10
System 2--
TypeScrollScroll
Quantity11
Unit Capacity Steps (%)100100
Face area (Sq. Ft.)16.316.3
Rows11
Fins per inch2323
Tube diameter (in./MM).63/16.63/16
Circuitry Type2-pass Microchannel2-pass Microchannel
Face area (Sq. Ft.)5.55.5
Rows33
Fins per inch1515
Tube diameter0.3750.375
Circuitry TypeIntertwinedIntertwined
Refrigerant controlTXVTXV
28Johnson Controls Unitary Products
ZY04 Physical Data (Continued)
Component
Nominal Tonnage33
Quantity of fans11
Fan diameter (Inch)2222
TypePropProp
CONDENSER
FAN DATA
EVAP FAN DATA
DIRECT DRIVE
EVAP FAN DATA
BELT DRIVE
Drive typeDirectDirect
Quantity of motors11
Motor HP each1/41/4
No. speeds11
RPM11001100
Nominal total CFM38003800
Airflow OptionAA
Quantity11
Fan Size (Inch)10 x 1010 x 10
TypeCentrifugalCentrifugal
Motor HP3/43/4
RPM10501050
Airflow OptionBCBC
Quantity1111
Fan Size (Inch)10 x 1010 x 1010 x 1010 x 10
TypeCentrifugalCentrifugal
Motor Sheave1VL341VL441VL341VL44
Blower SheaveAK46AK46AK46AK46
BeltA39A40A39A40
Motor HP each1.51.51.51.5
RPM1725172517251725
Frame size56Y56Y56Y56Y
Gross Capacity @ AHRI A point (Btu)5480054800
AHRI net capacity (Btu)4900049000
EER1212
SEER15.415.4
IEER-IEER IntelliSpeed-Nominal CFM16001600
System power (KW)3.503.50
Refrigerant typeR-410AR-410A
Refrigerant charge (lb-oz)
System 16-86-8
System 2--